Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071471R1 SACE Emax 2 E1.2N 1250 four-pole fixed air circuit breaker with front terminals, Ekip Dip LI electronic protection, 1250 A rated current and 66 kA ultimate breaking capacity at 400–440 V AC.
£5,567.48
The ABB E1.2N 1250 Ekip Dip LI 4p F F, order code 1SDA071471R1, is a SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power distribution systems. This fixed four-pole E1.2N breaker combines a 1250 A rated uninterrupted current with ABB's Ekip Dip LI electronic trip unit.
The Ekip Dip LI release provides long-time overload (L) and instantaneous short-circuit (I) protection. Its straightforward electronic protection architecture is well suited to applications requiring dependable overload and high-current fault protection without the additional short-time or ground-fault functions provided by LSI and LSIG releases.
The E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. With a 50 kA short-time withstand current for 1 s, fixed four-pole construction and front terminals, this breaker is suited to industrial switchboards, transformer protection and high-current incoming or distribution feeders.
The ABB SACE Emax 2 E1.2N combines switching, isolation and electronic protection in a compact air circuit breaker platform. Its 1250 A rated current, four-pole construction, 66 kA ultimate breaking capacity at 400–440 V AC and 50 kA short-time withstand capability for 1 s make it suitable for important incoming and distribution positions in demanding low-voltage switchboards.
The Ekip Dip LI release provides long-time overload protection together with instantaneous short-circuit protection, helping protect conductors, busbars, transformers and connected electrical equipment against sustained overcurrent and severe short-circuit conditions. The E1.2N platform also supports optional motor operation where electrically controlled breaker operation is required.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2N |
| ABB order code | 1SDA071471R1 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated current (In) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Neutral-pole current | 100% of Iu |
| Short-circuit performance level | N |
| Trip unit | Ekip Dip LI |
| Release type | Electronic |
| Protection functions | L and I |
| Instantaneous short-circuit setting | 1875 A minimum |
| Integrated earth-fault protection | No |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 50 kA |
| Ultimate short-circuit breaking capacity (Icu) at 525 V AC | 50 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 50 kA |
| Rated service short-circuit breaking capacity (Ics) at 400–690 V AC | 50 kA |
| Rated service breaking capacity | 100% of Icu |
| Short-time withstand current (Icw), 1 s | 50 kA |
| Short-time withstand current (Icw), 3 s | 30 kA |
| Execution | Fixed |
| Terminal arrangement | Front terminals |
| Main-circuit connection | Bolt connection |
| Recommended main-circuit screw | M10 |
| Main-circuit tightening torque | 45 N·m |
| Auxiliary contacts | 4 change-over contacts |
| Switched-off indication | Yes |
| Motor drive integrated | No |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Suitable for IT networks | Yes, up to 690 V AC |
| Electrical durability at Ue ≤ 440 V | 8000 cycles |
| Electrical durability at Ue 500–690 V | 6500 cycles |
| Mechanical durability | 20000 cycles |
| Power loss | 122 W |
| Product dimensions (W × H × D) | 280 × 296 × 183 mm |
| Product net weight | 16 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644753214 |
| Country of origin | Italy |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071471R1 is a SACE Emax 2 E1.2N 1250 Ekip Dip LI four-pole fixed air circuit breaker with front terminals, a 1250 A rated current and electronic LI protection.
The breaker has a rated uninterrupted current of 1250 A and a rated operational voltage of up to 690 V AC.
The Ekip Dip LI electronic release provides long-time overload (L) and instantaneous short-circuit (I) protection. This LI version does not incorporate integrated ground-fault protection.
The E1.2N 1250 has an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. Its short-time withstand current is 50 kA for 1 s.
It is typically used in industrial and commercial low-voltage switchboards, transformer protection, incoming feeders and four-pole distribution circuits requiring dependable overload and instantaneous short-circuit protection.
ABB SACE Emax 2 air circuit breakers combine compact construction, electronic circuit protection and robust short-circuit performance, providing dependable switching and protection for industrial, commercial and infrastructure low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.