1SDA071702R1 ABB E2.2S 2500 Ekip Dip LSI 4p FHR Air Circuit Breaker

1SDA071702R1 ABB E2.2S 2500 Ekip Dip LSI 4p FHR Air Circuit Breaker

ABB 1SDA071702R1 E2.2S 2500 Ekip Dip LSI four-pole fixed air circuit breaker with a 2500 A rated current, 85 kA breaking capacity at 400/415 V AC, LSI electronic protection and rear horizontal terminals.

SKU: 1SDA071702R1MPN: 1SDA071702R1
Price
List Price £15,416.32 ex VAT
Your Price (ex VAT) Save 25%
£11,562.24 25% OFF
You save £3,854.08 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,562.24
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,562.24

Why Choose the ABB E2.2S 2500 Ekip Dip LSI 4p FHR Air Circuit Breaker?

The ABB E2.2S 2500 Ekip Dip LSI 4p FHR, order code 1SDA071702R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and control of high-current low-voltage electrical distribution systems. Combining a 2500 A rated uninterrupted current with an Ekip Dip LSI electronic trip unit, it provides dependable long-time overload, selective short-circuit and instantaneous short-circuit protection for demanding industrial, commercial and infrastructure applications.

This E2.2S circuit breaker is supplied in a fixed four-pole configuration with rear horizontal terminals. Its Ekip Dip LSI solid-state electronic release provides adjustable LSI protection through straightforward DIP-switch settings, enabling protection parameters to be configured efficiently during commissioning and maintenance without the additional complexity of a touch-interface trip unit.

With an S short-circuit performance level and a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC, the 1SDA071702R1 is engineered for substantial power distribution duties. It maintains a breaking capacity of 66 kA at 690 V AC and provides a rated short-time withstand current of 66 kA for 1 second, supporting robust protection and selective coordination in high-current low-voltage switchboards.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 2500 A rated uninterrupted current for substantial industrial and commercial electrical loads.
  • Four-pole configuration suitable for three-phase systems requiring neutral switching.
  • Ekip Dip LSI electronic trip unit provides overload, selective short-circuit and instantaneous short-circuit protection.
  • 85 kA ultimate breaking capacity at 400/415 V AC for installations with high prospective fault currents.
  • 66 kA ultimate breaking capacity at 690 V AC supports demanding higher-voltage LV distribution networks.
  • 66 kA short-time withstand current for 1 second supports effective protection coordination.
  • Fixed installation with rear horizontal terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Emax 2 E2.2S series.
  • 2500 A rated uninterrupted current.
  • Four-pole air circuit breaker.
  • Ekip Dip LSI solid-state electronic protection release.
  • Long-time overload protection (L).
  • Selective short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Overload protection adjustable from 0.4–1 × In.
  • Selective short-circuit protection adjustable from 0.6–10 × In.
  • Instantaneous short-circuit protection adjustable from 1.5–15 × In.
  • Protection parameters configured using DIP switches.
  • 85 kA ultimate breaking capacity at 400/415 V AC.
  • 66 kA ultimate breaking capacity at 690 V AC.
  • 66 kA rated short-time withstand current for 1 second.
  • Fixed mounting configuration with rear horizontal terminals.
  • Supplied with four auxiliary contacts and circuit-breaker open/closed indication.

High-Current Circuit Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E2.2S provide switching, isolation and protection for high-current low-voltage distribution circuits. They are commonly installed as incoming, outgoing or bus-coupler breakers in main distribution switchboards where dependable interruption of overload and short-circuit currents is essential for protecting electrical equipment and maintaining continuity of supply.

The Ekip Dip LSI electronic trip unit combines configurable long-time, selective short-circuit and instantaneous protection with straightforward DIP-switch adjustment. Together with the E2.2S platform's high breaking and short-time withstand capabilities, these functions support effective protection coordination across demanding electrical networks while providing a practical protection solution for high-current distribution applications.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Incoming and outgoing feeder protection.
  • Bus-coupler and distribution circuit applications.
  • Transformer and generator distribution systems.
  • Data centres and critical power installations.
  • Manufacturing and process industry switchgear.

Technical Specifications

Series SACE Emax 2
Frame / product group E2.2S
ABB order code 1SDA071702R1
EAN 8015644755522
Product type Air circuit breaker
Rated uninterrupted current (Iu) 2500 A
Number of poles 4
Trip unit Ekip Dip LSI
Release type Solid-state electronic
Protection functions LSI – long-time overload, selective short-circuit and instantaneous short-circuit protection
Overload protection adjustment 0.4–1 × In
Selective short-circuit protection adjustment 0.6–10 × In
Instantaneous short-circuit protection adjustment 1.5–15 × In
Protection setting method DIP switches
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Rated short-time withstand current (Icw, 1 s) 66 kA
Short-circuit performance level S
Current type AC
Installation Fixed
Terminal arrangement Rear horizontal
Auxiliary contacts 4
Circuit-breaker position indication Open / closed
Integrated earth-fault protection No
Product dimensions (W × H × D) 366 × 371 × 270 mm
Net weight 60 kg
Mechanical durability 20,000 cycles
Electrical durability up to 440 V AC 8,000 cycles
Electrical durability at 500–690 V AC 7,000 cycles
Applicable standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071702R1 used for?

The ABB 1SDA071702R1 is a 2500 A four-pole air circuit breaker designed to protect and control high-current low-voltage power distribution circuits in industrial, commercial and infrastructure installations.

What is the rated current of the ABB E2.2S 2500?

The E2.2S 2500 supplied under ABB order code 1SDA071702R1 has a rated uninterrupted current of 2500 A.

What protection unit is fitted to the 1SDA071702R1?

The circuit breaker is fitted with an Ekip Dip LSI electronic trip unit, providing long-time overload, selective short-circuit and instantaneous short-circuit protection with settings configured using DIP switches.

What is the breaking capacity of the ABB E2.2S 2500?

The E2.2S 2500 has a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 66 kA at 690 V AC, together with a rated short-time withstand current of 66 kA for 1 second.

Is the ABB 1SDA071702R1 fixed or withdrawable?

The 1SDA071702R1 is a fixed air circuit breaker with four poles and rear horizontal terminals, intended for permanent installation within compatible low-voltage switchgear and distribution assemblies.

Trusted ABB Protection for High-Current Power Systems

ABB SACE Emax 2 air circuit breakers combine high fault-interruption performance with dependable electronic protection, making the E2.2S with Ekip Dip LSI a robust choice for demanding low-voltage distribution systems requiring reliable overload and short-circuit protection.