ABB 1SDA071562R1 Emax 2 E2.2S 1000 is a 1000 A four-pole fixed air circuit breaker with rear horizontal terminals and an Ekip Dip LSI electronic trip unit for long-time, short-time and instantaneous circuit protection.
£6,373.11
The ABB E2.2S 1000 Ekip Dip LSI 4p FHR, order code 1SDA071562R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for switching and protection in low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, this fixed four-pole circuit breaker combines a 1000 A rated current with an Ekip Dip LSI solid-state electronic trip unit.
The Ekip Dip LSI release provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. This combination enables effective protection coordination in industrial and commercial distribution networks, while DIP-switch adjustment provides a practical method for configuring the principal protection settings without requiring a touchscreen interface.
The E2.2S performance level provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, fixed construction and rear flat horizontal terminals, the 1SDA071562R1 is well suited to main switchboards, incomers and high-current feeder circuits in demanding power distribution installations.
Air circuit breakers such as the ABB Emax 2 E2.2S provide switching and protection at critical points within low-voltage distribution networks. The E2.2S frame combines high current-carrying capability with substantial short-circuit performance, making it suitable for main switchboards, transformer-fed distribution systems and industrial installations where continuity and selective fault isolation are important.
The Ekip Dip LSI release provides three complementary protection functions. Long-time protection responds to sustained overloads, short-time protection enables selective coordination during short-circuit conditions, and instantaneous protection responds rapidly to severe faults. Together these functions help protect conductors, switchgear and connected equipment while supporting coordinated operation with other protective devices.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2S |
| ABB order code | 1SDA071562R1 |
| EAN | 8015644754129 |
| Product type | Air circuit breaker |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 4 |
| Neutral pole current | 100% |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Icu at 400 / 415 / 440 V AC | 85 kA |
| Icu at 500 / 690 V AC | 66 kA |
| Rated service breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Installation | Fixed |
| Terminal connection | Rear flat horizontal |
| Terminal type | Bolt |
| Auxiliary contacts | 4 |
| Power loss | 53 W |
| Electrical durability | 15,000 cycles |
| Mechanical durability | 25,000 cycles |
| Standard | IEC 60947-2 |
| Net weight | 53 kg |
It is a 1000 A four-pole air circuit breaker designed to switch and protect high-current low-voltage AC distribution circuits in industrial, commercial and infrastructure installations.
The Ekip Dip LSI electronic release provides long-time overload protection, short-time selective short-circuit protection and instantaneous short-circuit protection.
The E2.2S 1000 provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC.
This version is a fixed air circuit breaker supplied with rear flat horizontal terminals for connection within low-voltage switchgear.
Short-time protection can introduce controlled selectivity between protective devices, helping a downstream breaker clear a fault before the upstream Emax 2 breaker operates and therefore helping maintain supply to unaffected circuits.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, configurable electronic protection and robust switchboard integration to provide dependable protection for modern low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.