ABB 1SDA071702R1 E2.2S 2500 Ekip Dip LSI four-pole fixed air circuit breaker with a 2500 A rated current, 85 kA breaking capacity at 400/415 V AC, LSI electronic protection and rear horizontal terminals.
£11,562.24
The ABB E2.2S 2500 Ekip Dip LSI 4p FHR, order code 1SDA071702R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and control of high-current low-voltage electrical distribution systems. Combining a 2500 A rated uninterrupted current with an Ekip Dip LSI electronic trip unit, it provides dependable long-time overload, selective short-circuit and instantaneous short-circuit protection for demanding industrial, commercial and infrastructure applications.
This E2.2S circuit breaker is supplied in a fixed four-pole configuration with rear horizontal terminals. Its Ekip Dip LSI solid-state electronic release provides adjustable LSI protection through straightforward DIP-switch settings, enabling protection parameters to be configured efficiently during commissioning and maintenance without the additional complexity of a touch-interface trip unit.
With an S short-circuit performance level and a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC, the 1SDA071702R1 is engineered for substantial power distribution duties. It maintains a breaking capacity of 66 kA at 690 V AC and provides a rated short-time withstand current of 66 kA for 1 second, supporting robust protection and selective coordination in high-current low-voltage switchboards.
Air circuit breakers such as the ABB SACE Emax 2 E2.2S provide switching, isolation and protection for high-current low-voltage distribution circuits. They are commonly installed as incoming, outgoing or bus-coupler breakers in main distribution switchboards where dependable interruption of overload and short-circuit currents is essential for protecting electrical equipment and maintaining continuity of supply.
The Ekip Dip LSI electronic trip unit combines configurable long-time, selective short-circuit and instantaneous protection with straightforward DIP-switch adjustment. Together with the E2.2S platform's high breaking and short-time withstand capabilities, these functions support effective protection coordination across demanding electrical networks while providing a practical protection solution for high-current distribution applications.
| Series | SACE Emax 2 |
|---|---|
| Frame / product group | E2.2S |
| ABB order code | 1SDA071702R1 |
| EAN | 8015644755522 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 2500 A |
| Number of poles | 4 |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI – long-time overload, selective short-circuit and instantaneous short-circuit protection |
| Overload protection adjustment | 0.4–1 × In |
| Selective short-circuit protection adjustment | 0.6–10 × In |
| Instantaneous short-circuit protection adjustment | 1.5–15 × In |
| Protection setting method | DIP switches |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated short-time withstand current (Icw, 1 s) | 66 kA |
| Short-circuit performance level | S |
| Current type | AC |
| Installation | Fixed |
| Terminal arrangement | Rear horizontal |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Integrated earth-fault protection | No |
| Product dimensions (W × H × D) | 366 × 371 × 270 mm |
| Net weight | 60 kg |
| Mechanical durability | 20,000 cycles |
| Electrical durability up to 440 V AC | 8,000 cycles |
| Electrical durability at 500–690 V AC | 7,000 cycles |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA071702R1 is a 2500 A four-pole air circuit breaker designed to protect and control high-current low-voltage power distribution circuits in industrial, commercial and infrastructure installations.
The E2.2S 2500 supplied under ABB order code 1SDA071702R1 has a rated uninterrupted current of 2500 A.
The circuit breaker is fitted with an Ekip Dip LSI electronic trip unit, providing long-time overload, selective short-circuit and instantaneous short-circuit protection with settings configured using DIP switches.
The E2.2S 2500 has a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 66 kA at 690 V AC, together with a rated short-time withstand current of 66 kA for 1 second.
The 1SDA071702R1 is a fixed air circuit breaker with four poles and rear horizontal terminals, intended for permanent installation within compatible low-voltage switchgear and distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine high fault-interruption performance with dependable electronic protection, making the E2.2S with Ekip Dip LSI a robust choice for demanding low-voltage distribution systems requiring reliable overload and short-circuit protection.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.