1SDA071645R1 ABB E2.2H 1600 Ekip Touch LSI 4p FHR Air Circuit Breaker

1SDA071645R1 ABB E2.2H 1600 Ekip Touch LSI 4p FHR Air Circuit Breaker

ABB 1SDA071645R1 Emax 2 E2.2H 1600 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Touch LSI electronic protection and 100 kA breaking capacity at 380–440 V AC for selective low-voltage power distribution protection.

SKU: 1SDA071645R1MPN: 1SDA071645R1
Price
List Price £9,861.76 ex VAT
Your Price (ex VAT) Save 25%
£7,396.32 25% OFF
You save £2,465.44 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,396.32
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,396.32

Why Choose the ABB E2.2H 1600 Ekip Touch LSI 4p FHR Air Circuit Breaker?

The ABB E2.2H 1600 Ekip Touch LSI 4p FHR, order code 1SDA071645R1, is a high-performance four-pole air circuit breaker (ACB) designed for demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 1600 A rated current with the high-breaking-capacity E2.2H frame and advanced electronic protection for industrial, commercial and infrastructure installations.

The breaker is equipped with the Ekip Touch LSI electronic trip unit, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Adjustable protection thresholds and the touch-sensitive display enable the breaker to be configured for coordinated distribution protection, while the short-time function supports selective operation between upstream and downstream protective devices.

The E2.2H frame provides an ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC and 85 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and fixed four-pole construction with rear flat horizontal terminals, the 1SDA071645R1 is engineered for permanent integration into substantial low-voltage switchboards and busbar systems.

Key Advantages

  • High-performance ABB SACE Emax 2 E2.2H air circuit breaker for demanding low-voltage distribution systems.
  • 1600 A rated current for substantial industrial, commercial and infrastructure loads.
  • Four-pole configuration for switching and protection of three-phase systems with neutral.
  • Ekip Touch LSI electronic trip unit provides overload and two-stage short-circuit protection.
  • 100 kA ultimate breaking capacity at 380–440 V AC for installations with high prospective fault currents.
  • 85 kA ultimate breaking capacity at 500–690 V AC for demanding higher-voltage distribution systems.
  • Short-time protection supports selective coordination between protective devices.
  • Fixed installation with rear flat horizontal terminals for efficient switchboard and busbar integration.

Key Features

  • ABB SACE Emax 2 E2.2H series.
  • 1600 A rated current.
  • Four-pole air circuit breaker.
  • Fixed mounting configuration.
  • Rear flat horizontal terminals.
  • Ekip Touch LSI electronic release.
  • Long-time overload protection.
  • Short-time selective short-circuit protection.
  • Instantaneous short-circuit protection.
  • Overload adjustment range of 0.4–1 × In.
  • Instantaneous protection adjustment range of 1.5–15 × In.
  • Touch-sensitive display for protection configuration.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 100 kA Icu at 380–440 V AC.
  • 85 kA Icu at 500–690 V AC.
  • 50/60 Hz operating frequency.
  • Designed to IEC 60947-2 requirements.

Advanced Selective Protection for Low-Voltage Power Distribution

Air circuit breakers used in high-current distribution systems must interrupt severe electrical faults while allowing protection settings to be coordinated across the installation. The ABB SACE Emax 2 E2.2H combines substantial short-circuit breaking performance with electronic protection, making it suitable for switchboards where both high fault levels and selective operation are important design considerations.

The Ekip Touch LSI release combines long-time overload, short-time selective and instantaneous short-circuit protection. The short-time protection stage provides additional flexibility compared with an LI release, allowing protection engineers to coordinate upstream and downstream devices so that, where correctly designed and configured, the protective device closest to a fault can operate before the upstream breaker.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Transformer-fed low-voltage distribution systems.
  • Industrial power distribution systems.
  • Commercial building electrical infrastructure.
  • Manufacturing and process plant switchgear.
  • Systems requiring selective short-circuit protection.
  • Installations with high prospective short-circuit currents.
  • OEM low-voltage switchgear and busbar assemblies.

Technical Specifications

Product group Emax2 Air Circuit Breaker
Series SACE Emax 2 E2.2H
ABB order code 1SDA071645R1
EAN 8015644754952
Product type Air circuit breaker
Frame E2.2H
Rated current 1600 A
Number of poles 4
Trip unit Ekip Touch LSI electronic release
Protection functions L (long-time overload), S (short-time short circuit) and I (instantaneous short circuit)
Overload protection adjustment 0.4–1 × In
Instantaneous protection adjustment 1.5–15 × In
Trip-unit interface Touch-sensitive display
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated frequency 50/60 Hz
Ultimate breaking capacity (Icu) at 380 V AC 100 kA
Ultimate breaking capacity (Icu) at 400 / 415 V AC 100 kA
Ultimate breaking capacity (Icu) at 440 V AC 100 kA
Ultimate breaking capacity (Icu) at 500 / 525 V AC 85 kA
Ultimate breaking capacity (Icu) at 690 V AC 85 kA
Installation Fixed
Terminal arrangement Rear flat horizontal
Country of origin Italy
Weight 58 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071645R1 used for?

The ABB 1SDA071645R1 is a four-pole air circuit breaker designed for switching and protection in high-current low-voltage distribution systems, particularly installations requiring high short-circuit breaking performance and selective electronic protection.

What is the rated current of the ABB E2.2H 1600?

The ABB E2.2H 1600 has a rated current of 1600 A, making it suitable for substantial industrial, commercial and infrastructure distribution circuits.

What protection does the Ekip Touch LSI trip unit provide?

The Ekip Touch LSI electronic trip unit provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection, with configurable electronic settings and a touch-sensitive interface.

What is the breaking capacity of the ABB 1SDA071645R1?

The E2.2H provides an ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC and 85 kA at 500–690 V AC, making it suitable for installations with demanding prospective fault-current levels.

What does FHR mean on the ABB E2.2H 1600?

The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.

Trusted Power Distribution Technology from ABB