1SDA071511R1 ABB E1.2N 1600 Ekip Dip LI 4p F F Air Circuit Breaker

1SDA071511R1 ABB E1.2N 1600 Ekip Dip LI 4p F F Air Circuit Breaker

ABB 1SDA071511R1 SACE Emax 2 E1.2N 1600 A four-pole fixed air circuit breaker with Ekip Dip LI electronic overload and instantaneous short-circuit protection for low-voltage power distribution systems.

SKU: 1SDA071511R1MPN: 1SDA071511R1
Price
List Price £7,744.26 ex VAT
Your Price (ex VAT) Save 25%
£5,808.20 25% OFF
You save £1,936.07 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,808.20
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,808.20

Why Choose the ABB E1.2N 1600 Ekip Dip LI 4p F F Air Circuit Breaker?

The ABB E1.2N 1600 Ekip Dip LI 4p F F, order code 1SDA071511R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 E1.2 series, it combines a compact fixed breaker platform with the Ekip Dip LI electronic trip unit for dependable overload and instantaneous short-circuit protection.

Rated at 1600 A, this E1.2N breaker features a fixed installation configuration with front terminals. Its Ekip Dip LI electronic release provides adjustable long-time overload and instantaneous short-circuit protection, with settings configured through DIP switches for straightforward commissioning and protection coordination.

The E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and operation at 50 / 60 Hz, the 1SDA071511R1 is well suited to demanding industrial and commercial power distribution installations.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for low-voltage distribution.
  • 1600 A rated current for high-capacity electrical distribution circuits.
  • Four-pole configuration suitable for three-phase systems with neutral.
  • Ekip Dip LI electronic trip unit provides overload and instantaneous short-circuit protection.
  • Adjustable overload protection from 0.4–1 × In.
  • Adjustable instantaneous protection from 1.5–15 × In.
  • Ultimate short-circuit breaking capacity up to 66 kA.
  • Fixed-mounted construction with front terminals for switchboard integration.

Key Features

  • ABB SACE Emax 2 E1.2N air circuit breaker.
  • 1600 A rated current.
  • 4-pole construction.
  • Fixed-mounted configuration.
  • Front terminals.
  • Ekip Dip LI electronic protection release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • DIP-switch adjustment for straightforward protection configuration.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • Designed in accordance with IEC 60947-2.

Reliable LI Protection for Power Distribution

The Ekip Dip LI electronic trip unit provides two essential protection functions for low-voltage electrical networks. Long-time protection responds to sustained overload conditions, while instantaneous protection rapidly disconnects severe short-circuit faults to help protect conductors, switchgear and connected equipment.

The ABB SACE Emax 2 platform combines high electrical performance with compact switchboard integration. The fixed E1.2N configuration is particularly suitable for installations requiring high breaking capacity, dependable high-current switching and straightforward electronic protection adjustment.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial buildings and infrastructure.
  • Transformer and generator distribution boards.
  • Power control centres and industrial distribution panels.

Technical Specifications

Series SACE Emax 2 E1.2
Order code / MPN 1SDA071511R1
Product type Air circuit breaker (ACB)
Rated current 1600 A
Number of poles 4
Performance level N
Trip unit Ekip Dip LI
Trip unit type Electronic / solid-state
Protection functions L (overload), I (instantaneous short circuit)
Overload protection adjustment 0.4–1 × In
Overload adjustment range 640–1600 A
Instantaneous protection adjustment 1.5–15 × In
Instantaneous adjustment range 2400–24000 A
Mounting Fixed
Terminals Front
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Ultimate breaking capacity (Icu) at 380 V AC 66 kA
Ultimate breaking capacity (Icu) at 400 / 415 V AC 66 kA
Ultimate breaking capacity (Icu) at 440 V AC 66 kA
Ultimate breaking capacity (Icu) at 500 / 525 V AC 50 kA
Ultimate breaking capacity (Icu) at 690 V AC 50 kA
Frequency 50 / 60 Hz
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071511R1?

The ABB 1SDA071511R1 is a SACE Emax 2 E1.2N four-pole fixed air circuit breaker rated at 1600 A and equipped with an Ekip Dip LI electronic trip unit.

What protection functions does the Ekip Dip LI provide?

The Ekip Dip LI provides long-time overload (L) and instantaneous short-circuit (I) protection for low-voltage power distribution circuits.

What is the breaking capacity of the ABB E1.2N 1600?

The breaker provides an ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC.

How is the Ekip Dip LI trip unit adjusted?

Protection thresholds are configured using DIP switches, with overload protection adjustable from 0.4–1 × In and instantaneous protection adjustable from 1.5–15 × In.

Is the ABB 1SDA071511R1 fixed or withdrawable?

This model is a fixed-mounted Emax 2 air circuit breaker with front terminals for integration into low-voltage switchboards.

Trusted Low-Voltage Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high breaking performance, configurable electronic protection and compact construction to provide dependable switching and protection for modern low-voltage power distribution systems.