ABB 1SDA071231R1 Emax 2 E6.2H 4000 air circuit breaker, a 4000 A three-pole fixed ACB with Ekip Dip LI electronic protection, 100 kA short-circuit breaking capacity at 440 V AC and 100 kA short-time withstand current for 1 s.
£17,043.74
The ABB E6.2H 4000 Ekip Dip LI 3p F HR, order code 1SDA071231R1, is a high-performance Emax 2 air circuit breaker (ACB) designed for protection and switching in high-current low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, it combines a 4000 A rated uninterrupted current with high short-circuit performance for industrial, infrastructure and critical power applications.
This fixed three-pole circuit breaker incorporates the Ekip Dip LI solid-state electronic trip unit, providing long-time overload and instantaneous short-circuit protection. The Ekip Dip interface provides straightforward local adjustment of the principal protection settings, making the breaker suitable for installations requiring dependable electronic protection without more complex selective or earth-fault functions.
With a rated uninterrupted current of 4000 A, an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s, the E6.2H is engineered for demanding high-current distribution systems. Its fixed three-pole construction and rear horizontal terminals provide a robust solution for integration into low-voltage switchboards.
Air circuit breakers such as the ABB Emax 2 E6.2H provide switching, isolation and protection for high-current low-voltage distribution systems. With a 4000 A rated uninterrupted current and both 100 kA breaking capacity at 440 V AC and 100 kA short-time withstand capability for 1 s, this configuration is suited to main distribution points, transformer applications and other high-current sections of electrical installations.
The Ekip Dip LI electronic trip unit combines adjustable long-time overload protection with instantaneous short-circuit protection. The long-time protection setting can be adjusted between 1600 A and 4000 A, allowing the breaker to be configured around the requirements of the protected circuit while retaining rapid instantaneous operation during severe short-circuit conditions.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071231R1 |
| EAN | 8015644750817 |
| Product type | Air circuit breaker (ACB) |
| Frame | E6.2 |
| Short-circuit performance level | H |
| Rated current | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 440 V AC |
| Rated short-time withstand current (Icw) | 100 kA for 1 s |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LI |
| Release type | Solid-state electronic |
| Protection functions | Long-time overload and instantaneous short circuit |
| Overload release adjustment | 1600–4000 A |
| Selective short-time protection | No |
| Integrated earth-fault protection | No |
| Mounting type | Fixed |
| Terminal connection | Rear horizontal |
| Main circuit connection | Screw / bolt connection |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Integrated undervoltage release | No |
| Degree of protection | IP30 |
The ABB 1SDA071231R1 is an Emax 2 air circuit breaker designed for switching and protection of high-current low-voltage electrical distribution systems, including transformer, main incomer and high-current feeder applications.
The circuit breaker has a rated uninterrupted current of 4000 A, making it suitable for demanding industrial, infrastructure and critical power distribution systems.
The E6.2H 4000 provides an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s.
The Ekip Dip LI solid-state electronic trip unit provides adjustable long-time overload and instantaneous short-circuit protection. This LI configuration does not incorporate selective short-time or integrated earth-fault protection.
The 1SDA071231R1 is a fixed three-pole air circuit breaker fitted with rear horizontal terminals for integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine high-current capability, robust short-circuit performance and dependable electronic protection for demanding industrial, infrastructure and critical low-voltage power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.