Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071631R1 Emax 2 E2.2S 1600 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Dip LI electronic protection, 85 kA breaking capacity at 440 V AC and 66 kA short-time withstand current for demanding low-voltage power distribution systems.
£6,665.48
The ABB E2.2S 1600 Ekip Dip LI 4p FHR, order code 1SDA071631R1, is a high-performance four-pole air circuit breaker (ACB) designed for switching and protection in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 1600 A rated uninterrupted current with robust short-circuit performance and straightforward electronic protection for industrial, commercial and infrastructure installations.
The breaker is equipped with the Ekip Dip LI solid-state electronic trip unit, providing long-time overload and instantaneous short-circuit protection. Its DIP-switch configuration provides a practical method of setting the protection functions, making the breaker well suited to applications requiring dependable electronic protection without the additional short-time or earth-fault functions of LSI and LSIG releases.
The E2.2S frame provides an ultimate short-circuit breaking capacity of 85 kA at 440 V AC together with a rated short-time withstand current of 66 kA for 1 s. Its fixed four-pole construction with rear flat horizontal terminals is designed for permanent integration into low-voltage switchboards and busbar assemblies.
Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection for high-current low-voltage electrical systems. By detecting abnormal current conditions and interrupting the circuit when configured thresholds are exceeded, the breaker helps protect cables, busbars, switchgear and connected equipment against potentially damaging overload and short-circuit faults.
The Ekip Dip LI release combines long-time overload protection with instantaneous short-circuit protection in a straightforward electronic platform. This makes the 1SDA071631R1 particularly suitable for distribution circuits where robust high-current protection is required without dedicated short-time selective or earth-fault protection functions.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E2.2S |
| ABB order code | 1SDA071631R1 |
| EAN | 8015644754815 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 1600 A |
| Current type | AC |
| Number of poles | 4 |
| Trip unit | Ekip Dip LI electronic release |
| Release technology | Solid-state electronic |
| Protection functions | L (long-time overload) and I (instantaneous short circuit) |
| Ultimate breaking capacity (Icu) at 440 V AC | 85 kA |
| Rated short-time withstand current (Icw) | 66 kA for 1 s |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Main circuit connection position | Rear |
| Connecting capacity | 1200 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker open/closed indication | Yes |
| Control element | Push button |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Degree of protection | IP30 |
| Electrical durability at ≤440 V | 12,000 operating cycles |
| Electrical durability at 500–690 V | 10,000 operating cycles |
| Mechanical durability | 25,000 operating cycles |
| Maximum operating frequency | 30 cycles per hour |
| Dimensions (W × H × D) | 366 × 371 × 270 mm |
| Net weight | 53 kg |
| Country of origin | Italy |
| Standard | IEC 60947-2 |
The ABB 1SDA071631R1 is a four-pole air circuit breaker designed for switching and protection in high-current low-voltage power distribution systems, including industrial, commercial and infrastructure switchboards.
The ABB E2.2S 1600 has a rated uninterrupted current of 1600 A, making it suitable for substantial low-voltage distribution circuits.
The Ekip Dip LI electronic trip unit provides long-time overload and instantaneous short-circuit protection, with protection settings configured through DIP switches.
The E2.2S has an ultimate short-circuit breaking capacity of 85 kA at 440 V AC and a rated short-time withstand current of 66 kA for 1 s.
The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.
ABB SACE Emax 2 air circuit breakers combine configurable electronic protection with high short-circuit performance and robust construction, providing dependable switching and protection for demanding low-voltage electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.