1SDA071411R1 ABB E1.2B 1000 Ekip Dip LI 4p F F Air Circuit Breaker

1SDA071411R1 ABB E1.2B 1000 Ekip Dip LI 4p F F Air Circuit Breaker

ABB 1SDA071411R1 SACE Emax 2 E1.2B 1000 four-pole fixed air circuit breaker with front terminals, Ekip Dip LI electronic protection, 1000 A rated current and 42 kA ultimate short-circuit breaking capacity.

SKU: 1SDA071411R1MPN: 1SDA071411R1
Price
List Price £6,139.25 ex VAT
Your Price (ex VAT) Save 25%
£4,604.44 25% OFF
You save £1,534.81 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,604.44
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,604.44

Why Choose the ABB E1.2B 1000 Ekip Dip LI 4p F F Air Circuit Breaker?

The ABB E1.2B 1000 Ekip Dip LI 4p F F, order code 1SDA071411R1, is a compact SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in low-voltage power distribution systems. This fixed four-pole E1.2B breaker combines a 1000 A rated uninterrupted current with ABB's Ekip Dip LI solid-state electronic trip unit.

The Ekip Dip LI release provides long-time overload and instantaneous short-circuit protection, with settings configured through DIP switches. The long-time threshold is adjustable from 0.4–1 × In, while instantaneous protection is adjustable from 1.5–15 × In, allowing the breaker to be matched to the requirements of the protected circuit.

The E1.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA across rated AC voltages from 400 to 690 V. With a 42 kA short-time withstand current for 1 s, fixed four-pole construction and front terminals, this breaker provides a practical solution for industrial switchboards, commercial distribution systems and high-current incoming or distribution feeders.

Key Advantages

  • Compact 1000 A SACE Emax 2 air circuit breaker for low-voltage power distribution.
  • Ekip Dip LI solid-state electronic release provides adjustable overload and instantaneous short-circuit protection.
  • 42 kA ultimate short-circuit breaking capacity across 400–690 V AC.
  • 42 kA short-time withstand current for 1 s.
  • Four-pole configuration with a 100% rated neutral pole.
  • Fixed construction with front terminals for straightforward switchboard installation.
  • Four auxiliary contacts and open/closed circuit-breaker position indication support control and status monitoring.

Key Features

  • ABB SACE Emax 2 E1.2B series.
  • 1000 A rated uninterrupted current (Iu).
  • 4-pole configuration.
  • 100% neutral-pole current rating.
  • Fixed circuit breaker construction.
  • Front terminals.
  • Ekip Dip LI solid-state electronic trip unit.
  • Long-time (L) overload protection.
  • Instantaneous (I) short-circuit protection.
  • 400–1000 A long-time overload adjustment range.
  • 1500–15000 A instantaneous short-circuit adjustment range.
  • Protection settings configured using DIP switches.
  • 42 kA Icu at 400–690 V AC.
  • Four auxiliary contacts fitted as standard.
  • Circuit-breaker open/closed position indication.

Reliable Overload and Short-Circuit Protection

The ABB SACE Emax 2 E1.2B combines switching, isolation and electronic protection in a compact air circuit breaker platform. Its 1000 A rated current, four-pole construction and 42 kA ultimate breaking capacity make it suitable for incoming feeders, distribution circuits and other switchboard positions requiring dependable protection at substantial operating currents.

The Ekip Dip LI release provides adjustable long-time overload protection together with instantaneous short-circuit protection. This combination enables the breaker to respond to sustained overcurrent conditions and rapidly interrupt severe short circuits, helping protect conductors, busbars and connected electrical equipment against damaging fault currents.

Typical Applications

  • Low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Main and sub-main incoming feeders.
  • Four-pole distribution circuits requiring neutral switching.
  • Transformer secondary and installation protection.
  • Commercial building electrical systems.
  • Manufacturing and process facilities.
  • Switchboards requiring a compact fixed 1000 A air circuit breaker with LI protection.

Technical Specifications

Series SACE Emax 2
Frame E1.2B
ABB order code 1SDA071411R1
Product type Air circuit breaker
Rated uninterrupted current (Iu) 1000 A
Rated current (In) 1000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50/60 Hz
Number of poles 4
Neutral-pole current 100% of Iu
Short-circuit performance level B
Trip unit Ekip Dip LI
Release type Solid-state electronic release
Protection functions L and I
Long-time overload adjustment 0.4–1 × In / 400–1000 A
Instantaneous short-circuit adjustment 1.5–15 × In / 1500–15000 A
Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 42 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 42 kA
Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 42 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 42 kA
Short-time withstand current (Icw), 1 s 42 kA
Integrated ground-fault protection No
Execution Fixed
Terminal arrangement Front terminals
Auxiliary contacts 4
Circuit-breaker open/closed indication Yes
Product net width 280 mm
Product net height 296 mm
Product net depth 183 mm
Net weight 16 kg
Standard IEC 60947-2
EAN 8015644752613
ABB product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA071411R1?

The ABB 1SDA071411R1 is a SACE Emax 2 E1.2B 1000 Ekip Dip LI four-pole fixed air circuit breaker with front terminals, a 1000 A rated current and electronic LI protection.

What is the rated current of the ABB E1.2B 1000?

The breaker has a rated uninterrupted current of 1000 A, with adjustable long-time overload protection from 400–1000 A.

What protection does the Ekip Dip LI trip unit provide?

The Ekip Dip LI electronic release provides long-time overload (L) and instantaneous short-circuit (I) protection. The long-time threshold is adjustable from 0.4–1 × In and the instantaneous threshold from 1.5–15 × In.

What is the breaking capacity of ABB 1SDA071411R1?

The E1.2B 1000 has an ultimate short-circuit breaking capacity of 42 kA across 400–690 V AC and a short-time withstand current of 42 kA for 1 s.

Where is the ABB E1.2B 1000 Ekip Dip LI typically used?

It is typically used in low-voltage distribution boards, industrial switchboards, incoming feeders and four-pole distribution circuits requiring reliable overload and instantaneous short-circuit protection.

Dependable Protection for Low-Voltage Distribution

ABB SACE Emax 2 air circuit breakers combine compact construction, adjustable electronic protection and dependable switching performance, providing a flexible solution for industrial, commercial and infrastructure low-voltage distribution systems.