1SDA071310R1 ABB E6.2V 6300 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker

1SDA071310R1 ABB E6.2V 6300 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker

ABB 1SDA071310R1 Emax 2 E6.2V 6300 air circuit breaker, a 6300 A three-pole fixed ACB with Ekip G Hi-Touch LSIG generator-oriented electronic protection, 690 V AC rated voltage and 150 kA short-circuit breaking capacity at 400 V AC.

SKU: 1SDA071310R1MPN: 1SDA071310R1
Price
List Price £61,528.80 ex VAT
Your Price (ex VAT) Save 25%
£46,146.60 25% OFF
You save £15,382.20 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £46,146.60
Trade pricing is personalised to your account

Manufacturer Lead Time

£46,146.60

Why Choose the ABB E6.2V 6300 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker?

The ABB E6.2V 6300 Ekip G Hi-Touch LSIG 3p F HR, order code 1SDA071310R1, is a high-performance Emax 2 air circuit breaker (ACB) designed for generator protection and demanding high-current low-voltage power distribution systems. As part of the ABB SACE Emax 2 series, it combines a substantial 6300 A rated uninterrupted current with the E6.2 frame and V performance level for installations requiring exceptionally high fault-interruption capability.

This fixed three-pole circuit breaker incorporates the advanced Ekip G Hi-Touch LSIG electronic trip unit, combining long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection with generator-oriented functionality. The Hi-Touch platform is intended for sophisticated protection, measurement and monitoring requirements in generating plants and complex electrical distribution systems.

With a rated voltage of 690 V AC and an ultimate short-circuit breaking capacity of 150 kA at 400 V AC, the E6.2V 6300 is engineered for installations with very high prospective fault currents. Its fixed three-pole construction and rear flat horizontal terminals provide a robust configuration for integration into high-current generator and low-voltage distribution switchboards.

Key Advantages

  • Very high 6300 A rated uninterrupted current for major generator and power-distribution systems.
  • 150 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Advanced Ekip G Hi-Touch LSIG electronic trip unit with generator-oriented functionality.
  • Long-time overload, selective short-time, instantaneous short-circuit and integrated earth-fault protection.
  • Wide overload adjustment range of 2520–6300 A.
  • Advanced Hi-Touch platform for sophisticated protection, measurement and monitoring requirements.
  • Fixed three-pole construction with rear flat horizontal terminals for high-current switchboard integration.
  • Four auxiliary change-over contacts and circuit-breaker open/closed indication.

Key Features

  • ABB SACE Emax 2 E6.2V series.
  • 6300 A rated uninterrupted current.
  • Three-pole fixed configuration.
  • 690 V AC rated voltage.
  • 150 kA Icu at 400 V AC, 50 Hz.
  • Ekip G Hi-Touch LSIG electronic release.
  • Long-time overload protection.
  • Selective short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • Generator-oriented protection functionality.
  • Overload release adjustment from 2520–6300 A.
  • Short-time delayed short-circuit adjustment from 3780–63000 A.
  • Instantaneous short-circuit adjustment from 9450–94500 A.
  • Rear flat horizontal main circuit terminals.
  • Four auxiliary change-over contacts.
  • Circuit-breaker open/closed indication.
  • Optional motor operating mechanism capability.
  • IP30 degree of protection.
  • 767 W power loss.

Advanced 6300 A Generator Protection for High-Fault-Level Power Systems

Air circuit breakers used in generator and major distribution applications must combine high continuous-current capability with dependable protection against overloads and severe electrical faults. The ABB Emax 2 E6.2V combines a 6300 A rated uninterrupted current with 150 kA ultimate short-circuit breaking capacity at 400 V AC, making it suitable for generator switchboards and distribution systems with exceptionally high prospective fault currents.

The Ekip G Hi-Touch LSIG electronic trip unit combines comprehensive LSIG protection with generator-oriented functionality. Adjustable long-time, selective short-time and instantaneous protection ranges enable the breaker to be coordinated with the wider electrical system, while integrated earth-fault protection adds coverage against faults involving earth. The Hi-Touch platform further supports advanced protection, measurement and monitoring requirements in sophisticated generating and distribution installations.

Typical Applications

  • Generator protection and power-generating plants.
  • Main low-voltage generator switchboards.
  • Very high-current main distribution boards.
  • Standby and emergency power systems.
  • High-fault-level industrial electrical distribution systems.
  • Data centres and critical power infrastructure.
  • Manufacturing and process facilities with on-site generation.
  • Generator incomers and high-current feeders requiring advanced LSIG protection.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA071310R1
EAN 8015644751609
Product type Air circuit breaker (ACB)
Frame E6.2
Short-circuit performance level V
Rated current 6300 A
Rated uninterrupted current (Iu) 6300 A
Rated voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) 150 kA at 400 V AC, 50 Hz
Number of poles 3
Current type AC
Trip unit Ekip G Hi-Touch LSIG
Release type Solid-state electronic
Protection functions Long-time overload, selective short-time, instantaneous short circuit and earth fault
Overload release adjustment 2520–6300 A
Short-time delayed short-circuit adjustment 3780–63000 A
Instantaneous short-circuit adjustment 9450–94500 A
Integrated earth-fault protection Yes
Generator-oriented protection Yes, Ekip G platform
Mounting type Fixed
Terminal connection Rear flat horizontal
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Integrated undervoltage release No
Motor drive integrated No
Motor drive optional Yes
Degree of protection IP30
Power loss 767 W
Dimensions (H × W × D) 371 × 762 × 270 mm
Net weight 109 kg
Country of origin Italy
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA071310R1 used for?

The ABB 1SDA071310R1 is an Emax 2 air circuit breaker designed for generator protection and very high-current low-voltage power distribution, combining a 6300 A current rating with advanced Ekip G Hi-Touch LSIG electronic protection.

What is the current rating of the ABB E6.2V 6300?

The circuit breaker has a rated uninterrupted current of 6300 A, making it suitable for major generator, industrial, infrastructure and critical power distribution systems.

What is the breaking capacity of the ABB 1SDA071310R1?

The E6.2V 6300 provides an ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, providing very high fault-interruption capability for demanding electrical distribution systems.

What protection does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection together with generator-oriented protection functionality and the advanced capabilities of ABB's Hi-Touch platform.

Is the ABB 1SDA071310R1 fixed or withdrawable?

The 1SDA071310R1 is a fixed three-pole air circuit breaker fitted with rear flat horizontal terminals for integration into generator and high-current low-voltage distribution switchboards.

Trusted Generator Protection from ABB

ABB SACE Emax 2 air circuit breakers with Ekip G protection combine very high continuous-current capability, exceptional short-circuit performance and advanced generator-oriented electronic protection for demanding generating, industrial and critical low-voltage power systems.