1SDA071596R1 ABB E2.2S 1250 Ekip Touch LSIG 4p FHR Air Circuit Breaker

1SDA071596R1 ABB E2.2S 1250 Ekip Touch LSIG 4p FHR Air Circuit Breaker

ABB 1SDA071596R1 Emax 2 E2.2S 1250 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Touch LSIG electronic protection and 85 kA breaking capacity at 400–440 V AC for comprehensive low-voltage power distribution protection.

SKU: 1SDA071596R1MPN: 1SDA071596R1
Price
List Price £9,452.48 ex VAT
Your Price (ex VAT) Save 25%
£7,089.36 25% OFF
You save £2,363.12 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,089.36
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,089.36

Why Choose the ABB E2.2S 1250 Ekip Touch LSIG 4p FHR Air Circuit Breaker?

The ABB E2.2S 1250 Ekip Touch LSIG 4p FHR, order code 1SDA071596R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 1250 A rated current with comprehensive electronic LSIG protection and high short-circuit breaking performance for industrial, commercial and infrastructure installations.

The breaker is equipped with the Ekip Touch LSIG electronic trip unit, providing long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection. Its electronic interface supports configurable protection settings, making the breaker well suited to distribution systems where selective coordination and comprehensive fault protection are required.

With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, the 1SDA071596R1 provides robust fault interruption across demanding low-voltage applications. Its fixed four-pole construction with rear flat horizontal terminals is designed for permanent integration into switchboards and busbar assemblies.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 1250 A rated uninterrupted current for substantial industrial, commercial and infrastructure loads.
  • Four-pole configuration for switching and protection of three-phase systems with neutral.
  • Ekip Touch LSIG electronic trip unit provides overload, short-circuit and earth-fault protection.
  • 85 kA ultimate breaking capacity at 400–440 V AC for high prospective fault-current applications.
  • 66 kA short-time withstand current for 1 s supports selective protection schemes.
  • Adjustable overload, delayed short-circuit and instantaneous short-circuit protection provides flexible system coordination.
  • Fixed installation with rear flat horizontal terminals for efficient switchboard and busbar integration.

Key Features

  • ABB SACE Emax 2 E2.2S series.
  • 1250 A rated uninterrupted current.
  • Four-pole air circuit breaker.
  • Fixed mounting configuration.
  • Rear flat horizontal terminals.
  • Ekip Touch LSIG solid-state electronic release.
  • Long-time overload protection.
  • Short-time selective short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • Overload adjustment range of 500–1250 A.
  • Delayed short-circuit adjustment range of 750–12500 A.
  • Instantaneous short-circuit adjustment range of 1875–18750 A.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.

Comprehensive LSIG Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection for high-current low-voltage electrical systems. By detecting abnormal current conditions and interrupting the circuit when configured thresholds are exceeded, the breaker helps protect cables, busbars, switchgear and connected equipment against damaging overload, short-circuit and earth-fault conditions.

The Ekip Touch LSIG release combines long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. Its adjustable protection ranges provide flexibility when coordinating upstream and downstream protective devices, while the dedicated earth-fault function adds protection against faults involving earth conductors and grounded parts of the electrical system.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical infrastructure.
  • Manufacturing and process plant switchgear.
  • Transformer-fed distribution systems.
  • Systems requiring selective short-circuit and earth-fault protection.
  • Critical infrastructure and utility electrical distribution.
  • OEM low-voltage switchgear and busbar assemblies.

Technical Specifications

Product group Emax2 Air Circuit Breaker
Series SACE Emax 2 E2.2S
ABB order code 1SDA071596R1
EAN 8015644754464
Product type Air circuit breaker
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Number of poles 4
Trip unit Ekip Touch LSIG electronic release
Release type Electronic
Protection functions L (long-time overload), S (short-time short circuit), I (instantaneous short circuit) and G (earth fault)
Overload release adjustment range 500–1250 A
Delayed short-circuit release adjustment range 750–12500 A
Instantaneous short-circuit release adjustment range 1875–18750 A
Integrated earth-fault protection Yes
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate breaking capacity (Icu) at 400 V AC 85 kA
Ultimate breaking capacity (Icu) at 415 V AC 85 kA
Ultimate breaking capacity (Icu) at 440 V AC 85 kA
Ultimate breaking capacity (Icu) at 500 / 525 V AC 66 kA
Ultimate breaking capacity (Icu) at 690 V AC 66 kA
Service breaking capacity (Ics) at 400–440 V AC 85 kA
Service breaking capacity (Ics) at 500–690 V AC 66 kA
Rated short-time withstand current (Icw) 66 kA for 1 s; 50 kA for 3 s
Installation Fixed
Terminal arrangement Rear flat horizontal
Main circuit connection Bolt connection
Recommended main-circuit screw size M12
Terminal tightening torque 70 N·m
Auxiliary contacts 4 change-over contacts
Protection rating IP30
Power loss 83 W
Optional motor operator Yes
Integrated motor operator No
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071596R1 used for?

The ABB 1SDA071596R1 is a four-pole air circuit breaker designed for switching and comprehensive fault protection in high-current low-voltage power distribution systems, including industrial, commercial and infrastructure switchboards.

What is the rated current of the ABB E2.2S 1250?

The ABB E2.2S 1250 has a rated uninterrupted current of 1250 A, with its overload release adjustable across 500–1250 A.

What protection does the Ekip Touch LSIG trip unit provide?

The Ekip Touch LSIG electronic trip unit provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection for comprehensive low-voltage distribution protection.

What is the breaking capacity of the ABB 1SDA071596R1?

The E2.2S has an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, providing robust fault-current interruption for demanding distribution systems.

What does FHR mean on the ABB E2.2S 1250?

The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.

Trusted Power Distribution Technology from ABB

ABB SACE Emax 2 air circuit breakers combine configurable electronic protection with high short-circuit performance and robust construction, providing dependable switching and comprehensive protection for demanding low-voltage electrical distribution systems.