1SDA071247R1 ABB E6.2V 4000 Ekip G Touch LSIG 3p FHR Air Circuit Breaker

1SDA071247R1 ABB E6.2V 4000 Ekip G Touch LSIG 3p FHR Air Circuit Breaker

ABB 1SDA071247R1 is a SACE Emax 2 E6.2V 4000 A fixed three-pole air circuit breaker with rear horizontal terminals and an Ekip G Touch LSIG electronic trip unit for advanced low-voltage distribution and generator protection.

SKU: 1SDA071247R1MPN: 1SDA071247R1
Price
List Price £27,519.39 ex VAT
Your Price (ex VAT) Save 25%
£20,639.54 25% OFF
You save £6,879.85 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £20,639.54
Trade pricing is personalised to your account

Manufacturer Lead Time

£20,639.54

Why Choose the ABB E6.2V 4000 Ekip G Touch LSIG 3p FHR Air Circuit Breaker?

The ABB E6.2V 4000 Ekip G Touch LSIG 3p FHR, order code 1SDA071247R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and control of high-current low-voltage distribution and generator systems. As part of the advanced ABB Emax 2 E6.2 series, this fixed three-pole breaker combines a 4000 A rated current with the sophisticated Ekip G Touch LSIG electronic trip unit.

The Ekip G Touch LSIG protection release provides long-time, short-time, instantaneous and earth-fault protection together with functions developed for generator protection applications. Its touchscreen interface supports intuitive configuration, measurement and monitoring, helping operators manage demanding electrical installations and coordinate protection throughout the distribution system.

With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 150 kA at 400/415 V AC, the E6.2V is engineered for installations with exceptionally high prospective fault currents. This configuration features a fixed, three-pole design with rear horizontal terminals and four auxiliary change-over contacts for breaker status signalling.

Key Advantages

  • High-performance ABB SACE Emax 2 E6.2V air circuit breaker.
  • 4000 A rated uninterrupted current for high-current electrical distribution.
  • 150 kA ultimate short-circuit breaking capacity at 400/415 V AC.
  • Advanced Ekip G Touch LSIG electronic trip unit for distribution and generator protection.
  • LSIG protection covers overload, selective short circuit, instantaneous short circuit and earth fault.
  • Touchscreen interface supports straightforward configuration and electrical monitoring.
  • Fixed three-pole construction with rear horizontal terminals for switchboard integration.
  • High short-time withstand capability supports selective protection in demanding networks.

Key Features

  • ABB SACE Emax 2 E6.2V series.
  • 4000 A rated current.
  • Three-pole fixed configuration.
  • Ekip G Touch LSIG solid-state electronic protection release.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Ultimate short-circuit breaking capacity of 150 kA at 400/415 V AC.
  • 100 kA short-time withstand current for 1 s and 3 s.
  • Integrated earth-fault protection.
  • Rear flat horizontal main terminals.
  • Four auxiliary change-over contacts for breaker status signalling.

Advanced Generator and Power Distribution Protection

The ABB Ekip G Touch LSIG trip unit combines comprehensive circuit protection with functions intended for generator and advanced power-distribution applications. Adjustable long-time, short-time, instantaneous and earth-fault protection allows the breaker to respond to overloads and fault conditions while supporting selective coordination with other protective devices.

The E6.2V performance level provides exceptionally high short-circuit interruption and withstand capability for demanding electrical networks. Combined with the Emax 2 platform's measurement, monitoring and connectivity capabilities, this breaker is well suited to critical switchboards where system reliability, protection selectivity and effective power management are important.

Typical Applications

  • Generator protection and generator switchboards.
  • High-current low-voltage power distribution systems.
  • Main incoming protection in LV switchboards.
  • High-capacity industrial feeder protection.
  • Manufacturing plants and process facilities.
  • Data centres and critical power infrastructure.
  • Utility, infrastructure and power-generation installations.

Technical Specifications

Series SACE Emax 2 E6.2
Order code / MPN 1SDA071247R1
Product type Air circuit breaker
Rated current (In) 4000 A
Rated uninterrupted current (Iu) 4000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Installation Fixed
Main terminals Rear flat horizontal
Trip unit Ekip G Touch LSIG
Release type Electronic
Protection functions Long-time, short-time, instantaneous and earth fault
Overload release adjustment 1600–4000 A
Short-time delayed short-circuit adjustment 2400–40000 A
Instantaneous short-circuit adjustment 6000–60000 A
Ultimate breaking capacity (Icu) at 400/415 V AC 150 kA
Ultimate breaking capacity (Icu) at 500 V AC 130 kA
Ultimate breaking capacity (Icu) at 690 V AC 100 kA
Service breaking capacity (Ics) 100% of Icu
Short-time withstand current (Icw) 100 kA for 1 s / 3 s
Power loss 309 W
Mechanical durability 12000 cycles
Auxiliary contacts 4 change-over contacts
Earth-fault protection Integrated
Suitable for IT networks Yes, up to 690 V
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071247R1 used for?

It is a high-current SACE Emax 2 air circuit breaker designed for protection and control of demanding low-voltage power distribution and generator systems.

What is the current rating of this circuit breaker?

The E6.2V 4000 has a rated uninterrupted current of 4000 A.

Which protection unit is fitted to the 1SDA071247R1?

The breaker is equipped with an Ekip G Touch LSIG electronic trip unit providing long-time, short-time, instantaneous and earth-fault protection together with generator-oriented protection functionality.

What is the breaking capacity of the ABB E6.2V 4000?

The E6.2V configuration provides an ultimate short-circuit breaking capacity of 150 kA at 400/415 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC.

How is this Emax 2 circuit breaker installed?

The 1SDA071247R1 is a fixed, three-pole air circuit breaker equipped with rear flat horizontal main terminals for integration into low-voltage switchboards.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance and flexible system integration for dependable protection of demanding industrial, infrastructure and power-generation electrical systems.