Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071322R1 Emax 2 E1.2N 250 Ekip Dip LSI four-pole fixed air circuit breaker with front terminals, a 250 A rated current, 690 V AC rated operational voltage and 66 kA ultimate short-circuit breaking capacity at 400/415 V AC.
£5,537.35
The ABB E1.2N 250 Ekip Dip LSI 4p F F, order code 1SDA071322R1, is a compact four-pole air circuit breaker (ACB) designed for switching and protection in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 series, this fixed circuit breaker combines a 250 A rated current, high short-circuit performance and an Ekip Dip LSI electronic protection release.
The integrated Ekip Dip LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Protection parameters are configured using DIP switches, providing straightforward adjustment and effective selectivity for industrial, commercial and infrastructure distribution networks.
With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, the E1.2N 250 provides robust protection in a compact Emax 2 frame. This version features a four-pole fixed configuration with front terminals, making it suitable for switchboards requiring switched neutral conductors and accessible front connections.
Air circuit breakers such as the ABB Emax 2 E1.2N provide switching and protection for low-voltage electrical distribution systems. By detecting overload and short-circuit conditions and interrupting fault current, the breaker helps protect switchboards, cables, busbars and connected electrical equipment while supporting safe and dependable system operation.
The Ekip Dip LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Its adjustable short-time function supports selective coordination with other protective devices, while the four-pole configuration allows the neutral conductor to be switched together with the three phases in applications where this is required.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071322R1 |
| Product type | Air circuit breaker |
| Frame / sub-type | E1.2 |
| Performance level | N |
| Rated current (In) | 250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 50 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 50 kA for 1 s / 30 kA for 3 s |
| Overload protection adjustment range | 100–250 A |
| Short-time short-circuit protection adjustment range | 150–2500 A |
| Instantaneous short-circuit protection adjustment range | 375–3750 A |
| Number of poles | 4P |
| Neutral pole current | 100% of Iu |
| Current type | AC |
| Trip unit | Ekip Dip LSI electronic release |
| Protection functions | Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) |
| Integrated earth-fault protection | No |
| Mounting type | Fixed |
| Terminal type | Front terminals |
| Main circuit connection | Bolt connection |
| Protection setting method | DIP switches |
| Mechanical durability | 20,000 cycles |
| Electrical durability at ≤440 V | 8,000 cycles |
| Electrical durability at 500–690 V | 8,000 cycles |
| Power loss | 31 W |
| Protection rating | IP30 |
| Standard | IEC 60947-2 |
| Width | 280 mm |
| Depth | 183 mm |
| Weight | approx. 16 kg |
The ABB 1SDA071322R1 is a four-pole air circuit breaker designed for switching and protecting low-voltage electrical distribution systems against overload and short-circuit conditions.
This Emax 2 air circuit breaker has a rated current of 250 A and is designed for industrial, commercial and infrastructure low-voltage distribution systems.
The E1.2N 250 has an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC and 50 kA at 690 V AC.
The Ekip Dip LSI electronic release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection, with settings configured using DIP switches.
The 1SDA071322R1 is a fixed four-pole air circuit breaker with front terminals for integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine compact construction, dependable interruption performance and configurable electronic protection for industrial, commercial and infrastructure low-voltage power distribution systems.
We use cookies