Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071583R1 Emax 2 E2.2N 1250 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Dip LSIG electronic protection and 66 kA breaking capacity across 400–690 V AC for comprehensive low-voltage power distribution protection.
£6,504.65
The ABB E2.2N 1250 Ekip Dip LSIG 4p FHR, order code 1SDA071583R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 1250 A rated current with comprehensive electronic LSIG protection and robust short-circuit performance for industrial, commercial and infrastructure installations.
The breaker is equipped with the Ekip Dip LSIG electronic trip unit, providing long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection. Protection thresholds are configured through DIP switches, providing a straightforward method of adapting the breaker to the electrical installation while supporting selective coordination and earth-fault protection.
With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 66 kA across 400–690 V AC, the 1SDA071583R1 provides dependable fault interruption across demanding low-voltage distribution applications. Its fixed four-pole construction with rear flat horizontal terminals is designed for permanent integration into switchboards and busbar assemblies.
Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection for high-current low-voltage electrical systems. By detecting abnormal current conditions and interrupting the circuit when configured thresholds are exceeded, the breaker helps protect cables, busbars, switchgear and connected equipment against damaging overload, short-circuit and earth-fault conditions.
The Ekip Dip LSIG release combines long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. Compared with an LSI configuration, the additional G function provides dedicated earth-fault protection, making the 1SDA071583R1 particularly suitable for distribution systems requiring comprehensive fault protection and selective coordination.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E2.2N |
| ABB order code | 1SDA071583R1 |
| EAN | 8015644754334 |
| Product type | Air circuit breaker |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 4 |
| Neutral pole current | 100% |
| Trip unit | Ekip Dip LSIG electronic release |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit) and G (earth fault) |
| Overload protection adjustment | 0.4–1 × In |
| Overload protection adjustment range | 500–1250 A |
| Short-time protection | Adjustable |
| Instantaneous protection adjustment | 1.5–15 × In |
| Earth-fault protection adjustment | 0.1–1 × In |
| Protection setting method | DIP switches |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50 / 60 Hz |
| Ultimate breaking capacity (Icu) at 400 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 500 / 525 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 66 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 66 kA for 1 s; 50 kA for 3 s |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Connecting capacity | 1200 mm² |
| Recommended main-circuit screw size | M12 |
| Terminal tightening torque | 70 N·m |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Power loss | 83 W |
| Electrical durability | 15,000 operating cycles |
| Mechanical durability | 25,000 operating cycles |
| Dimensions (W × H × D) | 366 × 371 × 270 mm |
| Net weight | 53 kg |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC 60947-2 |
The ABB 1SDA071583R1 is a four-pole air circuit breaker designed for switching and comprehensive fault protection in high-current low-voltage power distribution systems, including industrial, commercial and infrastructure switchboards.
The ABB E2.2N 1250 has a rated uninterrupted current of 1250 A, with long-time overload protection adjustable from 500–1250 A.
The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, with protection settings configured through DIP switches.
The E2.2N has an ultimate short-circuit breaking capacity of 66 kA across 400–690 V AC, with a rated service breaking capacity equal to 100% of Icu.
The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.
ABB SACE Emax 2 air circuit breakers combine configurable electronic protection with robust short-circuit performance and durable construction, providing dependable switching and comprehensive protection for demanding low-voltage electrical distribution systems.
We use cookies