Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071613R1 SACE Emax 2 E2.2B 1600 A four-pole fixed air circuit breaker with rear horizontal terminals and Ekip Dip LSIG electronic overload, short-circuit and earth-fault protection.
£6,416.99
The ABB E2.2B 1600 Ekip Dip LSIG 4p FHR, order code 1SDA071613R1, is a four-pole fixed air circuit breaker (ACB) from the ABB SACE Emax 2 range, engineered for dependable protection and switching in low-voltage power distribution systems. Its E2.2B frame combines a 1600 A current rating with the comprehensive Ekip Dip LSIG electronic trip unit.
The Ekip Dip LSIG solid-state release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection. This four-stage protection arrangement supports effective coordination and comprehensive fault protection while retaining the straightforward configuration characteristics of the Ekip Dip platform.
With an ultimate short-circuit breaking capacity of 42 kA throughout the principal 400–690 V AC range and a rated short-time withstand current of 42 kA for 1 s, the 1SDA071613R1 is suited to industrial, commercial and infrastructure distribution systems. Its fixed construction and rear horizontal terminals provide a robust arrangement for permanent switchboard installation.
The Ekip Dip LSIG electronic trip unit provides four complementary protection functions for low-voltage distribution systems. Long-time protection responds to sustained overload conditions, short-time protection enables selective coordination during short circuits, instantaneous protection rapidly disconnects severe faults, and the integrated G function provides protection against earth-fault currents.
The E2.2B frame complements this electronic protection with 42 kA ultimate breaking capacity across the principal 400–690 V AC operating range and 42 kA short-time withstand capability. This combination makes the 1SDA071613R1 a dependable solution for switchboards requiring comprehensive protection, selectivity and straightforward electronic configuration.
| Series | SACE Emax 2 E2.2 |
|---|---|
| Order code / MPN | 1SDA071613R1 |
| EAN / GTIN | 8015644754631 |
| Product type | Air circuit breaker (ACB) |
| Current type | AC |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4 |
| Neutral pole current | 100% |
| Short-circuit performance level | B |
| Trip unit | Ekip Dip LSIG |
| Release type | Electronic / solid-state |
| Protection functions | L (long-time overload), S (short-time selective short circuit), I (instantaneous short circuit), G (earth fault) |
| Integrated earth-fault protection | Yes |
| Mounting | Fixed |
| Terminal connection | Rear flat horizontal |
| Terminal type | Bolt |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate breaking capacity (Icu) at 400 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 42 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 42 kA for 1 s; 42 kA for 3 s |
| Suitable for IT networks | Yes, up to 690 V |
| Power loss | 136 W |
| Electrical durability at ≤440 V AC | 12000 cycles |
| Electrical durability at 500–690 V AC | 10000 cycles |
| Mechanical durability | 25000 cycles |
| Main-circuit screw size | M12 |
| Main-terminal tightening torque | 70 N·m |
| Standard | IEC 60947-2 |
The ABB 1SDA071613R1 is a SACE Emax 2 E2.2B four-pole fixed air circuit breaker rated at 1600 A, equipped with rear horizontal terminals and an Ekip Dip LSIG electronic trip unit.
The Ekip Dip LSIG provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection for low-voltage distribution circuits.
The E2.2B 1600 provides an ultimate short-circuit breaking capacity of 42 kA at 400, 415, 440, 500, 525 and 690 V AC, with service breaking capacity equal to 100% of Icu.
Yes. The Ekip Dip LSIG trip unit incorporates the G protection function for earth-fault protection in addition to long-time, short-time and instantaneous protection.
This model is a fixed-mounted Emax 2 air circuit breaker with rear flat horizontal terminals and bolted main-circuit connections.
ABB SACE Emax 2 air circuit breakers combine dependable short-circuit performance, comprehensive electronic protection and flexible switchboard integration to provide reliable switching and protection for modern low-voltage electrical distribution systems.