ABB 1SDA071261R1 is a SACE Emax 2 E6.2H 5000 A fixed three-pole air circuit breaker with rear horizontal terminals, an Ekip Dip LI electronic trip unit, a 690 V AC rated operational voltage and 100 kA short-circuit breaking capacity at 400 V AC.
£26,120.98
The ABB E6.2H 5000 Ekip Dip LI 3p FHR, order code 1SDA071261R1, is a high-current SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power distribution systems. Rated at 5000 A, this three-pole fixed circuit breaker combines ABB's E6.2H frame with an Ekip Dip LI solid-state electronic trip unit.
The Ekip Dip LI release provides long-time overload (L) and instantaneous short-circuit (I) protection. This LI configuration provides straightforward electronic overcurrent protection for major incomers and high-current feeders where long-time and instantaneous protection functions are required without integrated short-time or earth-fault protection.
The 1SDA071261R1 is supplied as a fixed three-pole breaker with rear horizontal (HR) terminals, four auxiliary contacts and circuit-breaker open/closed position indication. With a rated operational voltage of 690 V AC and a short-circuit breaking capacity of 100 kA at 400 V AC, it is engineered for substantial industrial, infrastructure and critical power distribution installations.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and fault protection for high-current low-voltage electrical networks. The E6.2H frame combines a substantial 5000 A current rating with 100 kA short-circuit breaking capacity at 400 V AC, making the 1SDA071261R1 suitable for major main incomers, transformer secondary circuits and other high-current distribution feeders.
The Ekip Dip LI trip unit provides electronic long-time overload and instantaneous short-circuit protection. Long-time protection responds to sustained overcurrent conditions that could otherwise cause excessive thermal stress, while instantaneous protection provides rapid operation during severe short-circuit faults, helping protect conductors, switchgear and connected equipment within a correctly coordinated electrical system.
| Series | SACE Emax 2 |
|---|---|
| Frame | E6.2H |
| ABB order code | 1SDA071261R1 |
| EAN / GTIN | 8015644751111 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated current | 5000 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LI |
| Release type | Solid-state electronic |
| Protection functions | L and I |
| Long-time overload protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Integrated short-time protection | No |
| Integrated earth-fault protection | No |
| Rated operational voltage | 690 V AC |
| Short-circuit breaking capacity at 400 V AC | 100 kA |
| Short-circuit performance level | H |
| Current type | AC |
| Installation | Fixed |
| Terminal configuration | Rear horizontal (HR) |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Product dimensions (W × H × D) | 762 × 371 × 270 mm |
| Product net weight | 109 kg |
| Country of origin | Italy |
| Standard | IEC 60947-2 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071261R1 is a SACE Emax 2 E6.2H fixed three-pole air circuit breaker rated at 5000 A and equipped with an Ekip Dip LI solid-state electronic trip unit.
The Ekip Dip LI release provides long-time overload (L) and instantaneous short-circuit (I) protection.
The circuit breaker has a rated uninterrupted current of 5000 A, making it suitable for major high-current low-voltage distribution circuits.
The ABB E6.2H 5000 configuration has a short-circuit breaking capacity of 100 kA at 400 V AC.
The ABB 1SDA071261R1 has a rated operational voltage of 690 V AC.
No. The supplied Ekip Dip LI configuration provides long-time overload and instantaneous short-circuit protection; an integrated G earth-fault protection function is not included in this LI configuration.
The 1SDA071261R1 is a fixed-version circuit breaker designed for permanent installation within a low-voltage switchboard.
This configuration is a fixed circuit breaker with rear horizontal terminals, providing rear-facing main connections suitable for integration with switchboard busbars and high-current conductors.
ABB SACE Emax 2 air circuit breakers combine high-current switching, isolation and electronic protection with robust short-circuit performance for demanding industrial, infrastructure, critical power and large-scale low-voltage distribution applications worldwide.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.