Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071712R1 E2.2H 2500 Ekip Dip LSI 4p F HR is a 2500 A four-pole fixed SACE Emax 2 air circuit breaker with Ekip Dip LSI electronic protection, up to 100 kA short-circuit breaking capacity and rear horizontal terminals.
£12,176.15
The ABB E2.2H 2500 Ekip Dip LSI 4p F HR, order code 1SDA071712R1, is a high-performance four-pole air circuit breaker (ACB) designed for demanding low-voltage power distribution applications. Part of the ABB SACE Emax 2 series, it combines a 2500 A rated uninterrupted current with an Ekip Dip LSI solid-state electronic release for long-time overload, selective short-time and instantaneous short-circuit protection.
The Ekip Dip LSI trip unit provides adjustable electronic protection using straightforward DIP-switch settings. Long-time overload protection is adjustable from 0.4–1 × In, selective short-circuit protection from 0.6–10 × In and instantaneous short-circuit protection from 1.5–15 × In, allowing effective coordination with other protective devices throughout the electrical distribution system.
The E2.2H performance level delivers a rated ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC and 85 kA at 500–690 V AC. Its four-pole fixed construction, rear horizontal terminals and factory-fitted auxiliary contacts make the 1SDA071712R1 a robust solution for high-current industrial, commercial and infrastructure switchboards.
ABB SACE Emax 2 air circuit breakers provide switching, isolation and protection for high-current low-voltage distribution circuits. With its 2500 A current rating and short-circuit breaking capacity of up to 100 kA, the E2.2H 2500 is designed for installations where substantial load currents and high prospective short-circuit levels require robust protective performance.
The Ekip Dip LSI release combines long-time overload protection with selective short-time and instantaneous short-circuit protection. Adjustable DIP-switch settings enable the breaker to be coordinated with upstream and downstream devices, helping a correctly engineered distribution system isolate localised faults while maintaining supply to unaffected circuits wherever possible.
| Series | SACE Emax 2 |
|---|---|
| ABB product group | Emax2 Air Circuit Breaker |
| Frame / type | E2.2H |
| Order code | 1SDA071712R1 |
| EAN | 8015644755621 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Number of poles | 4 |
| Release | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Long-time overload protection setting | 0.4–1 × In |
| Long-time overload adjustment | 1000–2500 A |
| Selective short-circuit protection setting | 0.6–10 × In |
| Instantaneous short-circuit protection setting | 1.5–15 × In |
| Instantaneous protection adjustment | 3750–37500 A |
| Protection adjustment method | DIP switches |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Short-circuit performance level | H |
| Version | Fixed (F) |
| Terminal connection | Rear horizontal (HR) |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Dimensions (W × H × D) | 366 × 371 × 270 mm |
| Reference standard | IEC 60947-2 |
The ABB 1SDA071712R1 is a 2500 A four-pole air circuit breaker designed for switching and protecting high-current low-voltage distribution circuits where high breaking capacity and configurable LSI protection are required.
The breaker has a rated uninterrupted current of 2500 A and a rated operational voltage of up to 690 V AC.
The Ekip Dip LSI electronic release provides long-time overload, selective short-time short-circuit and instantaneous short-circuit protection, with protection thresholds configured using DIP switches.
The E2.2H 2500 provides a rated ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC and 85 kA at 500–690 V AC.
The 1SDA071712R1 is a fixed four-pole air circuit breaker with rear horizontal terminals for permanent installation within a low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine high-current switching, substantial short-circuit breaking performance and configurable electronic protection to provide dependable selective protection for demanding low-voltage electrical distribution systems.