ABB 1SDA071464R1 is a SACE Emax 2 E1.2C 1250 A fixed four-pole air circuit breaker with front terminals, an Ekip Touch LI electronic trip unit, 690 V AC rated operational voltage and 50 kA breaking capacity at 400–440 V AC.
£5,116.04
The ABB 1SDA071464R1 is a high-performance SACE Emax 2 E1.2C air circuit breaker (ACB) designed for reliable protection and control of low-voltage electrical distribution systems. Rated at 1250 A, this fixed four-pole circuit breaker combines ABB’s compact E1.2 frame with the advanced Ekip Touch LI electronic trip unit for configurable overload and instantaneous short-circuit protection.
As part of the ABB SACE Emax 2 series, the E1.2C is engineered to deliver high short-circuit performance while maintaining compact switchboard dimensions. The Ekip Touch LI solid-state release provides long-time overload and instantaneous short-circuit protection, with a touchscreen interface that simplifies configuration, commissioning and access to electrical information.
With a rated uninterrupted current of 1250 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC, the 1SDA071464R1 provides robust protection for demanding low-voltage installations. This version features a fixed four-pole configuration with front terminals, making it suitable for main incomers, transformer secondary protection and distribution circuits within industrial and commercial switchboards.
Air circuit breakers such as the ABB SACE Emax 2 E1.2C protect important low-voltage distribution circuits against damaging overload and short-circuit conditions. The 1SDA071464R1 combines a 1250 A continuous-current rating with 50 kA short-circuit breaking capability at 400–440 V AC and a 42 kA short-time withstand rating for 1 s, making it suitable for demanding main and distribution circuits.
The Ekip Touch LI trip unit provides electronic long-time overload and instantaneous short-circuit protection through an intuitive touchscreen interface. This LI configuration is particularly suited to installations that require advanced configurable electronic protection without integrated short-time delayed or ground-fault functions.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E1.2C |
| Order code / MPN | 1SDA071464R1 |
| EAN / GTIN | 8015644753146 |
| Product type | Air circuit breaker |
| Short-circuit performance level | C |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated service short-circuit breaking capacity (Ics) at 380–440 V AC | 50 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 42 kA |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw) for 1 s | 42 kA |
| Rated short-time withstand current (Icw) for 3 s | 24 kA |
| Number of poles | 4 |
| Trip unit | Ekip Touch LI |
| Release type | Solid-state electronic |
| Protection functions | LI |
| Long-time overload protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Short-time delayed protection | No |
| Integrated ground-fault protection | No |
| Current type | AC |
| Installation version | Fixed |
| Terminal connection | Front |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Product net width | 280 mm |
| Product net height | 296 mm |
| Product net depth | 183 mm |
| Product net weight | 16 kg |
The ABB 1SDA071464R1 is a 1250 A Emax 2 air circuit breaker designed to protect and control low-voltage electrical distribution circuits in industrial, commercial and infrastructure switchboards.
The circuit breaker has a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC.
The E1.2C 1250 has a rated ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC.
The Ekip Touch LI solid-state electronic trip unit provides long-time overload and instantaneous short-circuit protection. This LI configuration does not include integrated short-time delayed or ground-fault protection.
The 1SDA071464R1 is a fixed four-pole air circuit breaker with front terminals for integration into low-voltage switchboards and distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance and compact construction for dependable protection of modern industrial, commercial and infrastructure low-voltage distribution systems.