ABB 1SDA071568R1 Emax 2 E2.2S 1000 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Hi-Touch LSI electronic protection and 85 kA breaking capacity at 380–440 V AC for advanced low-voltage power distribution protection and monitoring.
£9,091.94
The ABB E2.2S 1000 Ekip Hi-Touch LSI 4p FHR, order code 1SDA071568R1, is a high-performance four-pole air circuit breaker (ACB) designed for advanced protection, measurement and monitoring in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a 1000 A rated current, high short-circuit breaking performance and the sophisticated Ekip Hi-Touch LSI electronic trip unit.
The Ekip Hi-Touch LSI electronic release provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Its advanced platform also incorporates measurement and network analysis capabilities, providing detailed electrical information alongside configurable protection functions for sophisticated industrial and infrastructure distribution systems.
With a rated operational voltage of up to 690 V AC and an ultimate short-circuit breaking capacity of 85 kA at 380–440 V AC, the 1SDA071568R1 is engineered for substantial low-voltage distribution duties. Its four-pole fixed configuration with rear flat horizontal terminals enables permanent integration into switchboards and busbar assemblies.
Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection for high-current low-voltage electrical systems. The Ekip Hi-Touch platform extends this capability with advanced measurement and analysis functions, allowing the breaker to contribute to both electrical protection and detailed monitoring of the distribution network.
The Ekip Hi-Touch LSI release combines long-time overload, short-time selective and instantaneous short-circuit protection. Together with integrated Ekip Measuring Pro and Network Analyzer functionality, the 1SDA071568R1 is particularly suited to installations requiring effective protection coordination, high breaking capacity and detailed visibility of electrical system performance.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E2.2S |
| ABB order code | 1SDA071568R1 |
| EAN | 8015644754181 |
| Product type | Air circuit breaker |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 4 |
| Trip unit | Ekip Hi-Touch LSI electronic release |
| Protection functions | L (long-time overload), S (short-time short circuit) and I (instantaneous short circuit) |
| Overload protection adjustment | 0.4–1 × In |
| Overload protection adjustment range | 400–1000 A |
| Instantaneous protection adjustment | 1.5–15 × In |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Ultimate breaking capacity (Icu) at 380 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 400 / 415 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 500 / 525 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 66 kA |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Integrated measurement | Ekip Measuring Pro |
| Network analysis | Integrated Network Analyzer |
| Configuration interface | Touch-sensitive display |
| Dimensions (W × H × D) | 366 × 371 × 270 mm |
| Net weight | 53 kg |
| Country of origin | Italy |
| Standard | IEC 60947-2 |
The ABB 1SDA071568R1 is a four-pole air circuit breaker designed for advanced switching, protection, measurement and monitoring in high-current low-voltage power distribution systems.
The ABB E2.2S 1000 has a rated uninterrupted current of 1000 A, with the long-time overload protection adjustable from 400–1000 A.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection, together with advanced measurement and network analysis functionality.
The E2.2S has an ultimate short-circuit breaking capacity of 85 kA at 380–440 V AC and 66 kA at 500–690 V AC, providing robust fault-current interruption for demanding distribution systems.
The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.