ABB 1SDA071383R1 Emax 2 E1.2C 800 Ekip Dip LSIG four-pole fixed air circuit breaker with front terminals, an 800 A rated current, earth-fault protection and 50 kA ultimate short-circuit breaking capacity at 440 V AC.

SKU: 1SDA071383R1MPN: 1SDA071383R1
Price
List Price £7,122.32 ex VAT
Your Price (ex VAT) Save 25%
£5,341.74 25% OFF
You save £1,780.58 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,341.74
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,341.74

Why Choose the ABB E1.2C 800 Ekip Dip LSIG 4p F F Air Circuit Breaker?

The ABB E1.2C 800 Ekip Dip LSIG 4p F F, order code 1SDA071383R1, is a compact four-pole air circuit breaker (ACB) designed for comprehensive protection in low-voltage power distribution systems. As part of the ABB SACE Emax 2 series, this fixed circuit breaker combines an 800 A rated current, robust short-circuit performance and an Ekip Dip LSIG electronic protection release.

The integrated Ekip Dip LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. This combination supports selective coordination while adding dedicated earth-fault protection, making the breaker suitable for distribution systems requiring comprehensive electronic fault protection.

The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s. This version features a four-pole fixed configuration with front terminals and supports operation at up to 690 V AC, making it suitable for compact three-phase four-wire switchboards and industrial power distribution assemblies.

Key Advantages

  • Compact ABB SACE Emax 2 air circuit breaker for low-voltage power distribution.
  • 800 A rated current for industrial, commercial and infrastructure installations.
  • 50 kA Icu at 440 V AC for dependable short-circuit interruption.
  • 42 kA Icw for 1 s supports robust short-time current withstand capability.
  • Ekip Dip LSIG electronic protection release provides comprehensive fault protection.
  • Integrated earth-fault protection provides an additional level of distribution system protection.
  • Four-pole fixed construction supports three-phase four-wire distribution systems.
  • Front terminals provide straightforward integration into low-voltage switchboards.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 800 A rated current.
  • Operating voltage up to 690 V AC.
  • 50 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 42 kA rated short-time withstand current for 1 s.
  • Ekip Dip LSIG electronic protection release.
  • Long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
  • DIP-switch based protection configuration.
  • Four-pole construction for three-phase systems with a neutral conductor.
  • Fixed breaker construction.
  • Front main circuit terminals.
  • Compact E1.2 frame designed for efficient use of switchboard space.

Comprehensive Protection for Low-Voltage Distribution Systems

Air circuit breakers such as the ABB Emax 2 E1.2C provide switching and protection for low-voltage electrical distribution systems. By detecting overload, short-circuit and earth-fault conditions and interrupting fault current, the breaker helps protect switchboards, cables, busbars and connected electrical equipment while supporting dependable operation of the wider electrical installation.

The Ekip Dip LSIG release combines long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Short-time protection supports selective coordination between protective devices, while the integrated earth-fault function provides additional protection against faults involving earth, making this configuration well suited to installations requiring comprehensive distribution protection.

Typical Applications

  • Low-voltage main and sub-distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Three-phase four-wire distribution networks.
  • Transformer secondary-side protection.
  • Manufacturing and process industry installations.
  • Infrastructure and utility distribution systems.
  • Power distribution panels requiring selective protection and earth-fault detection.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA071383R1
Product type Air circuit breaker
Frame / sub-type E1.2
Performance level C
Rated current 800 A
Rated operational voltage Up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 50 kA
Rated short-time withstand current (Icw) for 1 s 42 kA
Number of poles 4P
Current type AC
Trip unit Ekip Dip LSIG electronic release
Protection functions Long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G)
Earth-fault protection Yes
Protection setting method DIP switches
Mounting type Fixed
Terminal type Front terminals
Main circuit connection Front connection
Configuration Fixed breaker with front connections
Approximate dimensions 280 mm width × 183 mm depth
Approximate net weight 16 kg

Frequently Asked Questions

What is the ABB 1SDA071383R1 used for?

The ABB 1SDA071383R1 is a four-pole air circuit breaker designed for switching and protecting low-voltage electrical distribution systems against overload, short-circuit and earth-fault conditions.

What is the rated current of the ABB E1.2C 800?

This Emax 2 air circuit breaker has a rated current of 800 A, making it suitable for industrial, commercial and infrastructure low-voltage distribution systems.

What is the short-circuit performance of the ABB 1SDA071383R1?

The E1.2C 800 has an ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.

What protection functions does the Ekip Dip LSIG release provide?

The Ekip Dip LSIG electronic release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection for comprehensive distribution system protection.

Is the ABB 1SDA071383R1 fixed or withdrawable?

The 1SDA071383R1 is a fixed four-pole air circuit breaker with front main circuit terminals for integration into low-voltage switchboards.

Trusted Low-Voltage Circuit Protection

ABB SACE Emax 2 air circuit breakers combine compact construction, dependable interruption performance and configurable electronic protection for industrial, commercial and infrastructure low-voltage power distribution systems.