ABB 1SDA071657R1 E2.2B 2000 Ekip G Touch LSIG four-pole fixed air circuit breaker for generator protection with a 2000 A rated current, 42 kA breaking capacity at 440 V AC, LSIG electronic protection and rear horizontal terminals.
£10,612.12
The ABB E2.2B 2000 Ekip G Touch LSIG 4p FHR, order code 1SDA071657R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for generator protection and demanding low-voltage electrical distribution systems. Combining a 2000 A rated uninterrupted current with the advanced Ekip G Touch LSIG electronic trip unit, it provides comprehensive overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.
This E2.2B circuit breaker is supplied in a fixed four-pole configuration with rear horizontal terminals. Its Ekip G Touch LSIG solid-state electronic release combines generator-oriented protection functionality with ABB's Ekip Touch interface, making the breaker well suited to generator switchboards, standby generation systems and associated low-voltage distribution circuits.
With a 2000 A rated uninterrupted current and a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC, the 1SDA071657R1 provides dependable fault interruption for substantial generator and distribution loads. The E2.2B platform also provides a rated short-time withstand current of 42 kA for 1 second, supporting selective protection and coordination within critical power systems.
Air circuit breakers such as the ABB SACE Emax 2 E2.2B provide switching, isolation and protection for high-current low-voltage circuits. Generator-oriented versions are particularly suited to generator switchboards, standby power systems and associated distribution assemblies where dependable interruption of overload, short-circuit and earth-fault currents is essential for protecting generation equipment and maintaining continuity of supply.
The Ekip G Touch LSIG electronic trip unit combines generator-oriented functionality with configurable long-time, short-time, instantaneous and earth-fault protection. Together with the Emax 2 platform, this enables comprehensive protection of generators and connected distribution circuits while supporting effective coordination and selective operation within complex electrical power systems.
| Series | SACE Emax 2 |
|---|---|
| Frame / product group | E2.2B |
| ABB order code | 1SDA071657R1 |
| EAN | 8015644755072 |
| Product type | Air circuit breaker |
| Application | Generator and low-voltage distribution protection |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 4 |
| Trip unit | Ekip G Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | LSIG – long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection |
| Integrated earth-fault protection | Yes |
| Rated operational voltage | up to 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated short-time withstand current (Icw, 1 s) | 42 kA |
| Short-circuit performance level | B |
| Installation | Fixed |
| Terminal arrangement | Rear horizontal |
| Main-circuit connection | Bolted |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Generator protection functionality | Yes |
| Weight | 53 kg |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA071657R1 is a 2000 A four-pole air circuit breaker designed for generator protection and high-current low-voltage power distribution applications.
The E2.2B 2000 supplied under ABB order code 1SDA071657R1 has a rated uninterrupted current of 2000 A.
The circuit breaker is fitted with an Ekip G Touch LSIG electronic trip unit, providing long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection together with generator-oriented protection functionality.
The E2.2B 2000 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 second.
The 1SDA071657R1 is a fixed air circuit breaker with four poles and rear horizontal terminals, intended for permanent installation within compatible generator switchgear and low-voltage distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine robust fault-interruption performance with advanced electronic protection technology, making the E2.2B with Ekip G Touch a dependable choice for generator protection and demanding low-voltage power distribution systems.