Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071503R1 SACE Emax 2 E1.2C 1600 A four-pole fixed air circuit breaker with Ekip Dip LSIG electronic overload, short-circuit and earth-fault protection for low-voltage power distribution systems.
£6,048.96
The ABB E1.2C 1600 Ekip Dip LSIG 4p F F, order code 1SDA071503R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 E1.2 series, it combines a compact breaker platform with the Ekip Dip LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.
Rated at 1600 A, this E1.2C breaker features a fixed installation configuration with front terminals. Its Ekip Dip LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, with protection settings configured through straightforward DIP switches.
The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V AC and operation at 50 / 60 Hz, the 1SDA071503R1 is well suited to demanding industrial and commercial power distribution systems.
The Ekip Dip LSIG electronic trip unit provides four essential protection functions for low-voltage electrical networks. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during short circuits, instantaneous protection rapidly disconnects severe faults, and the ground protection function detects potentially hazardous earth-fault currents.
The ABB SACE Emax 2 platform combines high electrical performance with compact switchboard integration. The fixed E1.2C configuration is particularly suitable for installations requiring dependable high-current protection, substantial short-circuit performance and adjustable electronic protection for critical distribution circuits.
| Series | SACE Emax 2 E1.2 |
|---|---|
| Order code / MPN | 1SDA071503R1 |
| Product type | Air circuit breaker (ACB) |
| Rated current | 1600 A |
| Number of poles | 4 |
| Performance level | C |
| Trip unit | Ekip Dip LSIG |
| Protection functions | L (overload), S (selective short circuit), I (instantaneous short circuit), G (earth fault) |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Earth-fault protection adjustment | 0.1–1 × In |
| Mounting | Fixed |
| Terminals | Front |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Ultimate breaking capacity (Icu) at 380 V AC | 50 kA |
| Ultimate breaking capacity (Icu) at 400 / 415 V AC | 50 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 50 kA |
| Ultimate breaking capacity (Icu) at 500 / 525 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Frequency | 50 / 60 Hz |
| Dimensions (H × W × D) | approx. 296 × 280 × 183 mm |
| Weight | approx. 16 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071503R1 is a SACE Emax 2 E1.2C four-pole fixed air circuit breaker rated at 1600 A and equipped with an Ekip Dip LSIG electronic trip unit.
The Ekip Dip LSIG provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The breaker provides an ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC.
Yes. The G protection function of the Ekip Dip LSIG trip unit provides adjustable earth-fault protection in addition to overload and short-circuit protection.