ABB 1SDA071193R1 is a SACE Emax 2 E4.2N 4000 A fixed three-pole air circuit breaker with rear horizontal terminals, an Ekip Dip LSIG solid-state electronic trip unit and 66 kA breaking capacity.
£14,894.96
The ABB E4.2N 4000 Ekip Dip LSIG 3p FHR, order code 1SDA071193R1, is a high-current SACE Emax 2 air circuit breaker (ACB) designed for reliable protection, switching and isolation in demanding low-voltage power distribution systems. Rated at 4000 A, this three-pole fixed circuit breaker combines the E4.2N frame with ABB's Ekip Dip LSIG solid-state electronic trip unit.
The Ekip Dip LSIG release provides comprehensive long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection. This combination provides adjustable electronic protection against the principal electrical fault conditions encountered in high-current distribution systems while supporting selective coordination between upstream and downstream protective devices.
This configuration is a fixed three-pole breaker equipped with rear horizontal (HR) terminals. The E4.2N frame provides a 66 kA breaking capacity and is rated for operation at up to 690 V AC, making the 1SDA071193R1 suitable for substantial industrial, commercial, infrastructure and critical power distribution installations.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage electrical systems against overloads and short circuits while providing switching and isolation of major distribution circuits. The E4.2N frame combines a substantial 4000 A current rating with 66 kA breaking capability for demanding main incomers, transformer-fed switchboards and high-current distribution feeders.
The Ekip Dip LSIG trip unit extends protection beyond standard overload and short-circuit functions by incorporating both short-time and earth-fault protection. This comprehensive arrangement supports selective coordination and allows a correctly engineered electrical system to isolate faults effectively while helping maintain continuity of supply to unaffected sections of the installation.
| Series | SACE Emax 2 |
|---|---|
| Frame | E4.2N |
| ABB order code | 1SDA071193R1 |
| EAN / GTIN | 8015644750435 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated current (In) | 4000 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LSIG |
| Release type | Solid-state electronic |
| Protection functions | L, S, I and G |
| Overload protection setting range | 1600–4000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Breaking capacity | 66 kA |
| Current type | AC |
| Earth-fault protection | Integrated G function |
| Installation | Fixed |
| Version | F |
| Terminal configuration | Rear flat horizontal (HR) |
| Connecting capacity | 4000 mm² |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Mechanical durability | 15000 cycles |
| Electrical durability at ≤440 V | 5000 cycles |
| Electrical durability at 500–690 V | 4000 cycles |
| Power loss | 465 W |
| Product net width | 384 mm |
| Product net height | 371 mm |
| Product net depth | 270 mm |
| Product net weight | 56 kg |
| Country of origin | Italy |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071193R1 is a SACE Emax 2 E4.2N fixed three-pole air circuit breaker rated at 4000 A and equipped with an Ekip Dip LSIG solid-state electronic trip unit.
The Ekip Dip LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The circuit breaker has a rated uninterrupted current of 4000 A.
The ABB E4.2N 1SDA071193R1 has a specified breaking capacity of 66 kA.
The circuit breaker is rated for operational voltages up to 690 V AC, with a rated insulation voltage of 1000 V AC.
Yes. The G function within the Ekip Dip LSIG release provides integrated earth-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
The 1SDA071193R1 is a fixed-version circuit breaker intended for permanent installation within a low-voltage switchboard.
This configuration is a fixed circuit breaker with rear horizontal terminals, providing rear-facing main connections suitable for integration with switchboard busbars and conductors.
ABB SACE Emax 2 air circuit breakers combine high-current switching and protection with proven electronic trip technology, selective protection functions and robust short-circuit performance for demanding industrial, commercial, infrastructure and critical power distribution installations worldwide.