Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071822R1 Emax 2 E4.2N 4000 Ekip Dip LSI four-pole fixed air circuit breaker rated at 4000 A and 690 V AC with 66 kA breaking capacity at 400 V AC for high-current low-voltage power distribution and circuit protection.
£18,125.39
The ABB 1SDA071822R1 is a high-current Emax 2 air circuit breaker (ACB) designed for reliable protection, switching and isolation in demanding low-voltage electrical distribution systems. Identified as the E4.2N 4000 Ekip Dip LSI 4p FHR, this four-pole fixed circuit breaker combines a 4000 A rated current with ABB’s Ekip Dip LSI solid-state electronic trip unit.
As part of the ABB SACE Emax 2 series, the E4.2N provides dependable short-circuit performance together with adjustable electronic protection. The Ekip Dip LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, allowing effective coordination with other protective devices throughout industrial and commercial power-distribution systems.
With a rated operational voltage of up to 690 V AC and an ultimate short-circuit breaking capacity of 66 kA at 400 V AC, the 1SDA071822R1 is suitable for high-current installations requiring robust fault protection. Its four-pole fixed construction and rear horizontal terminals make it well suited to integration into low-voltage switchboards, transformer distribution systems and large industrial power assemblies.
Air circuit breakers such as the ABB Emax 2 E4.2N provide switching, isolation and protection for high-current low-voltage electrical systems. The E4.2N 4000 combines a substantial 4000 A current rating with electronic protection, making it suitable for main distribution positions where dependable protection of transformers, conductors, busbars and connected equipment is essential.
The Ekip Dip LSI electronic trip unit provides adjustable long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its wide adjustment ranges allow protection settings to be coordinated with the characteristics of the electrical installation and other protective devices, helping improve selectivity and continuity of service.
| Product group | Emax 2 Air Circuit Breaker |
|---|---|
| Range | SACE Emax 2 |
| Series | E4.2N |
| ABB order code / MPN | 1SDA071822R1 |
| EAN | 8015644756727 |
| Product type | Air circuit breaker |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Number of poles | 4 |
| Neutral pole current | 100% |
| Short-circuit performance level | N |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI |
| Overload release adjustment range | 1600–4000 A |
| Short-time delayed short-circuit adjustment range | 2400–40000 A |
| Instantaneous short-circuit adjustment range | 6000–60000 A |
| Integrated earth-fault protection | No |
| Installation | Fixed |
| Terminal connection | Rear horizontal |
| Main circuit connection | Bolt connection |
| Current type | AC |
| Auxiliary contacts | 4 change-over contacts |
| Trip indication | Yes |
| Protection rating | IP30 |
| Motor operator | Optional |
| Mechanical durability | 15,000 cycles |
| Electrical durability at ≤440 V | 5000 cycles |
| Electrical durability at 500–690 V | 4000 cycles |
| Power loss | 465 W |
| Dimensions (H × W × D) | 371 × 510 × 270 mm |
The ABB 1SDA071822R1 is an Emax 2 air circuit breaker designed for high-current low-voltage switching and protection, including transformer, generator and electrical installation protection.
The E4.2N 4000 has a rated uninterrupted current of 4000 A, making it suitable for large high-current electrical distribution systems.
The E4.2N 4000 provides a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC.
The Ekip Dip LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI version does not include integrated earth-fault protection.
This model is a four-pole fixed air circuit breaker equipped with rear horizontal terminals for permanent integration into compatible low-voltage switchboards and power-distribution assemblies.
ABB SACE Emax 2 air circuit breakers provide dependable high-current switching and electronic circuit protection for demanding low-voltage installations, helping industrial and infrastructure systems achieve effective fault protection, selectivity and continuity of service.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.