Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071551R1 is a SACE Emax 2 E2.2N 1000 A fixed four-pole air circuit breaker with rear horizontal terminals, an Ekip Dip LI electronic trip unit, 690 V AC rated operational voltage and 66 kA breaking capacity across 380–690 V AC.
£5,466.87
The ABB 1SDA071551R1 is a high-performance SACE Emax 2 E2.2N air circuit breaker (ACB) designed for reliable protection and control of demanding low-voltage electrical distribution systems. Rated at 1000 A, this fixed four-pole circuit breaker combines ABB’s E2.2N frame with the Ekip Dip LI electronic trip unit for adjustable long-time overload and instantaneous short-circuit protection.
As part of the ABB SACE Emax 2 series, the E2.2N provides high short-circuit performance together with straightforward electronic protection. The Ekip Dip LI release uses DIP-switch adjustment for its protection settings, providing a practical solution where dependable overload and instantaneous fault protection are required without short-time delayed or integrated ground-fault functions.
With a rated uninterrupted current of 1000 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA across 380–690 V AC, the 1SDA071551R1 provides robust protection across a wide range of low-voltage distribution applications. This version features a fixed four-pole configuration with rear horizontal terminals, making it particularly suitable for switchboards with rear busbar connections.
Air circuit breakers such as the ABB SACE Emax 2 E2.2N protect important low-voltage distribution circuits against damaging overload and short-circuit conditions. The 1SDA071551R1 combines a 1000 A continuous-current rating with 66 kA ultimate short-circuit breaking capability throughout the 380–690 V AC range, providing dependable protection for demanding main incomers and distribution circuits.
The Ekip Dip LI trip unit provides adjustable electronic long-time overload and instantaneous short-circuit protection through straightforward DIP-switch settings. Combined with the breaker’s four-pole fixed construction and rear horizontal terminal arrangement, this configuration is well suited to switchboards where high fault capability, simple protection configuration and practical rear busbar connectivity are required.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E2.2N |
| Order code / MPN | 1SDA071551R1 |
| Product type | Air circuit breaker |
| Short-circuit performance level | N |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Number of poles | 4 |
| Trip unit | Ekip Dip LI |
| Release type | Solid-state electronic |
| Protection functions | LI |
| Overload protection adjustment | 0.4–1 × In |
| Overload protection adjustment range | 400–1000 A |
| Instantaneous protection adjustment | 1.5–15 × In |
| Instantaneous protection adjustment range | 1500–15,000 A |
| Long-time overload protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Short-time delayed short-circuit protection | No |
| Integrated ground-fault protection | No |
| Protection setting method | DIP switches |
| Current type | AC |
| Installation version | Fixed |
| Terminal configuration | Rear horizontal |
| Product net weight | 53 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071551R1 is a 1000 A Emax 2 air circuit breaker designed to protect and control low-voltage electrical distribution circuits in industrial, commercial and infrastructure switchboards.
The ABB 1SDA071551R1 has a rated uninterrupted current of 1000 A and a rated operational voltage of 690 V AC.
The E2.2N 1000 provides a rated ultimate short-circuit breaking capacity of 66 kA at 380 V, 400–415 V, 440 V, 500–525 V and 690 V AC.
The Ekip Dip LI electronic trip unit provides adjustable long-time overload and instantaneous short-circuit protection. Overload protection is adjustable from 0.4–1 × In and instantaneous protection from 1.5–15 × In. This LI configuration does not include short-time delayed or integrated ground-fault protection.
The 1SDA071551R1 is a fixed four-pole air circuit breaker with rear horizontal terminals, providing a practical connection arrangement for busbars within low-voltage switchboard assemblies.
ABB SACE Emax 2 air circuit breakers combine dependable electronic protection, high short-circuit performance and flexible installation configurations for reliable operation in modern industrial, commercial and infrastructure low-voltage distribution systems.
We use cookies