1SDA071465R1 ABB Emax 2 E1.2C 1250A Ekip Touch LSI 4P Air Circuit Breaker

1SDA071465R1 ABB Emax 2 E1.2C 1250A Ekip Touch LSI 4P Air Circuit Breaker

ABB 1SDA071465R1 is a SACE Emax 2 E1.2C 1250 A fixed four-pole air circuit breaker with front terminals, an Ekip Touch LSI electronic trip unit, 690 V AC rated operational voltage, 50 kA breaking capacity at 440 V AC and 42 kA short-time withstand current for 1 s.

SKU: 1SDA071465R1MPN: 1SDA071465R1
Price
List Price £7,242.70 ex VAT
Your Price (ex VAT) Save 25%
£5,432.03 25% OFF
You save £1,810.68 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,432.03
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,432.03

Why Choose the ABB 1SDA071465R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA071465R1 is a high-performance SACE Emax 2 E1.2C air circuit breaker (ACB) designed for advanced protection and control of low-voltage electrical distribution systems. Rated at 1250 A, this fixed four-pole circuit breaker combines ABB’s compact E1.2 frame with the advanced Ekip Touch LSI electronic trip unit for configurable overload, short-time and instantaneous short-circuit protection.

As part of the ABB SACE Emax 2 series, the E1.2C is engineered to provide dependable fault interruption and selective protection in demanding industrial and commercial installations. The Ekip Touch LSI solid-state release provides long-time, short-time and instantaneous protection functions, while its touchscreen interface supports intuitive configuration, commissioning and access to electrical information.

With a rated uninterrupted current of 1250 A, rated operational voltage of 690 V AC, rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and rated short-time withstand current of 42 kA for 1 s, the 1SDA071465R1 provides robust protection for demanding low-voltage networks. This version features a fixed four-pole configuration with front terminals for straightforward integration into switchboards and distribution assemblies.

Key Advantages

  • High-performance 1250 A air circuit breaker for low-voltage power distribution.
  • 50 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 42 kA rated short-time withstand current for 1 s supports effective protection coordination and selectivity.
  • Advanced Ekip Touch LSI electronic trip unit provides long-time, short-time and instantaneous protection.
  • Touchscreen interface simplifies protection configuration, commissioning and monitoring.
  • Four-pole fixed configuration with front terminals supports efficient switchboard integration.

Key Features

  • ABB SACE Emax 2 E1.2C air circuit breaker.
  • 1250 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 50 kA Icu at 440 V AC.
  • 42 kA Icw for 1 s.
  • Ekip Touch LSI solid-state electronic release.
  • Long-time overload, short-time delayed and instantaneous short-circuit protection.
  • Touchscreen interface for intuitive trip-unit configuration and operation.
  • Fixed four-pole construction with neutral pole rated at 100% of Iu.
  • Front terminals for main circuit connections.
  • Supplied with four auxiliary change-over contacts.
  • Open/closed circuit-breaker position indication.
  • Optional motor operating mechanism for remote operation.
  • IP30 degree of protection.

Advanced Selective Protection for Low-Voltage Distribution

Air circuit breakers such as the ABB SACE Emax 2 E1.2C protect important low-voltage distribution circuits against damaging overload and short-circuit conditions. The 1SDA071465R1 combines a 1250 A continuous-current rating with 50 kA short-circuit breaking capability at 440 V AC and 42 kA short-time withstand capability for 1 s, making it suitable for demanding main and distribution circuits.

The Ekip Touch LSI trip unit adds short-time delayed protection to the long-time and instantaneous functions, enabling more sophisticated protection coordination than an LI-only release. This makes the breaker particularly useful where selectivity between upstream and downstream protective devices is important, while the touchscreen interface provides convenient access to protection configuration and operating information.

Typical Applications

  • Main incoming protection for low-voltage switchboards.
  • Industrial electrical distribution systems.
  • Commercial building power distribution.
  • Transformer secondary protection.
  • Manufacturing and process facilities.
  • Distribution feeders requiring selective short-circuit protection.
  • Data centres and critical-power installations.
  • Low-voltage switchgear and controlgear assemblies.

Technical Specifications

Series SACE Emax 2
Frame / sub-type E1.2C
Order code / MPN 1SDA071465R1
EAN / GTIN 8015644753153
Product type Air circuit breaker
Short-circuit performance level C
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 50 kA
Rated short-time withstand current (Icw) for 1 s 42 kA
Number of poles 4
Neutral pole current 100% of Iu
Trip unit Ekip Touch LSI
Release type Solid-state electronic
Protection functions LSI
Long-time overload protection Yes
Short-time delayed short-circuit protection Yes
Instantaneous short-circuit protection Yes
Integrated earth-fault protection No
Current type AC
Installation version Fixed
Terminal configuration Front terminals
Main circuit connection type Bolt connection
Connecting capacity 1000 mm²
Auxiliary contacts 4 change-over contacts
Circuit-breaker position indication Open / closed
Integrated undervoltage release No
Integrated motor drive No
Optional motor drive Yes
Degree of protection IP30
Power loss 122 W
Electrical durability at ≤440 V AC 8000 operating cycles
Electrical durability at 500–690 V AC 6500 operating cycles
Mechanical durability 20,000 operating cycles
Product net width 280 mm
Product net height 296 mm
Product net depth 183 mm
Product net weight 16 kg

Frequently Asked Questions

What is the ABB 1SDA071465R1 used for?

The ABB 1SDA071465R1 is a 1250 A Emax 2 air circuit breaker designed to protect and control low-voltage electrical distribution circuits in industrial, commercial and infrastructure switchboards.

What is the current rating of the ABB 1SDA071465R1?

The circuit breaker has a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC.

What breaking capacity does the E1.2C 1250 provide?

The E1.2C 1250 has a rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.

What protection does the Ekip Touch LSI trip unit provide?

The Ekip Touch LSI solid-state electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated ground-fault protection.

Is the ABB 1SDA071465R1 a fixed or withdrawable circuit breaker?

The 1SDA071465R1 is a fixed four-pole air circuit breaker with front terminals for integration into low-voltage switchboards and distribution assemblies.