ABB 1SDA071357R1 is a SACE Emax 2 E1.2N 630 A fixed four-pole air circuit breaker with an Ekip G Touch LSIG electronic trip unit, 690 V AC rated operational voltage and 66 kA breaking capacity at 400 V AC.
£8,140.51
The ABB 1SDA071357R1 is a high-performance SACE Emax 2 E1.2N air circuit breaker (ACB) designed for advanced protection and control of low-voltage electrical distribution and generator systems. Rated at 630 A, this fixed four-pole circuit breaker combines ABB’s compact E1.2 frame with the specialised Ekip G Touch LSIG electronic trip unit for comprehensive generator and distribution protection.
As part of the ABB SACE Emax 2 series, the E1.2N provides dependable circuit protection in industrial, commercial and infrastructure installations. The Ekip G Touch LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions, with protection characteristics developed to support generator applications as well as conventional low-voltage distribution systems.
With a rated uninterrupted current of 630 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, the 1SDA071357R1 provides substantial fault-clearing performance in a compact format. This version uses a fixed four-pole configuration and is designed for permanent installation within low-voltage switchboards and power distribution assemblies.
Air circuit breakers such as the ABB SACE Emax 2 E1.2N protect important low-voltage circuits against damaging overload, short-circuit and earth-fault conditions. The 1SDA071357R1 combines a compact E1.2 frame with a 630 A continuous-current rating and high short-circuit performance, making it suitable for generator systems, main incomers and distribution circuits within industrial and commercial switchboards.
The Ekip G Touch LSIG trip unit extends the Emax 2 platform with protection functionality suited to generator applications. Its electronic architecture and touchscreen interface support precise protection configuration and monitoring, helping engineers coordinate generator and distribution protection across modern low-voltage electrical networks.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E1.2N |
| Order code / MPN | 1SDA071357R1 |
| Product type | Air circuit breaker |
| Short-circuit performance level | N |
| Rated current (In) | 630 A |
| Rated uninterrupted current (Iu) | 630 A |
| Rated operational voltage | 690 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 66 kA |
| Number of poles | 4 |
| Neutral pole current | 100% of Iu |
| Trip unit | Ekip G Touch LSIG |
| Release type | Electronic |
| Protection functions | LSIG |
| Overload release current setting | 252 A |
| Short-time delayed short-circuit release setting | 378 A |
| Instantaneous short-circuit release setting | 945 A |
| Integrated earth-fault protection | Yes |
| Current type | AC |
| Installation version | Fixed |
| Main circuit connection | Bolt connection |
| Main circuit connection position | Rear |
| Auxiliary contacts | 4 change-over contacts |
| Switched-off indicator | Yes |
| Integrated undervoltage release | No |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Protection rating | IP30 |
| Electrical durability | 8000 operating cycles |
| Mechanical durability | 20,000 operating cycles |
| Power loss | 31 W |
| Dimensions (W × H × D) | 280 × 296 × 183 mm |
| Net weight | 16 kg |
The ABB 1SDA071357R1 is a 630 A Emax 2 air circuit breaker used for protection and control of low-voltage generator and electrical distribution circuits in industrial, commercial and infrastructure installations.
The circuit breaker has a rated current and rated uninterrupted current of 630 A.
The E1.2N version has a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz.
The Ekip G Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, with functionality designed to support generator applications.
The 1SDA071357R1 is a fixed four-pole air circuit breaker designed for permanent installation within low-voltage switchboards and electrical distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance and flexible power-management capabilities for modern generator, industrial, commercial and infrastructure low-voltage electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.