Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071309R1 SACE Emax 2 E6.2V 6300 three-pole fixed air circuit breaker with Ekip Hi-Touch LSIG protection, 6300 A rated current and 150 kA ultimate breaking capacity at 400–440 V AC.
£45,693.46
The ABB E6.2V 6300 Ekip Hi-Touch LSIG 3p FHR, order code 1SDA071309R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and management of high-current low-voltage electrical distribution systems. Part of the advanced ABB SACE Emax 2 E6.2 range, this fixed three-pole breaker combines a 6300 A rated uninterrupted current with the Ekip Hi-Touch LSIG electronic trip unit for comprehensive circuit protection and electrical system supervision.
The Ekip Hi-Touch LSIG trip unit provides long-time, short-time, instantaneous and ground-fault protection, helping protect electrical installations against overloads, short circuits and earth faults. The Hi-Touch platform also provides advanced measurement and monitoring capabilities, making this breaker particularly suitable for critical industrial, infrastructure and commercial power distribution systems requiring sophisticated protection and system management.
The E6.2V performance level delivers an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, with a 100 kA short-time withstand current for 1 s and 3 s. Rated for operation up to 690 V AC, the breaker uses a fixed three-pole construction with horizontal rear flat terminals (FHR) for integration into high-capacity switchboards and busbar systems.
Air circuit breakers such as the ABB SACE Emax 2 E6.2V provide switching, isolation and protection for major low-voltage distribution circuits. The combination of a 6300 A current rating, 150 kA breaking capacity at 400–440 V AC and 690 V AC operating capability makes this breaker particularly suitable for main incomers, transformer secondary circuits, bus couplers and other critical high-power positions.
The Ekip Hi-Touch LSIG release continuously supervises circuit conditions and provides dedicated long-time, short-time, instantaneous and ground-fault protection. Its advanced measurement and monitoring capabilities support effective management of complex electrical networks, while adjustable protection settings enable selective coordination to help isolate faults without unnecessarily interrupting unaffected sections of the installation.
| Series | SACE Emax 2 |
|---|---|
| Frame | E6.2V |
| ABB order code | 1SDA071309R1 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 6300 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Short-circuit performance level | V |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Electronic / solid-state |
| Protection functions | L, S, I and G |
| Overload release adjustment | 2520–6300 A |
| Short-time short-circuit adjustment | 3780–63000 A |
| Instantaneous short-circuit adjustment | 9450–94500 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 150 kA |
| Ics as percentage of Icu | 100% |
| Short-time withstand current (Icw), 1 s | 100 kA |
| Short-time withstand current (Icw), 3 s | 100 kA |
| Integrated earth-fault protection | Yes |
| Execution | Fixed |
| Terminal arrangement | Rear flat horizontal (FHR) |
| Main terminal connection | Bolted |
| Terminal tightening torque | 70 N·m |
| Auxiliary contacts | 4 change-over contacts |
| Motor operator | Optional |
| Protection rating | IP30 |
| Suitable for IT networks | Yes, up to 690 V AC |
| Electrical durability | 2000 operating cycles |
| Mechanical durability | 12000 operating cycles |
| Power loss | 767 W |
| Dimensions (W × H × D) | 762 × 371 × 270 mm |
| Net weight | 109 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644751593 |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071309R1 is a SACE Emax 2 E6.2V 6300 Ekip Hi-Touch LSIG three-pole fixed air circuit breaker with horizontal rear terminals, designed for high-current low-voltage power distribution and protection.
This E6.2V air circuit breaker has a rated uninterrupted current of 6300 A and an overload protection adjustment range of 2520–6300 A.
The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection together with advanced electrical measurement and monitoring capabilities.
The E6.2V 6300 configuration has an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, with a short-time withstand current of 100 kA for 1 s and 3 s.
It is typically used in main low-voltage switchboards, transformer secondary circuits, industrial distribution systems, bus couplers and high-current incoming feeders requiring comprehensive LSIG protection and high short-circuit performance.
ABB SACE Emax 2 air circuit breakers are engineered for demanding low-voltage power distribution applications, combining high current capacity, advanced electronic protection and exceptional short-circuit performance for dependable operation in critical electrical systems.
We use cookies