ABB 1SDA071645R1 Emax 2 E2.2H 1600 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Touch LSI electronic protection and 100 kA breaking capacity at 380–440 V AC for selective low-voltage power distribution protection.
£7,396.32
The ABB E2.2H 1600 Ekip Touch LSI 4p FHR, order code 1SDA071645R1, is a high-performance four-pole air circuit breaker (ACB) designed for demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 1600 A rated current with the high-breaking-capacity E2.2H frame and advanced electronic protection for industrial, commercial and infrastructure installations.
The breaker is equipped with the Ekip Touch LSI electronic trip unit, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Adjustable protection thresholds and the touch-sensitive display enable the breaker to be configured for coordinated distribution protection, while the short-time function supports selective operation between upstream and downstream protective devices.
The E2.2H frame provides an ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC and 85 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and fixed four-pole construction with rear flat horizontal terminals, the 1SDA071645R1 is engineered for permanent integration into substantial low-voltage switchboards and busbar systems.
Air circuit breakers used in high-current distribution systems must interrupt severe electrical faults while allowing protection settings to be coordinated across the installation. The ABB SACE Emax 2 E2.2H combines substantial short-circuit breaking performance with electronic protection, making it suitable for switchboards where both high fault levels and selective operation are important design considerations.
The Ekip Touch LSI release combines long-time overload, short-time selective and instantaneous short-circuit protection. The short-time protection stage provides additional flexibility compared with an LI release, allowing protection engineers to coordinate upstream and downstream devices so that, where correctly designed and configured, the protective device closest to a fault can operate before the upstream breaker.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E2.2H |
| ABB order code | 1SDA071645R1 |
| EAN | 8015644754952 |
| Product type | Air circuit breaker |
| Frame | E2.2H |
| Rated current | 1600 A |
| Number of poles | 4 |
| Trip unit | Ekip Touch LSI electronic release |
| Protection functions | L (long-time overload), S (short-time short circuit) and I (instantaneous short circuit) |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Trip-unit interface | Touch-sensitive display |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated frequency | 50/60 Hz |
| Ultimate breaking capacity (Icu) at 380 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 400 / 415 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 / 525 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 85 kA |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Country of origin | Italy |
| Weight | 58 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071645R1 is a four-pole air circuit breaker designed for switching and protection in high-current low-voltage distribution systems, particularly installations requiring high short-circuit breaking performance and selective electronic protection.
The ABB E2.2H 1600 has a rated current of 1600 A, making it suitable for substantial industrial, commercial and infrastructure distribution circuits.
The Ekip Touch LSI electronic trip unit provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection, with configurable electronic settings and a touch-sensitive interface.
The E2.2H provides an ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC and 85 kA at 500–690 V AC, making it suitable for installations with demanding prospective fault-current levels.
The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection with high short-circuit breaking performance and flexible system coordination, providing dependable switching and protection for demanding low-voltage electrical distribution systems.