ABB 1SDA071300R1 is a SACE Emax 2 E6.2H 6300 A fixed three-pole air circuit breaker with rear flat horizontal terminals and an Ekip G Hi-Touch LSIG electronic trip unit for advanced low-voltage distribution and generator protection.
£38,253.28
The ABB E6.2H 6300 Ekip G Hi-Touch LSIG 3p FHR, order code 1SDA071300R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection, measurement and control of high-current low-voltage distribution and generator systems. As part of the ABB Emax 2 E6.2 series, this fixed three-pole breaker combines a 6300 A rated current with the advanced Ekip G Hi-Touch LSIG electronic trip unit.
The Ekip G Hi-Touch LSIG release provides sophisticated long-time, short-time, instantaneous and earth-fault protection together with generator-oriented protection functionality. Its advanced touchscreen interface supports intuitive configuration and monitoring, while the Hi-Touch platform provides enhanced measurement and power-quality analysis capabilities for demanding electrical networks.
With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 100 kA and a short-time withstand current of 100 kA, the E6.2H is engineered for high-capacity installations requiring dependable fault protection and selectivity. This configuration features a fixed, three-pole design with rear flat horizontal terminals and four auxiliary change-over contacts for breaker status signalling.
The ABB Ekip G Hi-Touch LSIG trip unit combines comprehensive circuit protection with advanced functions intended for generator and sophisticated power-distribution applications. Long-time, short-time, instantaneous and earth-fault protection enables the breaker to respond effectively to overloads and fault conditions while supporting selective coordination throughout complex electrical networks.
The E6.2H platform combines a 6300 A current rating with 100 kA short-circuit interruption and short-time withstand capability. Together with the advanced monitoring and analysis functions available through the Ekip Hi-Touch platform, this makes the 1SDA071300R1 particularly suitable for critical switchboards where protection selectivity, system visibility and continuity of supply are essential.
| Series | SACE Emax 2 E6.2 |
|---|---|
| Order code / MPN | 1SDA071300R1 |
| Product type | Air circuit breaker |
| Rated current (In) | 6300 A |
| Rated uninterrupted current (Iu) | 6300 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 3 |
| Installation | Fixed |
| Main terminals | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Trip unit | Ekip G Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and earth fault |
| Overload release setting range | 2520–6300 A |
| Short-time delayed short-circuit setting range | 3780–63000 A |
| Ultimate breaking capacity (Icu) at 400/415 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500/525 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 100 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Short-time withstand current (Icw) | 100 kA for 1 s / 3 s |
| Short-circuit performance level | H |
| Degree of protection | IP30 |
| Auxiliary contacts | 4 change-over contacts |
| Breaker position indication | Open / closed |
| Mechanical durability | 12000 cycles |
| Power loss | 767 W |
| Dimensions (W × H × D) | 762 × 371 × 270 mm |
| Net weight | approx. 109 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644751500 |
It is a high-current SACE Emax 2 air circuit breaker designed for advanced protection, measurement and control of demanding low-voltage distribution and generator systems.
The E6.2H 6300 has a rated uninterrupted current of 6300 A.
The breaker is equipped with an Ekip G Hi-Touch LSIG electronic trip unit providing advanced long-time, short-time, instantaneous and earth-fault protection together with generator-oriented functionality.
The E6.2H configuration provides an ultimate short-circuit breaking capacity of 100 kA at system voltages including 400/415 V AC and 690 V AC.