ABB 1SDA071373R1 SACE Emax 2 E1.2B 800 four-pole fixed air circuit breaker with front terminals, Ekip Dip LSIG electronic protection, 800 A rated current and 42 kA ultimate short-circuit breaking capacity at 400 V AC.
£5,161.17
The ABB E1.2B 800 Ekip Dip LSIG 4p F F, order code 1SDA071373R1, is a compact SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in low-voltage electrical distribution systems. This fixed four-pole E1.2B breaker combines an 800 A rated uninterrupted current with ABB's Ekip Dip LSIG solid-state electronic trip unit.
The Ekip Dip LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. Adjustable protection settings enable coordination with the protected circuit and other protective devices, helping provide selective fault clearance while also protecting against earth-fault conditions.
The E1.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA at 400 V AC. The breaker is rated for operation at 690 V AC and uses a fixed four-pole construction with front terminals, making it suitable for incoming feeders, industrial distribution boards and applications requiring four-pole switching with comprehensive LSIG protection.
The ABB SACE Emax 2 E1.2B combines switching, isolation and electronic protection in a compact air circuit breaker platform. Its 800 A rated current, four-pole configuration and 42 kA breaking capacity at 400 V AC make it suitable for incoming feeders, distribution circuits and other switchboard positions where dependable protection and isolation are required.
The Ekip Dip LSIG release provides adjustable long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. These functions help protect conductors, busbars and connected equipment while supporting selective coordination so faults can be isolated without unnecessarily disconnecting unaffected sections of the electrical installation.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2B |
| ABB order code | 1SDA071373R1 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 800 A |
| Rated current (In) | 800 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Neutral-pole current | 100% of Iu |
| Short-circuit performance level | B |
| Trip unit | Ekip Dip LSIG |
| Release type | Solid-state electronic release |
| Protection functions | L, S, I and G |
| Overload release adjustment | 320–800 A |
| Short-time delayed short-circuit adjustment | 480–8000 A |
| Instantaneous short-circuit adjustment | 1200–12000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 42 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 42 kA |
| Integrated earth-fault protection | Yes |
| Execution | Fixed |
| Terminal arrangement | Front terminals |
| Main circuit connection | Bolted connection |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker open/closed indication | Yes |
| Trip indication | Yes |
| Motor drive integrated | No |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Power loss | 50 W |
| Electrical durability | 8000 operating cycles |
| Mechanical durability | 20000 operating cycles |
| Dimensions (W × H × D) | 280 × 296 × 183 mm |
| Net weight | 16 kg |
| EAN | 8015644752231 |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071373R1 is a SACE Emax 2 E1.2B 800 Ekip Dip LSIG four-pole fixed air circuit breaker with front terminals, an 800 A rated current and comprehensive electronic LSIG protection.
The breaker has a rated uninterrupted current of 800 A, with an adjustable long-time overload protection range of 320–800 A.
The Ekip Dip LSIG solid-state release provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection.
The E1.2B 800 has an ultimate short-circuit breaking capacity of 42 kA at 400 V AC, 50 Hz, with a service short-circuit breaking capacity of 42 kA at the same voltage.
It is typically used in low-voltage distribution boards, industrial switchboards, incoming feeders and four-pole distribution circuits requiring adjustable overload, short-circuit and integrated ground-fault protection.