1SDA071218R1 ABB E4.2H 4000 Ekip Hi-Touch LSI 3p FHR Air Circuit Breaker

1SDA071218R1 ABB E4.2H 4000 Ekip Hi-Touch LSI 3p FHR Air Circuit Breaker

ABB 1SDA071218R1 SACE Emax 2 E4.2H fixed three-pole air circuit breaker with Ekip Hi-Touch LSI electronic protection, 4000 A rated current, 690 V AC operational voltage and 100 kA breaking capacity at 400–440 V AC.

SKU: 1SDA071218R1MPN: 1SDA071218R1
Price
List Price £27,188.06 ex VAT
Your Price (ex VAT) Save 25%
£20,391.05 25% OFF
You save £6,797.02 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £20,391.05
Trade pricing is personalised to your account

Manufacturer Lead Time

£20,391.05

Why Choose the ABB E4.2H 4000 Ekip Hi-Touch LSI 3p FHR Air Circuit Breaker?

The ABB E4.2H 4000 Ekip Hi-Touch LSI 3p FHR, order code 1SDA071218R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) engineered for protection and switching in demanding low-voltage power distribution systems. This fixed three-pole E4.2 breaker combines a 4000 A rated uninterrupted current with ABB's advanced Ekip Hi-Touch LSI electronic trip unit.

The Ekip Hi-Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. The Hi-Touch platform extends the capabilities of the Ekip electronic protection system with advanced measurement, monitoring and power-quality functionality, making it particularly suitable for critical installations where detailed electrical-system supervision is required.

The E4.2H performance level provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, a short-time withstand current of 85 kA for 1 s and rear flat horizontal terminals, the 1SDA071218R1 provides robust protection for major industrial, infrastructure and critical-power switchboards.

Key Advantages

  • High-performance ABB SACE Emax 2 E4.2H air circuit breaker.
  • 4000 A rated uninterrupted current for high-capacity low-voltage distribution.
  • 100 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 85 kA breaking capacity at 500–690 V AC.
  • 85 kA rated short-time withstand current for 1 s.
  • Advanced Ekip Hi-Touch LSI electronic trip unit.
  • Long-time, short-time and instantaneous protection supports selective system coordination.
  • Hi-Touch functionality supports advanced measurement, monitoring and power-system supervision.
  • Fixed three-pole construction with rear flat horizontal terminals for high-current switchboard integration.

Key Features

  • ABB SACE Emax 2 E4.2H series.
  • 4000 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed installation version.
  • Ekip Hi-Touch LSI solid-state electronic release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • Overload release adjustable from 1600–4000 A.
  • Short-time delayed short-circuit release adjustable from 2400–40,000 A.
  • Instantaneous short-circuit release adjustable from 6000–60,000 A.
  • Rated operational voltage of 690 V AC.
  • 100 kA Icu at 400–440 V AC.
  • 85 kA Icu at 500–690 V AC.
  • 85 kA Icw for 1 s.
  • Rear flat horizontal main terminals.
  • Four change-over auxiliary contacts.
  • Circuit-breaker open/closed position indication.

Advanced Hi-Touch LSI Protection for 4000 A Distribution

The ABB SACE Emax 2 E4.2H is engineered for major low-voltage distribution points where very high continuous currents and substantial prospective fault levels require dependable interruption and withstand performance. Its combination of a 4000 A current rating, 100 kA breaking capacity at 400–440 V AC and 85 kA short-time withstand capability provides robust protection for high-capacity switchboards, transformers, busbars and major feeders.

The Ekip Hi-Touch LSI trip unit combines adjustable long-time overload, short-time delayed and instantaneous short-circuit protection with the advanced capabilities of ABB's Hi-Touch platform. The short-time function supports selective coordination with downstream protective devices, while enhanced measurement and monitoring capabilities make this configuration well suited to critical installations where both protection performance and detailed electrical-system supervision are priorities.

Typical Applications

  • High-current low-voltage main switchboards.
  • Industrial power distribution systems.
  • Main incomer and high-current feeder protection.
  • Manufacturing and process plant switchgear.
  • Large commercial and infrastructure installations.
  • Power distribution centres and substations.
  • Transformer secondary distribution systems.
  • Data centre and critical-power switchboards.
  • Heavy-industry electrical distribution.
  • Systems requiring selective short-circuit coordination.
  • Installations requiring advanced electrical measurement and monitoring.
  • OEM low-voltage switchboards and switchgear assemblies.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA071218R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Frame E4.2
Short-circuit performance level H
Rated current (In) 4000 A
Rated uninterrupted current (Iu) 4000 A
Current type AC
Number of poles 3
Installation Fixed
Trip unit Ekip Hi-Touch LSI
Release type Electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Integrated earth-fault protection No
Overload release setting range 1600–4000 A
Short-time delayed short-circuit setting range 2400–40,000 A
Instantaneous short-circuit setting range 6000–60,000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 525 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 400–440 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 500–690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 85 kA
Rated short-time withstand current (Icw), 3 s 75 kA
Main terminal position Rear
Terminal configuration Rear flat horizontal
Terminal type Bolt
Recommended main-circuit screw M12
Tightening torque 70 N·m
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Complete device with protection unit Yes
Motor drive integrated No
Motor drive optional Yes
Integrated undervoltage release No
DIN rail mounting No
Electrical durability at Ue ≤ 440 V 5000 cycles
Electrical durability at 500–690 V 4000 cycles
Electrical operating frequency 20 cycles per hour
Mechanical durability 15,000 cycles
Product net width 384 mm
Product net height 371 mm
Product net depth 270 mm
Product net weight 81 kg
EAN / GTIN 8015644750688
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071218R1?

The ABB 1SDA071218R1 is a SACE Emax 2 E4.2H fixed three-pole air circuit breaker rated at 4000 A and equipped with an Ekip Hi-Touch LSI electronic trip unit.

What protection functions does the Ekip Hi-Touch LSI trip unit provide?

The Ekip Hi-Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.

What is the breaking capacity of the ABB E4.2H 4000?

The E4.2H 4000 provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC.

What is the short-time withstand rating of the ABB 1SDA071218R1?

The breaker has a rated short-time withstand current of 85 kA for 1 s and 75 kA for 3 s, supporting demanding selective protection schemes.

Where is the ABB E4.2H 4000 Ekip Hi-Touch LSI typically used?

It is designed for high-current low-voltage distribution applications including industrial main switchboards, major incomers and feeders, transformer secondary systems, data centres, infrastructure installations, critical-power networks and OEM switchgear assemblies.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high-current switching, substantial short-circuit performance and advanced electronic protection, measurement and monitoring capabilities for dependable low-voltage power distribution in critical installations.