ABB 1SDA071293R1 Emax 2 E6.2H 6300 air circuit breaker, a 6300 A three-pole fixed ACB with Ekip Dip LSIG electronic protection, 690 V AC rated operational voltage, 100 kA short-circuit breaking capacity and rear flat horizontal terminals.
£34,979.02
The ABB E6.2H 6300 Ekip Dip LSIG 3p F HR, order code 1SDA071293R1, is a high-current Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, it combines a substantial 6300 A rated uninterrupted current with the E6.2 frame and H short-circuit performance level for industrial, infrastructure and critical power applications.
This fixed three-pole circuit breaker incorporates the Ekip Dip LSIG solid-state electronic trip unit, providing long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection. The comprehensive LSIG protection package supports selective coordination while adding integrated earth-fault protection for installations requiring broader fault coverage.
With a rated operational voltage of 690 V AC, the E6.2H 6300 provides an ultimate short-circuit breaking capacity of 100 kA across 400–690 V AC and a rated short-time withstand current of 100 kA for both 1 s and 3 s. Its fixed three-pole construction and rear flat horizontal terminals provide a robust solution for integration into very high-current low-voltage switchboards.
Air circuit breakers such as the ABB Emax 2 E6.2H provide switching, isolation and electronic protection at major distribution points in high-current low-voltage systems. With a rated uninterrupted current of 6300 A, 100 kA ultimate short-circuit breaking capacity across 400–690 V AC and 100 kA short-time withstand capability for both 1 s and 3 s, this configuration is designed for substantial loads and high prospective fault levels.
The Ekip Dip LSIG trip unit combines long-time overload protection with selective short-time, instantaneous short-circuit and earth-fault protection. The selective short-time function can assist coordination with downstream protective devices, while integrated earth-fault protection provides additional coverage against faults involving earth, making this breaker suitable for sophisticated high-current distribution architectures.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071293R1 |
| EAN | 8015644751432 |
| Product type | Air circuit breaker (ACB) |
| Frame | E6.2 |
| Short-circuit performance level | H |
| Rated current (In) | 6300 A |
| Rated uninterrupted current (Iu) | 6300 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 400 / 415 / 440 / 500 / 525 / 690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 100 kA at 220 / 230 / 380 / 400 / 415 / 440 / 500 / 660 / 690 V AC |
| Rated service short-circuit breaking capacity | 100% of Icu |
| Rated short-time withstand current (Icw) | 100 kA for 1 s; 100 kA for 3 s |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSIG |
| Release type | Solid-state electronic |
| Protection functions | Long-time overload, selective short-time, instantaneous short circuit and earth fault |
| Integrated earth-fault protection | Yes |
| Mounting type | Fixed |
| Terminal connection | Rear flat horizontal |
| Terminal type | Bolt |
| Recommended main circuit screw | M12 |
| Tightening torque | 70 N·m |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 767 W |
| Mechanical durability | 12,000 cycles |
| Mechanical operating rate | 60 cycles per hour |
| Electrical durability | 2000 cycles at Ue ≤ 440 V AC |
| Electrical operating rate | 10 cycles per hour |
| Product height | 371 mm |
| Product width | 762 mm |
| Country of origin | Italy |
| Standard | IEC 60947-2 |
The ABB 1SDA071293R1 is an Emax 2 air circuit breaker designed for switching and protection of very high-current low-voltage electrical distribution systems, including main incomers, transformer applications and high-current feeders requiring comprehensive LSIG protection.
The circuit breaker has a rated uninterrupted current of 6300 A, making it suitable for major industrial, infrastructure and critical low-voltage power distribution systems.
The E6.2H 6300 provides an ultimate short-circuit breaking capacity of 100 kA at 400 / 415 / 440 / 500 / 525 / 690 V AC, together with a rated short-time withstand current of 100 kA for both 1 s and 3 s.
The Ekip Dip LSIG solid-state electronic trip unit provides long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection, giving this configuration comprehensive protection for demanding low-voltage distribution systems.