Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071642R1 E2.2H 1600 Ekip Dip LSI four-pole fixed air circuit breaker with a 1600 A rated current, 100 kA breaking capacity at 400/415 V AC, LSI electronic protection and rear horizontal terminals.
£7,337.84
The ABB E2.2H 1600 Ekip Dip LSI 4p FHR, order code 1SDA071642R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and control of demanding low-voltage electrical distribution systems. Combining a 1600 A rated current with an Ekip Dip LSI electronic trip unit, it provides dependable overload, selective short-circuit and instantaneous short-circuit protection for industrial, commercial and infrastructure power distribution applications.
This E2.2H circuit breaker is supplied in a fixed four-pole configuration with rear horizontal terminals. Its Ekip Dip LSI solid-state electronic release provides long-time overload, selective short-circuit and instantaneous short-circuit protection, with DIP-switch adjustment allowing protection parameters to be configured straightforwardly during commissioning and maintenance.
With a 1600 A rated current, an H short-circuit performance level and a rated ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC, the 1SDA071642R1 is engineered for substantial power distribution duties. It provides an 85 kA short-time withstand current for 1 second and is rated for operation up to 690 V AC, making it particularly suitable for switchboards with high prospective fault currents.
Air circuit breakers such as the ABB SACE Emax 2 E2.2H provide switching, isolation and protection for high-current low-voltage distribution circuits. They are commonly installed as incoming, outgoing or bus-coupler breakers in electrical switchboards, where dependable interruption of overload and short-circuit currents is essential for protecting equipment and maintaining continuity of supply.
The Ekip Dip LSI electronic trip unit combines configurable electronic protection with straightforward DIP-switch adjustment. Its long-time, selective short-circuit and instantaneous protection functions enable the breaker to respond appropriately to sustained overloads and different levels of short-circuit fault current, while the high breaking and short-time withstand capabilities of the E2.2H platform support effective protection coordination in demanding electrical networks.
| Series | SACE Emax 2 |
|---|---|
| Frame / product group | E2.2H |
| ABB order code | 1SDA071642R1 |
| EAN | 8015644754921 |
| Product type | Air circuit breaker |
| Rated current (In) | 1600 A |
| Number of poles | 4 |
| Neutral pole current | 100% of Iu |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI – long-time overload, selective short-circuit and instantaneous short-circuit protection |
| Overload protection adjustment | 0.4–1 × In |
| Selective short-circuit protection adjustment | 0.6–10 × In |
| Instantaneous short-circuit protection adjustment | 1.5–15 × In |
| Protection setting method | DIP switches |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw, 1 s) | 85 kA |
| Rated short-time withstand current (Icw, 3 s) | 66 kA |
| Short-circuit performance level | H |
| Frequency | 50 / 60 Hz |
| Installation | Fixed |
| Terminal arrangement | Rear horizontal |
| Main-circuit connection | Bolted |
| Connecting capacity | 1200 mm² |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Power loss | 136 W |
| Mechanical durability | 25,000 cycles |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA071642R1 is a 1600 A four-pole air circuit breaker designed to protect and control high-current low-voltage power distribution circuits in industrial, commercial and infrastructure installations.
The E2.2H 1600 supplied under ABB order code 1SDA071642R1 has a rated current of 1600 A.
The circuit breaker is fitted with an Ekip Dip LSI electronic trip unit, providing long-time overload, selective short-circuit and instantaneous short-circuit protection with settings configured using DIP switches.
The E2.2H 1600 has a rated ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC and 85 kA at 690 V AC, with an 85 kA short-time withstand current for 1 second.
The 1SDA071642R1 is a fixed air circuit breaker with four poles and rear horizontal terminals, intended for permanent installation within compatible low-voltage switchgear and distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine high fault-interruption performance with dependable electronic protection, making the E2.2H range a robust choice for demanding low-voltage distribution systems in industrial, commercial and infrastructure applications.
We use cookies