Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071292R1 Emax 2 E6.2H 6300 air circuit breaker, a 6300 A three-pole fixed ACB with Ekip Dip LSI electronic protection, 690 V AC rated operational voltage and rear horizontal connections.
£34,467.44
The ABB E6.2H 6300 Ekip Dip LSI 3p F HR, order code 1SDA071292R1, is a high-current Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, it combines a substantial 6300 A rated uninterrupted current with the E6.2 frame and H short-circuit performance level for industrial, infrastructure and critical power applications.
This fixed three-pole circuit breaker incorporates the Ekip Dip LSI solid-state electronic trip unit, providing long-time overload, selective short-time and instantaneous short-circuit protection. The LSI protection functions support selective coordination between upstream and downstream protective devices, while the Ekip Dip interface provides straightforward local configuration of the principal protection settings.
With a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V AC and a rated impulse withstand voltage of 12 kV, the E6.2H 6300 is engineered for demanding high-current distribution. Its fixed three-pole construction and rear horizontal terminals provide a robust solution for integration into large low-voltage switchboards.
Air circuit breakers such as the ABB Emax 2 E6.2H provide switching, isolation and electronic protection at major distribution points in high-current low-voltage systems. With a rated uninterrupted current of 6300 A, this configuration is designed for substantial loads in main switchboards, transformer distribution systems, industrial installations and other applications where very high continuous-current capability is required.
The Ekip Dip LSI trip unit combines long-time overload protection with selective short-time and instantaneous short-circuit protection. The selective short-time function can support coordination with downstream protective devices, helping isolate faults closer to their source while maintaining continuity in unaffected sections of a properly engineered distribution system.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071292R1 |
| EAN | 8015644751425 |
| Product type | Air circuit breaker (ACB) |
| Frame | E6.2 |
| Performance level | H |
| Rated current (In) | 6300 A |
| Rated uninterrupted current (Iu) | 6300 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time overload, selective short-time and instantaneous short circuit |
| Integrated earth-fault protection | No |
| Mounting type | Fixed |
| Terminal connection | Rear horizontal |
| Connecting capacity | 6000 mm² |
| Power loss | 767 W |
| Mechanical durability | 12,000 cycles |
| Mechanical operating rate | 60 cycles per hour |
| Electrical durability | 2000 cycles at Ue ≤ 440 V AC |
| Electrical operating rate | 10 cycles per hour |
| Dimensions (H × W × D) | 371 × 762 × 270 mm |
| Net weight | 109 kg |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA071292R1 is an Emax 2 air circuit breaker designed for switching and protection of very high-current low-voltage electrical distribution systems, including main incomers, transformer applications and high-current feeders.
The circuit breaker has a rated uninterrupted current of 6300 A, making it suitable for major industrial, infrastructure and critical low-voltage power distribution systems.
The ABB 1SDA071292R1 has a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V AC and a rated impulse withstand voltage of 12 kV.
The Ekip Dip LSI solid-state electronic trip unit provides long-time overload, selective short-time and instantaneous short-circuit protection. As an LSI configuration, it does not incorporate integrated earth-fault protection.
The 1SDA071292R1 is a fixed three-pole air circuit breaker with rear horizontal connections for integration into high-current low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine substantial continuous-current capability, advanced electronic protection and robust construction for demanding industrial, infrastructure and critical low-voltage power distribution applications.
We use cookies