ABB 1SDA071669R1 Emax 2 E2.2N 2000 is a 2000 A four-pole fixed air circuit breaker with rear flat horizontal terminals and an Ekip Hi-Touch LSIG electronic trip unit for advanced long-time, short-time, instantaneous and ground-fault protection.
£11,401.45
The ABB E2.2N 2000 Ekip Hi-Touch LSIG 4p FHR, order code 1SDA071669R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection and switching in demanding low-voltage power distribution systems. This fixed four-pole E2.2N configuration combines a 2000 A rated current with ABB's Ekip Hi-Touch LSIG solid-state electronic trip unit and rear flat horizontal main terminals.
The Ekip Hi-Touch LSIG release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. This comprehensive protection package makes the breaker particularly suitable for critical distribution networks where overload protection, selective fault clearance and earth-fault protection must be combined within a single advanced electronic release.
The E2.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–690 V AC, while its rated short-time withstand capability is 66 kA for 1 s and 50 kA for 3 s. Rated for operation up to 690 V AC, the 1SDA071669R1 provides a robust solution for main switchboards, transformer secondary systems, industrial incomers and critical high-current distribution networks.
The ABB SACE Emax 2 E2.2N is engineered for switching and protection at critical points within high-current low-voltage networks. Its 2000 A current capability, consistent 66 kA ultimate breaking capacity and substantial short-time withstand performance make this configuration suitable for main distribution circuits where fault interruption, selectivity and continuity of service are important design considerations.
The Ekip Hi-Touch LSIG release combines four complementary protection functions. Long-time protection responds to sustained overloads, short-time protection supports selective coordination, instantaneous protection rapidly interrupts severe short circuits, and ground-fault protection detects earth-fault conditions. Together, these functions provide a comprehensive electronic protection solution for sophisticated low-voltage distribution systems.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2N |
| ABB order code | 1SDA071669R1 |
| EAN | 8015644755195 |
| Product type | Air circuit breaker |
| Application | Power distribution |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 4 |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | Long-time (L), short-time (S), instantaneous (I) and ground-fault (G) |
| Integrated ground-fault protection | Yes |
| Overload protection adjustment | 800–2000 A |
| Short-time short-circuit protection adjustment | 1200–20,000 A |
| Instantaneous short-circuit protection adjustment | 3000–30,000 A |
| Rated operational voltage | 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Icu at 415 / 440 V AC | 66 kA |
| Icu at 500 / 525 / 690 V AC | 66 kA |
| Rated service breaking capacity (Ics) at 220–690 V AC | 66 kA |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Short-circuit performance level | N |
| Installation | Fixed |
| Main connection position | Rear |
| Terminal connection | Rear flat horizontal |
| Main-circuit connection | Bolt |
| Main-circuit screw size | M12 |
| Main-circuit tightening torque | 70 N·m |
| Changeover auxiliary contacts | 4 |
| Breaker position indication | Open / closed |
| Operating element | Push-button |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Degree of protection | IP30 |
| Power loss | 212 W |
| Product dimensions | 371 × 366 × 270 mm |
| Product net weight | 53 kg |
| Standard | IEC |
It is a 2000 A four-pole fixed air circuit breaker designed for advanced switching and protection of high-current low-voltage distribution circuits in industrial, commercial and critical-power installations.
The Ekip Hi-Touch LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and integrated ground-fault protection.
The E2.2N 2000 provides an ultimate short-circuit breaking capacity of 66 kA at 400–690 V AC, with a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.
The overload protection range is 800–2000 A, short-time short-circuit protection is adjustable from 1200–20,000 A, and instantaneous short-circuit protection is adjustable from 3000–30,000 A.
This configuration is a fixed four-pole air circuit breaker equipped with rear flat horizontal bolted terminals for integration into low-voltage switchgear.
ABB SACE Emax 2 air circuit breakers combine high-current switching capability, selective electronic protection and integrated ground-fault protection to support dependable operation of demanding low-voltage power distribution systems.