ABB 1SDA071502R1 SACE Emax 2 E1.2C 1600 A four-pole fixed air circuit breaker with Ekip Dip LSI electronic overload and short-circuit protection for low-voltage power distribution systems.
£5,582.52
The ABB E1.2C 1600 Ekip Dip LSI 4p F F, order code 1SDA071502R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 E1.2 series, it combines a compact breaker platform with the Ekip Dip LSI solid-state trip unit for dependable overload and short-circuit protection.
Rated at 1600 A, this E1.2C breaker uses a fixed installation configuration with front terminals. Its Ekip Dip LSI electronic release provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection, making it suitable for distribution systems where adjustable and coordinated circuit protection is required.
With a rated operational voltage of 690 V AC and a short-circuit breaking capacity of 50 kA, the E1.2C 1600 provides robust protection for demanding industrial and commercial installations. Its compact fixed four-pole format makes it particularly suitable for integration into main switchboards, distribution panels and power control centres.
The Ekip Dip LSI electronic trip unit provides three essential protection functions for electrical distribution networks. Long-time protection responds to sustained overload conditions, short-time protection supports selective coordination during short circuits, and instantaneous protection rapidly disconnects severe short-circuit faults.
The ABB SACE Emax 2 platform combines high electrical performance with compact dimensions and flexible switchboard integration. The fixed E1.2C configuration is particularly suitable for installations requiring dependable high-current protection, straightforward electronic adjustment and robust switching performance.
| Series | SACE Emax 2 E1.2 |
|---|---|
| Order code / MPN | 1SDA071502R1 |
| EAN | 8015644753528 |
| Product type | Air circuit breaker (ACB) |
| Rated current | 1600 A |
| Number of poles | 4 |
| Performance level | C |
| Trip unit | Ekip Dip LSI |
| Trip unit type | Electronic / solid-state |
| Protection functions | L (overload), S (selective short circuit), I (instantaneous short circuit) |
| Overload adjustment range | 640–1600 A |
| Short-time short-circuit adjustment range | 960–16000 A |
| Instantaneous short-circuit adjustment range | 2400–24000 A |
| Mounting | Fixed |
| Terminals | Front |
| Rated operational voltage | 690 V AC |
| Breaking capacity | 50 kA |
| Integrated earth-fault protection | No |
| Auxiliary change-over contacts | 4 |
| Power loss | 201 W |
| Protection rating | IP30 |
| Dimensions (H × W × D) | 296 × 280 × 183 mm |
| Net weight | 16 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071502R1 is a SACE Emax 2 E1.2C four-pole fixed air circuit breaker rated at 1600 A and fitted with an Ekip Dip LSI electronic trip unit.
The Ekip Dip LSI provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection.
The E1.2C 1600 has a short-circuit breaking capacity of 50 kA, providing robust fault protection for demanding low-voltage distribution systems.
This model is a fixed-mounted Emax 2 air circuit breaker supplied with front terminals for integration into low-voltage switchboards.
The breaker is rated for operation at up to 690 V AC, making it suitable for a wide range of industrial and commercial low-voltage distribution systems.
ABB SACE Emax 2 air circuit breakers combine high breaking performance, configurable electronic protection and compact construction to provide dependable switching and protection for modern low-voltage power distribution systems.