Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071841R1 SACE Emax 2 E4.2H 4000 Ekip Dip LI four-pole fixed air circuit breaker rated at 4000 A and 690 V AC with 100 kA breaking capacity at 400–440 V AC and electronic long-time and instantaneous protection.
£22,408.21
The ABB E4.2H 4000 Ekip Dip LI 4p FHR, order code 1SDA071841R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 4000 A rated uninterrupted current with the Ekip Dip LI electronic protection release and the high short-circuit performance of the E4.2H frame.
This fixed circuit breaker incorporates the Ekip Dip LI solid-state electronic trip unit, providing long-time overload and instantaneous short-circuit protection. Protection settings are configured using DIP switches, providing a straightforward solution for applications requiring dependable electronic protection without the additional short-time or earth-fault functions of LSI and LSIG releases.
Rated for operation at up to 690 V AC, the E4.2H 4000 provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 690 V AC. It also provides a short-time withstand current of 85 kA for 1 s. This version features a fixed four-pole construction with rear flat horizontal terminals, making it suitable for high-capacity industrial, commercial and infrastructure switchboards.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage distribution circuits against potentially damaging overload and short-circuit conditions. The E4.2H frame combines a substantial 4000 A current rating with high fault-interruption capability, helping protect cables, busbars, switchgear and connected electrical equipment in large power distribution systems.
The Ekip Dip LI electronic trip unit provides long-time overload and instantaneous short-circuit protection with adjustable settings configured through DIP switches. Combined with the E4.2H frame's 100 kA Icu at 400–440 V AC, 85 kA Icu at 690 V AC and 85 kA Icw for 1 s, the 1SDA071841R1 is particularly suited to main switchboards and high-current distribution circuits requiring dependable electronic protection and substantial fault-interruption performance.
| Range | SACE Emax 2 |
|---|---|
| Series | E4.2H |
| ABB order code | 1SDA071841R1 |
| EAN / GTIN | 8015644756918 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated current (In) | 4000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50/60 Hz |
| Number of poles | 4 |
| Neutral pole current | 100% of Iu |
| Short-circuit performance level | H |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) | 100% of Icu |
| Short-time withstand current (Icw) | 85 kA for 1 s; 75 kA for 3 s |
| Trip unit | Ekip Dip LI |
| Release type | Solid-state electronic |
| Protection functions | Long-time (L) and instantaneous (I) |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Integrated earth-fault protection | No |
| Mounting type | Fixed |
| Terminal type | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Auxiliary contacts | 4 |
| Power loss | 465 W |
| Mechanical durability | 15,000 operating cycles |
| Electrical durability | 5000 cycles at up to 440 V AC; 4000 cycles at 500–690 V AC |
| Dimensions (W × H × D) | 510 × 371 × 270 mm |
| Net weight | 70 kg |
| Standard | IEC 60947-2 |
| Country of origin | Italy |
The ABB 1SDA071841R1 is a four-pole air circuit breaker used for switching and protecting high-current low-voltage power distribution circuits against overload and short-circuit conditions.
The E4.2H 4000 Ekip Dip LI 4p FHR has a rated uninterrupted current of 4000 A and a rated operational voltage of up to 690 V AC.
The E4.2H provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 690 V AC, with a short-time withstand current of 85 kA for 1 s.
The Ekip Dip LI electronic trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection, with settings adjusted through DIP switches. This LI configuration does not include integrated short-time or earth-fault protection.
This model is a fixed four-pole circuit breaker with rear flat horizontal terminals and bolt-connected main terminals, designed for installation within compatible low-voltage switchboards and high-capacity power distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine electronic protection with robust switching and high short-circuit performance, providing dependable protection and control for demanding industrial, commercial and infrastructure power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.