1SDA071665R1 ABB E2.2N 2000 Ekip Touch LSI 4p F HR Air Circuit Breaker 2000 A

1SDA071665R1 ABB E2.2N 2000 Ekip Touch LSI 4p F HR Air Circuit Breaker 2000 A

ABB 1SDA071665R1 E2.2N 2000 Ekip Touch LSI 4p F HR is a 2000 A four-pole fixed SACE Emax 2 air circuit breaker with Ekip Touch LSI electronic protection, 66 kA short-circuit breaking capacity and rear horizontal terminals.

SKU: 1SDA071665R1MPN: 1SDA071665R1
Price
List Price £10,816.77 ex VAT
Your Price (ex VAT) Save 25%
£8,112.58 25% OFF
You save £2,704.19 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,112.58
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,112.58

Why Choose the ABB E2.2N 2000 Ekip Touch LSI 4p F HR Air Circuit Breaker?

The ABB E2.2N 2000 Ekip Touch LSI 4p F HR, order code 1SDA071665R1, is a high-performance four-pole air circuit breaker (ACB) designed for switching and protection in high-current low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, it combines a 2000 A rated current with an Ekip Touch LSI electronic trip unit for configurable overload, selective short-circuit and instantaneous short-circuit protection.

The Ekip Touch LSI release provides long-time, short-time and instantaneous protection functions through a touch-sensitive interface. Long-time protection is adjustable from 0.4–1 × In, selective short-circuit protection from 0.6–10 × In and instantaneous protection from 1.5–15 × In, allowing the breaker to be coordinated precisely with the characteristics of the protected electrical system.

With a rated operational voltage of 690 V AC, four-pole configuration and fixed construction with rear horizontal terminals, the E2.2N 2000 is designed for integration into low-voltage switchboards. Its N performance level provides a rated ultimate short-circuit breaking capacity of 66 kA from 380–690 V AC, making it a robust solution for industrial, commercial and infrastructure power distribution.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for low-voltage power distribution.
  • 2000 A rated current for substantial industrial and commercial electrical loads.
  • Four-pole configuration for switching and protection of three phases and neutral.
  • Advanced Ekip Touch LSI electronic trip unit with touch-sensitive configuration interface.
  • Provides long-time, selective short-time and instantaneous short-circuit protection.
  • 66 kA Icu across key operating voltages from 380–690 V AC.
  • Adjustable short-time protection supports selective coordination between upstream and downstream protective devices.
  • Fixed construction with rear horizontal terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Emax 2 E2.2N series.
  • 2000 A rated current.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 50 / 60 Hz operating frequency.
  • Four-pole fixed air circuit breaker.
  • Ekip Touch LSI electronic trip unit.
  • Adjustable long-time overload protection.
  • Adjustable selective short-time short-circuit protection.
  • Adjustable instantaneous short-circuit protection.
  • Long-time protection adjustment from 0.4–1 × In.
  • Short-time protection adjustment from 0.6–10 × In.
  • Instantaneous protection adjustment from 1.5–15 × In.
  • 66 kA Icu at 380–690 V AC.
  • Rear horizontal terminals for fixed switchboard installation.

Selective Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and protection for high-current low-voltage distribution circuits. With its 2000 A current rating and 66 kA short-circuit breaking capacity, the E2.2N 2000 helps protect switchboards, cables, transformers and connected electrical equipment against overloads and severe short-circuit conditions.

The Ekip Touch LSI electronic release adds selective short-time protection to long-time overload and instantaneous protection. This enables more sophisticated coordination between protective devices, helping downstream breakers clear localised faults before an upstream breaker operates and thereby supporting continuity of supply across correctly coordinated electrical distribution systems.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial electrical distribution systems.
  • Commercial building power distribution.
  • Manufacturing and process plants.
  • Transformer secondary protection.
  • Incoming and outgoing distribution feeders.
  • Infrastructure and utility installations.
  • Power distribution systems requiring selective short-circuit coordination.

Technical Specifications

Series SACE Emax 2
ABB product group Emax2 Air Circuit Breaker
Frame / type E2.2N
Order code 1SDA071665R1
EAN 8015644755157
Product type Air circuit breaker
Rated current 2000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Number of poles 4
Release Ekip Touch LSI
Release type Electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Long-time overload protection setting 0.4–1 × In
Selective short-circuit protection setting 0.6–10 × In
Instantaneous short-circuit protection setting 1.5–15 × In
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Short-circuit performance level N
Version Fixed (F)
Terminal connection Rear horizontal (HR)
Net weight 58 kg
Reference standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071665R1 used for?

The ABB 1SDA071665R1 is a 2000 A four-pole air circuit breaker used for switching and protecting high-current low-voltage power distribution circuits in industrial, commercial and infrastructure installations.

What is the current rating of the E2.2N 2000 Ekip Touch LSI?

The circuit breaker has a rated current of 2000 A and is designed for low-voltage systems with a rated operational voltage of up to 690 V AC.

What protection does the Ekip Touch LSI release provide?

The Ekip Touch LSI electronic trip unit provides long-time overload, selective short-time short-circuit and instantaneous short-circuit protection, with adjustable thresholds for coordination with the electrical installation.

What is the breaking capacity of the ABB E2.2N 2000?

The E2.2N 2000 provides a rated ultimate short-circuit breaking capacity of 66 kA at 380 V AC, 400–415 V AC, 440 V AC, 500–525 V AC and 690 V AC.

Is the ABB 1SDA071665R1 fixed or withdrawable?

The 1SDA071665R1 is a fixed four-pole air circuit breaker with rear horizontal terminals for permanent installation within a low-voltage switchboard.

Trusted Selective Power Protection from ABB

ABB SACE Emax 2 air circuit breakers combine robust short-circuit performance, configurable electronic protection and selective fault coordination to provide dependable protection for modern high-current low-voltage electrical distribution systems.