1SDA071670R1 ABB E2.2N 2000 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker

1SDA071670R1 ABB E2.2N 2000 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker

ABB 1SDA071670R1 E2.2N 2000 Ekip G Hi-Touch LSIG four-pole fixed air circuit breaker for generator protection with a 2000 A rated current, 66 kA breaking capacity at 400/415 V AC, LSIG electronic protection and rear horizontal flat terminals.

SKU: 1SDA071670R1MPN: 1SDA071670R1
Price
List Price £15,806.12 ex VAT
Your Price (ex VAT) Save 25%
£11,854.59 25% OFF
You save £3,951.53 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,854.59
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,854.59

Why Choose the ABB E2.2N 2000 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker?

The ABB E2.2N 2000 Ekip G Hi-Touch LSIG 4p FHR, order code 1SDA071670R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for generator protection and demanding low-voltage electrical distribution systems. Combining a 2000 A rated uninterrupted current with the advanced Ekip G Hi-Touch LSIG electronic trip unit, it provides comprehensive overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.

This E2.2N circuit breaker is supplied in a fixed four-pole configuration with rear horizontal flat terminals. Its Ekip G Hi-Touch LSIG solid-state electronic release combines generator-oriented protection with ABB's advanced Hi-Touch platform, providing configurable protection, measurement and monitoring functionality for generator switchboards, critical power systems and associated distribution circuits.

With a 2000 A rated uninterrupted current, an N short-circuit performance level and a rated ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, the 1SDA071670R1 is engineered for substantial power distribution duties. It maintains a 66 kA ultimate breaking capacity at 690 V AC and provides a rated short-time withstand current of 66 kA for 1 second, supporting selective protection in demanding low-voltage networks.

Key Advantages

  • Advanced ABB SACE Emax 2 generator-protection air circuit breaker.
  • 2000 A rated uninterrupted current for substantial generator and distribution loads.
  • Four-pole configuration with the neutral pole rated at 100% of uninterrupted current.
  • Ekip G Hi-Touch LSIG electronic trip unit with advanced generator-oriented protection functionality.
  • Comprehensive LSIG protection against overloads, short circuits and earth faults.
  • 66 kA ultimate breaking capacity at 400/415 V AC for dependable fault interruption.
  • 66 kA ultimate breaking capacity at 690 V AC for higher-voltage LV distribution systems.
  • 66 kA short-time withstand current for 1 second supports coordinated and selective protection.

Key Features

  • ABB SACE Emax 2 E2.2N series.
  • 2000 A rated uninterrupted current.
  • Four-pole air circuit breaker.
  • Ekip G Hi-Touch LSIG solid-state electronic protection release.
  • Long-time overload protection (L).
  • Selective short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Integrated earth-fault protection (G).
  • Overload release setting range of 800–2000 A.
  • Short-time delayed short-circuit setting range of 1200–20000 A.
  • Instantaneous short-circuit setting range of 3000–30000 A.
  • 66 kA ultimate breaking capacity at 400–690 V AC.
  • 1000 V AC rated insulation voltage and 12 kV impulse withstand voltage.
  • Fixed mounting configuration with rear horizontal flat terminals.
  • Fitted with four auxiliary changeover contacts and open/closed position indication.

Advanced Generator and Power Distribution Protection

Air circuit breakers such as the ABB SACE Emax 2 E2.2N provide switching, isolation and protection for high-current low-voltage circuits. Generator-oriented configurations are particularly suited to generator switchboards, standby generation systems and critical distribution assemblies where dependable interruption of overload, short-circuit and earth-fault currents is essential for protecting equipment and maintaining continuity of supply.

The Ekip G Hi-Touch LSIG electronic trip unit combines generator-oriented functionality with configurable long-time, short-time, instantaneous and earth-fault protection. Its advanced protection and monitoring capabilities, together with the E2.2N platform's 66 kA breaking performance, enable comprehensive protection of generators and connected distribution circuits while supporting effective coordination within complex electrical networks.

Typical Applications

  • Generator protection and generator switchboards.
  • Standby and emergency power generation systems.
  • Low-voltage main distribution switchboards.
  • Industrial power generation and distribution systems.
  • Incoming and outgoing feeder protection.
  • Bus-coupler and distribution circuit applications.
  • Data centres and critical power systems.
  • Commercial and infrastructure electrical installations.

Technical Specifications

Series SACE Emax 2
Frame / product group E2.2N
ABB order code 1SDA071670R1
EAN 8015644755201
Product type Air circuit breaker
Application Generator and low-voltage distribution protection
Rated uninterrupted current (Iu) 2000 A
Rated current (In) 2000 A
Number of poles 4
Neutral pole current 100% of Iu
Trip unit Ekip G Hi-Touch LSIG
Release type Electronic
Protection functions LSIG – long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection
Overload release setting range 800–2000 A
Short-time delayed short-circuit setting range 1200–20000 A
Instantaneous short-circuit setting range 3000–30000 A
Integrated earth-fault protection Yes
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw, 1 s) 66 kA
Rated short-time withstand current (Icw, 3 s) 50 kA
Short-circuit performance level N
Current type AC
Installation Fixed
Terminal arrangement Rear flat horizontal
Auxiliary contacts 4 changeover contacts
Circuit-breaker position indication Open / closed
Motor drive Optional
Power loss 212 W
Mechanical durability 25,000 cycles
Electrical durability at 440 V AC 10,000 cycles
Electrical durability at 500–690 V AC 8,000 cycles
Dimensions (W × H × D) 366 × 371 × 270 mm
Weight 53 kg
Applicable standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071670R1 used for?

The ABB 1SDA071670R1 is a 2000 A four-pole air circuit breaker designed for generator protection and high-current low-voltage power distribution applications.

What is the rated current of the ABB E2.2N 2000?

The E2.2N 2000 supplied under ABB order code 1SDA071670R1 has a rated uninterrupted current of 2000 A.

What protection unit is fitted to the 1SDA071670R1?

The circuit breaker is fitted with an Ekip G Hi-Touch LSIG electronic trip unit, providing long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection together with advanced generator-oriented protection functionality.

What is the breaking capacity of the ABB E2.2N 2000?

The E2.2N 2000 has a rated ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, with the 66 kA rating maintained at operating voltages up to 690 V AC.

Is the ABB 1SDA071670R1 fixed or withdrawable?

The 1SDA071670R1 is a fixed air circuit breaker with four poles and rear horizontal flat terminals, intended for permanent installation within compatible generator switchgear and low-voltage distribution assemblies.

Trusted ABB Protection for Generator and Critical Power Systems

ABB SACE Emax 2 air circuit breakers combine robust fault-interruption performance with advanced electronic protection technology, making the E2.2N with Ekip G Hi-Touch LSIG a dependable choice for generator protection and demanding low-voltage power distribution systems.