ABB 1SDA071624R1 SACE Emax 2 E2.2N 1600 A four-pole fixed air circuit breaker with rear horizontal terminals and Ekip Touch LI electronic overload and instantaneous short-circuit protection.
£5,978.45
The ABB E2.2N 1600 Ekip Touch LI 4p FHR, order code 1SDA071624R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for dependable protection and switching in demanding low-voltage power distribution systems. Its E2.2N frame combines a 1600 A current rating with the advanced Ekip Touch LI solid-state electronic trip unit.
The Ekip Touch LI release provides long-time overload and instantaneous short-circuit protection, combining essential circuit protection with ABB's touchscreen-based Ekip interface. The breaker is supplied as a fixed four-pole unit with rear horizontal terminals, four auxiliary contacts and breaker open/closed position indication.
The E2.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA throughout the principal 400–690 V AC range, with service breaking capacity equal to 100% of Icu and a rated short-time withstand current of 66 kA for 1 s. These characteristics make the 1SDA071624R1 a robust solution for industrial, commercial and infrastructure distribution switchboards.
The Ekip Touch LI electronic trip unit combines long-time overload protection with instantaneous short-circuit protection for applications requiring reliable electronic circuit protection without additional short-time or earth-fault stages. Long-time protection safeguards conductors and equipment against sustained overcurrent conditions, while instantaneous protection provides rapid interruption of severe short circuits.
The E2.2N frame complements this electronic protection with 66 kA ultimate breaking capacity across the principal 400–690 V AC range and substantial short-time withstand performance. Combined with the fixed rear-horizontal connection arrangement and touchscreen-based Ekip interface, the 1SDA071624R1 provides an effective solution for modern high-capacity distribution switchboards.
| Series | SACE Emax 2 E2.2 |
|---|---|
| Order code / MPN | 1SDA071624R1 |
| EAN / GTIN | 8015644754747 |
| Product type | Air circuit breaker (ACB) |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4 |
| Short-circuit performance level | N |
| Trip unit | Ekip Touch LI |
| Release type | Electronic / solid-state |
| Protection functions | L (long-time overload), I (instantaneous short circuit) |
| Mounting | Fixed |
| Terminal connection | Rear flat horizontal |
| Terminal type | Bolt |
| Rated voltage | 690 V AC |
| Ultimate breaking capacity (Icu) at 400 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 66 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 66 kA for 1 s; 50 kA for 3 s |
| Suitable for IT networks | Yes, up to 690 V |
| Auxiliary contacts | 4 |
| Breaker position indication | Open/closed |
| Main-circuit screw size | M12 |
| Main-terminal tightening torque | 70 N·m |
| Product width | 366 mm |
| Product height | 371 mm |
| Product depth | 270 mm |
| Net weight | 53 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071624R1 is a SACE Emax 2 E2.2N four-pole fixed air circuit breaker rated at 1600 A, equipped with rear horizontal terminals and an Ekip Touch LI electronic trip unit.
The Ekip Touch LI provides long-time overload (L) and instantaneous short-circuit (I) protection for low-voltage distribution circuits.
The E2.2N 1600 provides an ultimate short-circuit breaking capacity of 66 kA at 400, 415, 440, 500, 525 and 690 V AC, with service breaking capacity equal to 100% of Icu.
The breaker has a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s, supporting robust low-voltage distribution applications.
This model is a fixed-mounted Emax 2 air circuit breaker with rear flat horizontal terminals and bolted main-circuit connections.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection and flexible switchboard integration to provide dependable switching and protection for modern low-voltage electrical distribution systems.