1SDA071360R1 ABB E1.2N 630 Ekip G Hi-Touch LSIG 4p F F Air Circuit Breaker 630 A

1SDA071360R1 ABB E1.2N 630 Ekip G Hi-Touch LSIG 4p F F Air Circuit Breaker 630 A

ABB 1SDA071360R1 Emax 2 E1.2N 630 Ekip G Hi-Touch LSIG four-pole fixed air circuit breaker with front connections, a 630 A rated current, generator and earth-fault protection and 66 kA ultimate short-circuit breaking capacity at 400/415 V AC.

SKU: 1SDA071360R1MPN: 1SDA071360R1
Price
List Price £11,676.59 ex VAT
Your Price (ex VAT) Save 25%
£8,757.44 25% OFF
You save £2,919.15 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,757.44
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,757.44

Why Choose the ABB E1.2N 630 Ekip G Hi-Touch LSIG 4p F F Air Circuit Breaker?

The ABB E1.2N 630 Ekip G Hi-Touch LSIG 4p F F, order code 1SDA071360R1, is an advanced four-pole air circuit breaker (ACB) designed for generator protection and sophisticated low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, this fixed circuit breaker combines a 630 A rated current, high short-circuit performance and the feature-rich Ekip G Hi-Touch LSIG electronic protection release.

The integrated Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection together with advanced generator-specific protection, measurement and monitoring capabilities. This makes the breaker particularly suitable for generator installations and critical distribution systems where sophisticated protection and electrical supervision are required.

With a rated operational voltage of up to 690 V AC and an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, the E1.2N 630 provides robust protection in the compact Emax 2 E1.2 frame. This version features a four-pole fixed configuration with front terminals for integration into three-phase four-wire switchboards and generator distribution assemblies.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for generator and power distribution protection.
  • 630 A rated current for industrial, commercial and infrastructure installations.
  • 66 kA Icu at 400/415 V AC for dependable short-circuit interruption.
  • Premium Ekip G Hi-Touch LSIG electronic protection release.
  • Long-time, short-time, instantaneous and earth-fault protection functions.
  • Advanced generator-specific protection, measurement and monitoring capabilities.
  • Four-pole fixed construction supports three-phase four-wire distribution systems.
  • Front terminals provide convenient access for switchboard and generator-panel integration.

Key Features

  • ABB SACE Emax 2 E1.2N series.
  • 630 A rated current.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 66 kA Icu at 400/415 V AC.
  • 50 kA Icu at 690 V AC.
  • Ekip G Hi-Touch LSIG advanced electronic protection release.
  • Long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
  • Generator-oriented protection functions with advanced measurement and monitoring.
  • Four-pole construction for three-phase systems with neutral conductors.
  • Fixed breaker configuration with front main circuit terminals.
  • Compact E1.2 frame designed for efficient use of switchboard space.

Advanced Generator and Power Distribution Protection

Air circuit breakers such as the ABB Emax 2 E1.2N provide switching and protection for low-voltage electrical distribution and generator systems. By detecting overload, short-circuit and earth-fault conditions and interrupting fault current, the breaker helps protect generators, switchboards, cables, busbars and connected electrical equipment while supporting reliable operation of the wider electrical installation.

The Ekip G Hi-Touch LSIG release combines comprehensive overcurrent and earth-fault protection with advanced functions intended for generator applications. Its long-time, short-time, instantaneous and earth-fault protection functions support selective coordination, while its advanced measurement and monitoring capabilities make the 1SDA071360R1 well suited to critical installations where generator protection and detailed electrical supervision are required.

Typical Applications

  • Generator protection and generator switchboards.
  • Low-voltage main and sub-distribution switchboards.
  • Industrial power generation and distribution systems.
  • Three-phase four-wire distribution networks.
  • Standby and emergency power systems.
  • Manufacturing and process industry installations.
  • Infrastructure and critical power distribution systems.
  • Distribution panels requiring advanced monitoring, selectivity and earth-fault protection.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA071360R1
Product type Air circuit breaker
Frame / sub-type E1.2
Performance level N
Rated current 630 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Number of poles 4P
Current type AC
Trip unit Ekip G Hi-Touch LSIG electronic release
Protection functions Long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G)
Earth-fault protection Yes
Generator protection Yes
Measurement functionality Advanced integrated measurement and monitoring
Mounting type Fixed
Terminal type Front terminals
Main circuit connection Front connection
Configuration Fixed breaker with front connections
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071360R1 used for?

The ABB 1SDA071360R1 is a four-pole air circuit breaker designed for generator protection and advanced low-voltage power distribution, providing protection against overload, short-circuit and earth-fault conditions.

What is the rated current of the ABB E1.2N 630?

This Emax 2 air circuit breaker has a rated current of 630 A, making it suitable for generator, industrial, commercial and infrastructure low-voltage distribution systems.

What is the breaking capacity of the ABB 1SDA071360R1?

The E1.2N 630 has an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC and 50 kA at 690 V AC.

What protection functions does the Ekip G Hi-Touch LSIG release provide?

The Ekip G Hi-Touch LSIG electronic release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection together with advanced generator protection, measurement and monitoring capabilities.

Is the ABB 1SDA071360R1 fixed or withdrawable?

The 1SDA071360R1 is a fixed four-pole air circuit breaker with front main circuit terminals for integration into low-voltage switchboards and generator distribution assemblies.

Trusted Advanced Generator Protection

ABB SACE Emax 2 air circuit breakers combine dependable interruption performance, advanced electronic protection and sophisticated measurement and monitoring capabilities for generator, industrial, infrastructure and critical low-voltage power distribution systems.