1SDA071202R1 ABB E4.2S 4000 Ekip Dip LSI 3p F HR Air Circuit Breaker

1SDA071202R1 ABB E4.2S 4000 Ekip Dip LSI 3p F HR Air Circuit Breaker

ABB 1SDA071202R1 Emax 2 E4.2S 4000 air circuit breaker, a 4000 A three-pole fixed ACB with Ekip Dip LSI electronic protection, 690 V AC rated voltage and up to 85 kA short-circuit breaking capacity.

SKU: 1SDA071202R1MPN: 1SDA071202R1
Price
List Price £22,198.70 ex VAT
Your Price (ex VAT) Save 25%
£16,649.03 25% OFF
You save £5,549.68 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £16,649.03
Trade pricing is personalised to your account

Manufacturer Lead Time

£16,649.03

Why Choose the ABB E4.2S 4000 Ekip Dip LSI 3p F HR Air Circuit Breaker?

The ABB E4.2S 4000 Ekip Dip LSI 3p F HR, order code 1SDA071202R1, is a high-performance Emax 2 air circuit breaker (ACB) designed for protection and switching in high-current low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, it combines a 4000 A rated uninterrupted current with substantial short-circuit performance for industrial, infrastructure and critical power installations.

This fixed three-pole circuit breaker incorporates the Ekip Dip LSI solid-state electronic trip unit, providing long-time overload, selective short-time and instantaneous short-circuit protection. Adjustable electronic protection enables the breaker to be coordinated with other protective devices, while the straightforward Ekip Dip interface supports efficient local configuration and commissioning.

With a rated uninterrupted current of 4000 A and a rated voltage of 690 V AC, the E4.2S provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. Its fixed three-pole construction and rear flat horizontal terminals provide a robust solution for integration into high-current low-voltage switchboards.

Key Advantages

  • High-current 4000 A Emax 2 air circuit breaker for demanding low-voltage distribution systems.
  • 85 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 66 kA ultimate short-circuit breaking capacity at 500–690 V AC.
  • Ekip Dip LSI electronic trip unit for overload and short-circuit protection.
  • Long-time, selective short-time and instantaneous protection functions.
  • 66 kA short-time withstand current for 1 s and 3 s supports selective system coordination.
  • Fixed three-pole construction with rear flat horizontal terminals for switchboard integration.
  • Robust Emax 2 design optimised for high-current industrial and infrastructure power distribution.

Key Features

  • ABB SACE Emax 2 E4.2S series.
  • 4000 A rated uninterrupted current.
  • Three-pole fixed configuration.
  • 690 V AC rated voltage.
  • 85 kA Icu at 400 / 415 / 440 V AC.
  • 66 kA Icu at 500 / 525 / 690 V AC.
  • 100% Ics-to-Icu ratio.
  • 66 kA Icw for 1 s and 3 s.
  • Ekip Dip LSI solid-state electronic release.
  • Long-time overload protection adjustable from 1600–4000 A.
  • Selective short-time protection adjustable from 2400–40000 A.
  • Instantaneous short-circuit protection adjustable from 6000–60000 A.
  • Rear flat horizontal terminal connections.
  • Four auxiliary change-over contacts.
  • Circuit-breaker open/closed position indication.
  • Optional motor operating mechanism.
  • Suitable for IT networks up to 690 V.
  • Designed in accordance with IEC requirements.

High-Current LSI Protection for Power Distribution

Air circuit breakers such as the ABB Emax 2 E4.2S protect high-current low-voltage distribution systems against overload and short-circuit conditions while providing controlled switching and isolation. With a 4000 A current rating and substantial fault-interruption capability, this E4.2S configuration is well suited to main distribution points, transformer secondaries and other high-current sections of electrical installations.

The Ekip Dip LSI electronic trip unit combines long-time overload protection with selective short-time and instantaneous short-circuit protection. Adjustable protection thresholds support coordination between upstream and downstream protective devices, while the Ekip Dip interface provides a straightforward method of configuring essential protection settings directly at the circuit breaker.

Typical Applications

  • Main low-voltage switchboards and power distribution boards.
  • High-current industrial electrical distribution systems.
  • Manufacturing and process facilities.
  • Data centres and critical power infrastructure.
  • Large commercial and infrastructure installations.
  • Transformer secondary and main incomer protection.
  • High-current feeder protection.
  • Electrical systems requiring selective overload and short-circuit protection.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA071202R1
EAN 8015644750527
Product type Air circuit breaker (ACB)
Frame E4.2
Short-circuit performance level S
Rated uninterrupted current (Iu) 4000 A
Rated voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) 85 kA at 400 / 415 / 440 V AC
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw) 66 kA for 1 s; 66 kA for 3 s
Number of poles 3
Current type AC
Trip unit Ekip Dip LSI
Release type Solid-state electronic
Protection functions Long-time overload, selective short-time and instantaneous short circuit
Overload release adjustment 1600–4000 A
Short-time delayed short-circuit adjustment 2400–40000 A
Instantaneous short-circuit adjustment 6000–60000 A
Integrated earth-fault protection No
Mounting type Fixed
Terminal connection Rear flat horizontal
Terminal type Bolt
Recommended main circuit screw M12
Tightening torque 70 N·m
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Motor drive integrated No
Motor drive optional Yes
Dimensions (H × W × D) 371 × 384 × 270 mm
Net weight 56 kg
Suitable for IT networks Yes, up to 690 V
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA071202R1 used for?

The ABB 1SDA071202R1 is an Emax 2 air circuit breaker designed for switching and protection of high-current low-voltage electrical distribution systems, including main incomers, transformer secondaries and high-current feeders.

What is the current rating of the ABB E4.2S 4000?

The circuit breaker has a rated uninterrupted current of 4000 A, making it suitable for high-current industrial, infrastructure and critical power distribution systems.

What is the breaking capacity of the ABB 1SDA071202R1?

The E4.2S 4000 provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, with a rated short-time withstand current of 66 kA for 1 s and 3 s.

What protection does the Ekip Dip LSI trip unit provide?

The Ekip Dip LSI electronic trip unit provides adjustable long-time overload, selective short-time and instantaneous short-circuit protection for coordinated protection of low-voltage electrical distribution systems.

Is the ABB 1SDA071202R1 fixed or withdrawable?

The 1SDA071202R1 is a fixed three-pole air circuit breaker equipped with rear flat horizontal terminals for integration into low-voltage switchboards.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high-current capability, dependable short-circuit performance and flexible electronic protection for demanding industrial, infrastructure and critical low-voltage power distribution applications.