1SDA071661R1 ABB E2.2N 2000 Ekip Dip LI 4p FHR Air Circuit Breaker

1SDA071661R1 ABB E2.2N 2000 Ekip Dip LI 4p FHR Air Circuit Breaker

ABB 1SDA071661R1 Emax 2 E2.2N 2000 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Dip LI electronic protection and 66 kA breaking capacity across 380–690 V AC for high-current low-voltage power distribution systems.

SKU: 1SDA071661R1MPN: 1SDA071661R1
Price
List Price £10,310.00 ex VAT
Your Price (ex VAT) Save 25%
£7,732.50 25% OFF
You save £2,577.50 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,732.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,732.50

Why Choose the ABB E2.2N 2000 Ekip Dip LI 4p FHR Air Circuit Breaker?

The ABB E2.2N 2000 Ekip Dip LI 4p FHR, order code 1SDA071661R1, is a high-performance four-pole air circuit breaker (ACB) designed for high-current low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 2000 A rated uninterrupted current with dependable electronic protection and strong short-circuit performance for industrial, commercial and infrastructure installations.

The breaker is equipped with the Ekip Dip LI solid-state electronic trip unit, providing long-time overload and instantaneous short-circuit protection. Overload protection is adjustable from 0.4–1 × In, while instantaneous protection is adjustable from 1.5–15 × In. Settings are configured through DIP switches, providing a straightforward method of adapting protection to the requirements of the electrical installation.

The E2.2N frame provides an ultimate short-circuit breaking capacity of 66 kA across 380–690 V AC, with a rated operational voltage of 690 V AC. Its fixed four-pole construction with rear flat horizontal terminals and bolt-connected main circuit is designed for permanent integration into substantial low-voltage switchboards and busbar systems.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 2000 A rated uninterrupted current for substantial industrial, commercial and infrastructure loads.
  • Four-pole configuration with the neutral pole rated at 100% of Iu.
  • Ekip Dip LI electronic trip unit provides adjustable overload and instantaneous short-circuit protection.
  • 66 kA ultimate breaking capacity across 380–690 V AC for robust fault interruption.
  • Rated service breaking capacity equal to 100% of Icu.
  • 66 kA short-time withstand current for 1 s supports demanding distribution applications.
  • Fixed installation with rear flat horizontal terminals for efficient switchboard and busbar integration.

Key Features

  • ABB SACE Emax 2 E2.2N series.
  • 2000 A rated uninterrupted current.
  • Four-pole air circuit breaker.
  • 100% neutral pole current rating.
  • Fixed mounting configuration.
  • Rear flat horizontal terminals.
  • Ekip Dip LI solid-state electronic release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • Overload adjustment range of 0.4–1 × In.
  • Instantaneous protection adjustment range of 1.5–15 × In.
  • Protection settings configured through DIP switches.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 66 kA Icu across 380–690 V AC.
  • 50/60 Hz operating frequency.
  • Suitable for IT networks up to 690 V.

Dependable LI Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection for high-current low-voltage electrical systems. The E2.2N performance level combines substantial short-circuit interruption capability with high continuous-current capacity, helping protect cables, busbars, switchgear and connected equipment against potentially damaging overload and short-circuit conditions.

The Ekip Dip LI release combines adjustable long-time overload protection with adjustable instantaneous short-circuit protection in a straightforward electronic platform. Together with the E2.2N frame's 66 kA breaking capacity, this makes the 1SDA071661R1 particularly suitable for high-current incomers and distribution circuits requiring robust electronic protection without dedicated short-time or earth-fault functions.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Transformer-fed low-voltage distribution systems.
  • Industrial power distribution systems.
  • Commercial building electrical infrastructure.
  • Manufacturing and process plant switchgear.
  • High-current incomer and feeder protection.
  • Infrastructure and utility electrical distribution.
  • OEM low-voltage switchgear and busbar assemblies.

Technical Specifications

Product group Emax2 Air Circuit Breaker
Series SACE Emax 2 E2.2N
ABB order code 1SDA071661R1
EAN 8015644755119
Product type Air circuit breaker
Frame E2.2N
Rated uninterrupted current (Iu) 2000 A
Rated current (In) 2000 A
Current type AC
Number of poles 4
Neutral pole current 100% of Iu
Trip unit Ekip Dip LI electronic release
Release technology Solid-state electronic
Protection functions L (long-time overload) and I (instantaneous short circuit)
Overload protection adjustment 0.4–1 × In / 800–2000 A
Instantaneous protection adjustment 1.5–15 × In / 3000–30000 A
Integrated earth-fault protection No
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated frequency 50/60 Hz
Ultimate breaking capacity (Icu) at 380 V AC 66 kA
Ultimate breaking capacity (Icu) at 400 / 415 V AC 66 kA
Ultimate breaking capacity (Icu) at 440 V AC 66 kA
Ultimate breaking capacity (Icu) at 500 / 525 V AC 66 kA
Ultimate breaking capacity (Icu) at 690 V AC 66 kA
Rated service breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw) 66 kA for 1 s; 50 kA for 3 s
Installation Fixed
Terminal arrangement Rear flat horizontal
Main circuit connection Bolt connection
Main circuit connection position Rear
Connecting capacity 1800 mm²
Recommended main-circuit screw M12
Terminal tightening torque 70 N·m
Auxiliary contacts 4 change-over contacts
Circuit-breaker open/closed indication Yes
Integrated motor drive No
Optional motor drive Yes
Degree of protection IP30
Power loss 212 W
Electrical durability at ≤440 V 10,000 operating cycles
Electrical durability at 500–690 V 8,000 operating cycles
Mechanical durability 25,000 operating cycles
Suitable for IT networks Yes, up to 690 V
Dimensions (W × H × D) 366 × 371 × 270 mm
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071661R1 used for?

The ABB 1SDA071661R1 is a four-pole air circuit breaker designed for switching and protection in high-current low-voltage power distribution systems, including industrial, commercial, infrastructure and transformer-fed switchboards.

What is the rated current of the ABB E2.2N 2000?

The ABB E2.2N 2000 has a rated uninterrupted current of 2000 A, with the neutral pole rated at 100% of Iu.

What protection does the Ekip Dip LI trip unit provide?

The Ekip Dip LI electronic trip unit provides adjustable long-time overload and instantaneous short-circuit protection. The overload setting range is 0.4–1 × In, while instantaneous protection is adjustable from 1.5–15 × In.

What is the breaking capacity of the ABB 1SDA071661R1?

The E2.2N provides an ultimate short-circuit breaking capacity of 66 kA across 380–690 V AC. Its rated service breaking capacity is 100% of Icu, with a short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.

What does FHR mean on the ABB E2.2N 2000?

The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.

Trusted Power Distribution Technology from ABB

ABB SACE Emax 2 air circuit breakers combine configurable electronic protection with robust short-circuit performance and high-current capability, providing dependable switching and protection for demanding low-voltage electrical distribution systems.