Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071411R1 SACE Emax 2 E1.2B 1000 four-pole fixed air circuit breaker with front terminals, Ekip Dip LI electronic protection, 1000 A rated current and 42 kA ultimate short-circuit breaking capacity.
£4,604.44
The ABB E1.2B 1000 Ekip Dip LI 4p F F, order code 1SDA071411R1, is a compact SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in low-voltage power distribution systems. This fixed four-pole E1.2B breaker combines a 1000 A rated uninterrupted current with ABB's Ekip Dip LI solid-state electronic trip unit.
The Ekip Dip LI release provides long-time overload and instantaneous short-circuit protection, with settings configured through DIP switches. The long-time threshold is adjustable from 0.4–1 × In, while instantaneous protection is adjustable from 1.5–15 × In, allowing the breaker to be matched to the requirements of the protected circuit.
The E1.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA across rated AC voltages from 400 to 690 V. With a 42 kA short-time withstand current for 1 s, fixed four-pole construction and front terminals, this breaker provides a practical solution for industrial switchboards, commercial distribution systems and high-current incoming or distribution feeders.
The ABB SACE Emax 2 E1.2B combines switching, isolation and electronic protection in a compact air circuit breaker platform. Its 1000 A rated current, four-pole construction and 42 kA ultimate breaking capacity make it suitable for incoming feeders, distribution circuits and other switchboard positions requiring dependable protection at substantial operating currents.
The Ekip Dip LI release provides adjustable long-time overload protection together with instantaneous short-circuit protection. This combination enables the breaker to respond to sustained overcurrent conditions and rapidly interrupt severe short circuits, helping protect conductors, busbars and connected electrical equipment against damaging fault currents.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2B |
| ABB order code | 1SDA071411R1 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated current (In) | 1000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Number of poles | 4 |
| Neutral-pole current | 100% of Iu |
| Short-circuit performance level | B |
| Trip unit | Ekip Dip LI |
| Release type | Solid-state electronic release |
| Protection functions | L and I |
| Long-time overload adjustment | 0.4–1 × In / 400–1000 A |
| Instantaneous short-circuit adjustment | 1.5–15 × In / 1500–15000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Short-time withstand current (Icw), 1 s | 42 kA |
| Integrated ground-fault protection | No |
| Execution | Fixed |
| Terminal arrangement | Front terminals |
| Auxiliary contacts | 4 |
| Circuit-breaker open/closed indication | Yes |
| Product net width | 280 mm |
| Product net height | 296 mm |
| Product net depth | 183 mm |
| Net weight | 16 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644752613 |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071411R1 is a SACE Emax 2 E1.2B 1000 Ekip Dip LI four-pole fixed air circuit breaker with front terminals, a 1000 A rated current and electronic LI protection.
The breaker has a rated uninterrupted current of 1000 A, with adjustable long-time overload protection from 400–1000 A.
The Ekip Dip LI electronic release provides long-time overload (L) and instantaneous short-circuit (I) protection. The long-time threshold is adjustable from 0.4–1 × In and the instantaneous threshold from 1.5–15 × In.
The E1.2B 1000 has an ultimate short-circuit breaking capacity of 42 kA across 400–690 V AC and a short-time withstand current of 42 kA for 1 s.
It is typically used in low-voltage distribution boards, industrial switchboards, incoming feeders and four-pole distribution circuits requiring reliable overload and instantaneous short-circuit protection.
ABB SACE Emax 2 air circuit breakers combine compact construction, adjustable electronic protection and dependable switching performance, providing a flexible solution for industrial, commercial and infrastructure low-voltage distribution systems.
We use cookies