1SDA071307R1 ABB Emax 2 E6.2V 6300A Ekip G Touch LSIG 3P Air Circuit Breaker

1SDA071307R1 ABB Emax 2 E6.2V 6300A Ekip G Touch LSIG 3P Air Circuit Breaker

ABB 1SDA071307R1 is a SACE Emax 2 E6.2V 6300 A fixed three-pole air circuit breaker with an Ekip G Touch LSIG electronic trip unit, 690 V AC rated operational voltage and 150 kA breaking capacity at 400–440 V AC.

SKU: 1SDA071307R1MPN: 1SDA071307R1
Price
List Price £60,632.25 ex VAT
Your Price (ex VAT) Save 25%
£45,474.19 25% OFF
You save £15,158.06 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £45,474.19
Trade pricing is personalised to your account

Manufacturer Lead Time

£45,474.19

Why Choose the ABB 1SDA071307R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA071307R1 is a high-performance SACE Emax 2 E6.2V air circuit breaker (ACB) designed for protection, control and management of high-current low-voltage electrical distribution systems. Rated at 6300 A, this fixed three-pole circuit breaker combines ABB’s E6.2 frame with the advanced Ekip G Touch LSIG electronic trip unit for comprehensive protection in demanding industrial and infrastructure applications.

As part of the ABB SACE Emax 2 series, the E6.2V is engineered for high-performance power distribution and provides protection against overload, short-circuit and earth-fault conditions. The Ekip G Touch LSIG release provides advanced electronic protection functions together with an intuitive touchscreen interface, making the breaker suitable for sophisticated power distribution and generator applications.

With a rated uninterrupted current of 6300 A, rated operational voltage up to 690 V AC and rated ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, the 1SDA071307R1 is designed for installations requiring high fault-clearing performance. This version is a fixed, three-pole breaker with rear horizontal terminals, providing a robust solution for integration into low-voltage switchboards and power distribution assemblies.

Key Advantages

  • High-capacity 6300 A air circuit breaker for demanding low-voltage distribution systems.
  • 150 kA ultimate breaking capacity at 400–440 V AC for high fault-level installations.
  • Advanced Ekip G Touch LSIG electronic trip unit for comprehensive circuit protection.
  • LSIG protection provides overload, short-time, instantaneous and earth-fault protection.
  • Three-pole fixed configuration for permanent installation within switchboards.
  • Rear horizontal terminals support efficient integration with high-current busbar systems.

Key Features

  • ABB SACE Emax 2 E6.2V air circuit breaker.
  • 6300 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • 150 kA Icu at 400–440 V AC.
  • 100 kA short-time withstand current for 1 and 3 seconds.
  • Ekip G Touch LSIG electronic release.
  • Fixed three-pole construction.
  • Rear flat horizontal terminals.
  • Suitable for IT networks up to 690 V.
  • Designed and rated in accordance with IEC 60947-2.

Advanced Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E6.2V protect major low-voltage distribution circuits against damaging overcurrent and short-circuit conditions. The 1SDA071307R1 combines a high continuous-current rating with substantial short-circuit interruption capability, making it particularly suitable for main incomers, generators and high-power distribution assemblies.

The Ekip G Touch LSIG trip unit provides long-time, short-time, instantaneous and ground-fault protection functions. Its electronic architecture allows protection settings to be configured for the requirements of the electrical system, helping engineers achieve effective protection and selectivity throughout complex low-voltage networks.

Typical Applications

  • Main incoming protection for low-voltage switchboards.
  • High-current industrial power distribution systems.
  • Generator protection and generator distribution systems.
  • Transformer secondary and installation protection.
  • Manufacturing plants and process facilities.
  • Data centres and critical power infrastructure.
  • Commercial and infrastructure electrical distribution.
  • High-power IEC low-voltage switchgear assemblies.

Technical Specifications

Series SACE Emax 2
Frame / sub-type E6.2
Order code / MPN 1SDA071307R1
Product type Air circuit breaker
Short-circuit performance level V
Rated current (In) 6300 A
Rated uninterrupted current (Iu) 6300 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 380–440 V AC 150 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 130 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 100 kA
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 100 kA for 1 s / 100 kA for 3 s
Number of poles 3
Trip unit Ekip G Touch LSIG
Release type Electronic
Protection functions LSIG
Current type AC
Installation version Fixed
Terminal connection Rear flat horizontal
Connecting capacity 6000 mm²
Electrical durability 2000 operating cycles
Mechanical durability 12,000 operating cycles
Power loss 767 W
Dimensions (W × H × D) 762 × 371 × 270 mm
Net weight 109 kg
Standard IEC 60947-2
Suitable for IT networks Yes, up to 690 V

Frequently Asked Questions

What is the ABB 1SDA071307R1 used for?

The ABB 1SDA071307R1 is a 6300 A Emax 2 air circuit breaker used to protect and control high-current low-voltage electrical distribution systems, including switchboards, generator systems and industrial power networks.

What is the current rating of the ABB 1SDA071307R1?

The breaker has a rated current and rated uninterrupted current of 6300 A.

What breaking capacity does the E6.2V 6300 provide?

The E6.2V version has a rated ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, reducing to 130 kA at 500–525 V AC and 100 kA at 690 V AC.

What protection does the Ekip G Touch LSIG trip unit provide?

The Ekip G Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection functions.

Is the ABB 1SDA071307R1 a fixed or withdrawable circuit breaker?

The 1SDA071307R1 is a fixed three-pole air circuit breaker equipped with rear flat horizontal terminals for integration into low-voltage switchboards.

Trusted High-Performance Circuit Protection

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection and flexible power-management capabilities for demanding industrial, infrastructure and critical-power distribution systems.