ABB 1SDA071670R1 E2.2N 2000 Ekip G Hi-Touch LSIG four-pole fixed air circuit breaker for generator protection with a 2000 A rated current, 66 kA breaking capacity at 400/415 V AC, LSIG electronic protection and rear horizontal flat terminals.
£11,854.59
The ABB E2.2N 2000 Ekip G Hi-Touch LSIG 4p FHR, order code 1SDA071670R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for generator protection and demanding low-voltage electrical distribution systems. Combining a 2000 A rated uninterrupted current with the advanced Ekip G Hi-Touch LSIG electronic trip unit, it provides comprehensive overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.
This E2.2N circuit breaker is supplied in a fixed four-pole configuration with rear horizontal flat terminals. Its Ekip G Hi-Touch LSIG solid-state electronic release combines generator-oriented protection with ABB's advanced Hi-Touch platform, providing configurable protection, measurement and monitoring functionality for generator switchboards, critical power systems and associated distribution circuits.
With a 2000 A rated uninterrupted current, an N short-circuit performance level and a rated ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, the 1SDA071670R1 is engineered for substantial power distribution duties. It maintains a 66 kA ultimate breaking capacity at 690 V AC and provides a rated short-time withstand current of 66 kA for 1 second, supporting selective protection in demanding low-voltage networks.
Air circuit breakers such as the ABB SACE Emax 2 E2.2N provide switching, isolation and protection for high-current low-voltage circuits. Generator-oriented configurations are particularly suited to generator switchboards, standby generation systems and critical distribution assemblies where dependable interruption of overload, short-circuit and earth-fault currents is essential for protecting equipment and maintaining continuity of supply.
The Ekip G Hi-Touch LSIG electronic trip unit combines generator-oriented functionality with configurable long-time, short-time, instantaneous and earth-fault protection. Its advanced protection and monitoring capabilities, together with the E2.2N platform's 66 kA breaking performance, enable comprehensive protection of generators and connected distribution circuits while supporting effective coordination within complex electrical networks.
| Series | SACE Emax 2 |
|---|---|
| Frame / product group | E2.2N |
| ABB order code | 1SDA071670R1 |
| EAN | 8015644755201 |
| Product type | Air circuit breaker |
| Application | Generator and low-voltage distribution protection |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated current (In) | 2000 A |
| Number of poles | 4 |
| Neutral pole current | 100% of Iu |
| Trip unit | Ekip G Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | LSIG – long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection |
| Overload release setting range | 800–2000 A |
| Short-time delayed short-circuit setting range | 1200–20000 A |
| Instantaneous short-circuit setting range | 3000–30000 A |
| Integrated earth-fault protection | Yes |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw, 1 s) | 66 kA |
| Rated short-time withstand current (Icw, 3 s) | 50 kA |
| Short-circuit performance level | N |
| Current type | AC |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Auxiliary contacts | 4 changeover contacts |
| Circuit-breaker position indication | Open / closed |
| Motor drive | Optional |
| Power loss | 212 W |
| Mechanical durability | 25,000 cycles |
| Electrical durability at 440 V AC | 10,000 cycles |
| Electrical durability at 500–690 V AC | 8,000 cycles |
| Dimensions (W × H × D) | 366 × 371 × 270 mm |
| Weight | 53 kg |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA071670R1 is a 2000 A four-pole air circuit breaker designed for generator protection and high-current low-voltage power distribution applications.
The E2.2N 2000 supplied under ABB order code 1SDA071670R1 has a rated uninterrupted current of 2000 A.
The circuit breaker is fitted with an Ekip G Hi-Touch LSIG electronic trip unit, providing long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection together with advanced generator-oriented protection functionality.
The E2.2N 2000 has a rated ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, with the 66 kA rating maintained at operating voltages up to 690 V AC.
The 1SDA071670R1 is a fixed air circuit breaker with four poles and rear horizontal flat terminals, intended for permanent installation within compatible generator switchgear and low-voltage distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine robust fault-interruption performance with advanced electronic protection technology, making the E2.2N with Ekip G Hi-Touch LSIG a dependable choice for generator protection and demanding low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.