1SDA071560R1 ABB E2.2N 1000 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker

1SDA071560R1 ABB E2.2N 1000 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker

ABB 1SDA071560R1 SACE Emax 2 E2.2N 1000 A four-pole fixed air circuit breaker with rear horizontal terminals and Ekip G Hi-Touch LSIG electronic protection for generator and low-voltage power distribution applications.

SKU: 1SDA071560R1MPN: 1SDA071560R1
Price
List Price £12,765.73 ex VAT
Your Price (ex VAT) Save 25%
£9,574.30 25% OFF
You save £3,191.43 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,574.30
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,574.30

Why Choose the ABB E2.2N 1000 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker?

The ABB E2.2N 1000 Ekip G Hi-Touch LSIG 4p FHR, order code 1SDA071560R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for advanced generator and low-voltage distribution protection. Its E2.2N frame combines dependable short-circuit performance with the sophisticated Ekip G Hi-Touch LSIG solid-state electronic release.

Rated at 1000 A, this breaker uses a fixed installation configuration with rear horizontal terminals and a 100% rated neutral pole. The Ekip G Hi-Touch LSIG release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection together with advanced generator-oriented protection, measurement and power-management functionality.

The E2.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA from 400 to 690 V AC, with a rated short-time withstand current of 66 kA for 1 s. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and rated impulse withstand voltage of 12 kV, the 1SDA071560R1 is engineered for demanding generator, industrial and critical-power installations.

Key Advantages

  • Advanced ABB SACE Emax 2 E2.2N air circuit breaker for generator and distribution protection.
  • 1000 A rated current for high-capacity low-voltage circuits.
  • Four-pole configuration with 100% rated neutral pole.
  • Ekip G Hi-Touch LSIG electronic release for sophisticated protection and monitoring.
  • Provides overload, selective short-circuit, instantaneous and earth-fault protection.
  • 66 kA ultimate breaking capacity across 400–690 V AC applications.
  • 66 kA for 1 s short-time withstand capability supports selective distribution systems.
  • Fixed construction with rear horizontal terminals for switchboard integration.

Key Features

  • ABB SACE Emax 2 E2.2N air circuit breaker.
  • 1000 A rated uninterrupted current.
  • 4-pole construction.
  • 100% neutral pole current.
  • Fixed-mounted configuration.
  • Rear horizontal terminals.
  • Ekip G Hi-Touch LSIG solid-state electronic release.
  • Long-time overload protection.
  • Short-time selective short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • Advanced generator-oriented protection and measurement capabilities.
  • Suitable for IT networks up to 690 V.
  • Supplied with four auxiliary change-over contacts and breaker open/closed indication.

Advanced Generator Protection with Ekip G Hi-Touch

The Ekip G Hi-Touch LSIG electronic trip unit combines comprehensive circuit protection with advanced functionality for generator applications. Its L, S, I and G protection stages address sustained overloads, selective short circuits, severe instantaneous faults and earth faults while providing sophisticated measurement and monitoring capabilities for critical electrical systems.

The ABB SACE Emax 2 platform combines protection, switching and power-management functionality within a robust circuit-breaker architecture. The E2.2N 1000 configuration offers 66 kA breaking performance throughout its principal AC voltage range, making it particularly suitable for generator switchboards and distribution systems requiring high selectivity and dependable fault interruption.

Typical Applications

  • Generator protection and generating sets.
  • Standby and emergency power systems.
  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process facilities.
  • Data centres and critical power installations.
  • Transformer distribution systems.
  • Power control centres and automated switchboards.

Technical Specifications

Series SACE Emax 2 E2.2
Order code / MPN 1SDA071560R1
EAN 8015644754105
Product type Air circuit breaker (ACB)
Rated current (In) 1000 A
Rated uninterrupted current (Iu) 1000 A
Number of poles 4
Neutral pole current 100%
Performance level N
Trip unit Ekip G Hi-Touch LSIG
Trip unit type Electronic / solid-state
Protection functions L (overload), S (selective short circuit), I (instantaneous short circuit), G (earth fault)
Integrated earth-fault protection Yes
Mounting Fixed
Terminals Rear horizontal
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate breaking capacity (Icu) at 400/415 V AC 66 kA
Ultimate breaking capacity (Icu) at 440 V AC 66 kA
Ultimate breaking capacity (Icu) at 500/525 V AC 66 kA
Ultimate breaking capacity (Icu) at 690 V AC 66 kA
Service breaking capacity (Ics) 66 kA
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 66 kA for 1 s; 50 kA for 3 s
Power loss 53 W
Electrical durability 15000 cycles
Mechanical durability 25000 cycles
Auxiliary change-over contacts 4
Protection rating IP30
Dimensions (W × H × D) 366 × 371 × 270 mm
Net weight 53 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071560R1?

The ABB 1SDA071560R1 is a SACE Emax 2 E2.2N four-pole fixed air circuit breaker rated at 1000 A, equipped with rear horizontal terminals and an Ekip G Hi-Touch LSIG electronic trip unit.

What protection functions does the Ekip G Hi-Touch LSIG provide?

The Ekip G Hi-Touch LSIG provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection together with advanced generator-oriented protection and monitoring functionality.

What is the breaking capacity of the ABB E2.2N 1000?

The E2.2N 1000 provides an ultimate short-circuit breaking capacity of 66 kA at 400, 415, 440, 500, 525 and 690 V AC.

Is the ABB 1SDA071560R1 suitable for generator protection?

Yes. The Ekip G Hi-Touch electronic release is designed for advanced generator and installation protection, combining LSIG functions with sophisticated measurement, monitoring and power-management capabilities.

What terminal configuration does the ABB 1SDA071560R1 use?

This model is a fixed-mounted Emax 2 air circuit breaker equipped with rear horizontal terminals for integration into low-voltage switchboards.

Trusted Generator and Low-Voltage Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection and power-management capabilities to provide dependable switching and protection for generator and modern low-voltage distribution systems.