ABB 1SDA071785R1 SACE Emax 2 E4.2S 3200 Ekip Touch LSI four-pole fixed air circuit breaker rated at 3200 A and 690 V AC with 85 kA breaking capacity at 400/415 V AC and electronic long-time, short-time and instantaneous protection.
£14,909.56
The ABB E4.2S 3200 Ekip Touch LSI 4p F HR, order code 1SDA071785R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 3200 A rated current with the advanced Ekip Touch LSI electronic protection release and robust short-circuit performance.
This fixed circuit breaker incorporates the Ekip Touch LSI solid-state electronic trip unit, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Adjustable electronic protection settings support effective coordination throughout complex distribution networks, while the Ekip Touch interface provides convenient configuration and monitoring of the breaker.
Rated for operation at up to 690 V AC, the E4.2S 3200 provides an 85 kA ultimate short-circuit breaking capacity at 400/415 V AC and 66 kA at 690 V AC. This version features a fixed four-pole construction with rear horizontal terminals and four auxiliary contacts, making it suitable for high-current industrial, commercial and infrastructure distribution assemblies.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage distribution circuits against potentially damaging overload and short-circuit conditions. The E4.2S frame combines substantial current-carrying capability with high fault-interruption performance, helping protect cables, busbars, switchgear and connected electrical equipment in large power distribution systems.
The Ekip Touch LSI electronic trip unit combines long-time overload, short-time selective and instantaneous short-circuit protection, allowing protection settings to be coordinated with upstream and downstream devices. With a 3200 A current rating, 85 kA Icu at 400/415 V AC and 66 kA Icu at 690 V AC, the 1SDA071785R1 is particularly suited to main switchboards and high-current distribution circuits requiring configurable electronic protection and dependable fault interruption.
| Range | SACE Emax 2 |
|---|---|
| Series | E4.2S |
| ABB order code | 1SDA071785R1 |
| EAN | 8015644756352 |
| Product type | Air circuit breaker |
| Rated current | 3200 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Number of poles | 4 |
| Short-circuit performance level | S |
| Ultimate short-circuit breaking capacity (Icu) at 380 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Short-time withstand current (Icw) | 66 kA for 1 s |
| Trip unit | Ekip Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Integrated earth-fault protection | No |
| Mounting type | Fixed |
| Terminal position | Rear horizontal |
| Auxiliary contacts | 4 |
| Power loss | 425 W |
| Dimensions | 510 × 371 × 270 mm |
| Standard | IEC 60947-2 |
| Country of origin | Italy |
The ABB 1SDA071785R1 is a four-pole air circuit breaker used for switching and protecting high-current low-voltage power distribution circuits against overload and short-circuit conditions.
The E4.2S 3200 Ekip Touch LSI 4p F HR has a rated current of 3200 A and a rated operational voltage of up to 690 V AC.
The E4.2S provides an ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 66 kA at 690 V AC, with a short-time withstand current of 66 kA for 1 s.
The Ekip Touch LSI electronic trip unit provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection. This LSI configuration does not include integrated earth-fault protection.
This model is a fixed four-pole circuit breaker with rear horizontal terminals, designed for installation within compatible low-voltage switchboards and high-capacity power distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine advanced Ekip electronic protection with robust switching and fault-interruption performance, providing dependable protection and control for demanding industrial, commercial and infrastructure power distribution systems.