ABB 1SDA071596R1 Emax 2 E2.2S 1250 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Touch LSIG electronic protection and 85 kA breaking capacity at 400–440 V AC for comprehensive low-voltage power distribution protection.
£7,089.36
The ABB E2.2S 1250 Ekip Touch LSIG 4p FHR, order code 1SDA071596R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 1250 A rated current with comprehensive electronic LSIG protection and high short-circuit breaking performance for industrial, commercial and infrastructure installations.
The breaker is equipped with the Ekip Touch LSIG electronic trip unit, providing long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection. Its electronic interface supports configurable protection settings, making the breaker well suited to distribution systems where selective coordination and comprehensive fault protection are required.
With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, the 1SDA071596R1 provides robust fault interruption across demanding low-voltage applications. Its fixed four-pole construction with rear flat horizontal terminals is designed for permanent integration into switchboards and busbar assemblies.
Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection for high-current low-voltage electrical systems. By detecting abnormal current conditions and interrupting the circuit when configured thresholds are exceeded, the breaker helps protect cables, busbars, switchgear and connected equipment against damaging overload, short-circuit and earth-fault conditions.
The Ekip Touch LSIG release combines long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. Its adjustable protection ranges provide flexibility when coordinating upstream and downstream protective devices, while the dedicated earth-fault function adds protection against faults involving earth conductors and grounded parts of the electrical system.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E2.2S |
| ABB order code | 1SDA071596R1 |
| EAN | 8015644754464 |
| Product type | Air circuit breaker |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 4 |
| Trip unit | Ekip Touch LSIG electronic release |
| Release type | Electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit) and G (earth fault) |
| Overload release adjustment range | 500–1250 A |
| Delayed short-circuit release adjustment range | 750–12500 A |
| Instantaneous short-circuit release adjustment range | 1875–18750 A |
| Integrated earth-fault protection | Yes |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate breaking capacity (Icu) at 400 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 500 / 525 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 66 kA |
| Service breaking capacity (Ics) at 400–440 V AC | 85 kA |
| Service breaking capacity (Ics) at 500–690 V AC | 66 kA |
| Rated short-time withstand current (Icw) | 66 kA for 1 s; 50 kA for 3 s |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Recommended main-circuit screw size | M12 |
| Terminal tightening torque | 70 N·m |
| Auxiliary contacts | 4 change-over contacts |
| Protection rating | IP30 |
| Power loss | 83 W |
| Optional motor operator | Yes |
| Integrated motor operator | No |
| Standard | IEC 60947-2 |
The ABB 1SDA071596R1 is a four-pole air circuit breaker designed for switching and comprehensive fault protection in high-current low-voltage power distribution systems, including industrial, commercial and infrastructure switchboards.
The ABB E2.2S 1250 has a rated uninterrupted current of 1250 A, with its overload release adjustable across 500–1250 A.
The Ekip Touch LSIG electronic trip unit provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection for comprehensive low-voltage distribution protection.
The E2.2S has an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, providing robust fault-current interruption for demanding distribution systems.
The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.
ABB SACE Emax 2 air circuit breakers combine configurable electronic protection with high short-circuit performance and robust construction, providing dependable switching and comprehensive protection for demanding low-voltage electrical distribution systems.