Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071375R1 Emax 2 E1.2B 800 four-pole fixed air circuit breaker with an 800 A rating, 690 V AC operational voltage, Ekip Touch LSI electronic protection and 42 kA ultimate breaking capacity.
£4,754.90
The ABB E1.2B 800 Ekip Touch LSI 4p F F, order code 1SDA071375R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 series, it combines the compact E1.2 frame with an Ekip Touch electronic trip unit for accurate, configurable circuit protection in industrial, commercial and infrastructure installations.
This fixed circuit breaker features front terminals and an Ekip Touch LSI electronic protection release, providing long-time overload, selective short-time short-circuit and instantaneous short-circuit protection. The touch-sensitive display simplifies configuration of the protection functions, while the LSI functionality provides greater selectivity and coordination flexibility than an LI-only trip unit.
With a rated uninterrupted current of 800 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 42 kA across its specified AC operational voltage range, the E1.2B 800 provides dependable protection for demanding electrical distribution systems. Its four-pole configuration enables switching across three phases and neutral, while the fixed construction provides a robust solution for permanent switchboard installation.
Air circuit breakers such as the ABB SACE Emax 2 E1.2B protect electrical distribution systems against overload and short-circuit conditions while providing dependable switching of high-current circuits. The compact E1.2 frame combines high current capability with 42 kA short-circuit performance, making it suitable for main distribution, incomer and feeder duties within modern low-voltage switchboards.
The Ekip Touch LSI trip unit adds selective short-time protection to the long-time and instantaneous functions, allowing improved coordination between upstream and downstream protective devices. This helps isolate faults closer to their source while maintaining continuity elsewhere in the electrical distribution system, making the 1SDA071375R1 well suited to installations where protection selectivity is important.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071375R1 |
| Product type | Air circuit breaker |
| Frame | E1.2 |
| Performance level | B |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | Ekip Touch LSI |
| Release type | Electronic |
| Long-time protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Protection functions | Long-time overload, selective short-circuit and instantaneous short-circuit protection |
| Version | Fixed |
| Terminal connection | Front terminals |
| Standard | IEC 60947-2 |
The ABB 1SDA071375R1 is an Emax 2 air circuit breaker designed for switching and configurable overload and short-circuit protection in low-voltage electrical distribution systems.
The circuit breaker has a rated uninterrupted current of 800 A.
The E1.2B 800 has a rated ultimate short-circuit breaking capacity (Icu) of 42 kA across specified operational voltages from 380 V AC to 690 V AC.
The breaker is fitted with an ABB Ekip Touch LSI electronic trip unit, providing long-time overload, selective short-time short-circuit and instantaneous short-circuit protection.
The 1SDA071375R1 is a fixed four-pole circuit breaker with front terminals, designed for permanent installation within a low-voltage electrical switchboard.
ABB SACE Emax 2 air circuit breakers combine intelligent electronic protection, dependable switching and selective short-circuit protection for low-voltage electrical distribution systems across industrial, commercial and infrastructure applications.