Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071513R1 Emax 2 E1.2N 1600 A four-pole fixed air circuit breaker with front terminals, Ekip Dip LSIG electronic protection and 66 kA breaking capacity at 380–440 V AC for demanding low-voltage power distribution systems.
£6,605.70
The ABB E1.2N 1600 Ekip Dip LSIG 4p F F, order code 1SDA071513R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 series, it combines a 1600 A rated current with comprehensive electronic LSIG protection and robust short-circuit performance for demanding industrial, commercial and infrastructure installations.
This fixed circuit breaker is equipped with the Ekip Dip LSIG electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Its adjustable protection functions enable the breaker to be configured to suit the requirements of the electrical installation, supporting effective selectivity and coordination with upstream and downstream protective devices.
With a rated current of 1600 A, four-pole construction and an ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC, the 1SDA071513R1 provides dependable protection for substantial low-voltage distribution systems. Its fixed configuration with front terminals enables permanent integration into switchboards, power distribution panels and industrial electrical assemblies.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current electrical distribution systems against potentially damaging fault conditions. By automatically interrupting the circuit when configured protection thresholds are exceeded, the breaker helps safeguard cables, busbars, switchgear and connected equipment while supporting reliable operation of the wider electrical installation.
The Ekip Dip LSIG trip unit combines long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. This comprehensive protection package makes the E1.2N particularly suitable for main and distribution switchboards where effective selectivity, high fault-current interruption capability and protection against earth faults are required.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E1.2N |
| ABB order code | 1SDA071513R1 |
| Product type | Air circuit breaker |
| Rated current | 1600 A |
| Number of poles | 4 |
| Trip unit | Ekip Dip LSIG electronic release |
| Protection functions | L (overload), S (short-time short circuit), I (instantaneous short circuit) and G (earth fault) |
| Overload protection adjustment | 640–1600 A |
| Instantaneous short-circuit adjustment | 2400–24000 A |
| Rated operational voltage (Ue) | up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate breaking capacity (Icu) at 380 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 400 / 415 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 500 / 525 V AC | 50 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 50 kA |
| Frequency | 50 / 60 Hz |
| Installation | Fixed |
| Terminal arrangement | Front terminals |
| Standard | IEC 60947-2 |
The ABB 1SDA071513R1 is a four-pole air circuit breaker used for switching and protection in high-current low-voltage power distribution systems, including industrial, commercial and infrastructure switchboards.
This Emax 2 air circuit breaker has a rated current of 1600 A.
The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection for comprehensive low-voltage distribution protection.
The E1.2N has an ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC.
The 1SDA071513R1 is a fixed air circuit breaker with front terminals, designed for permanent installation within compatible low-voltage switchgear and electrical distribution assemblies.
ABB SACE Emax 2 air circuit breakers are engineered for dependable switching and protection in modern low-voltage power distribution systems, combining advanced electronic protection with robust short-circuit performance for demanding electrical installations.
We use cookies