Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071192R1 is a SACE Emax 2 E4.2N 4000 A fixed three-pole air circuit breaker with rear horizontal terminals, an Ekip Dip LSI electronic trip unit and 66 kA ultimate short-circuit breaking capacity at 400/415 V AC.
£14,383.35
The ABB E4.2N 4000 Ekip Dip LSI 3p FHR, order code 1SDA071192R1, is a high-current SACE Emax 2 air circuit breaker (ACB) designed for reliable protection, switching and isolation in demanding low-voltage power distribution systems. Rated at 4000 A, this three-pole fixed circuit breaker combines the E4.2N frame with ABB's Ekip Dip LSI solid-state electronic trip unit.
The Ekip Dip LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. Adjustable overload, delayed short-circuit and instantaneous protection settings allow the breaker to be coordinated with downstream protective devices, making it well suited to main incomers and high-current feeders where selective fault clearance is important.
This configuration is a fixed three-pole breaker equipped with rear horizontal (HR) terminals. The E4.2N provides an ultimate short-circuit breaking capacity of 66 kA across key low-voltage AC ratings up to 690 V AC, together with a rated short-time withstand current of 66 kA for 1 s, making the 1SDA071192R1 suitable for substantial industrial, commercial and infrastructure distribution systems.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage electrical systems against overloads and short circuits while providing switching and isolation of major distribution circuits. The E4.2N frame combines a substantial 4000 A current rating with 66 kA short-circuit breaking performance across a wide range of AC system voltages, making it suitable for major main incomers and distribution feeders.
The Ekip Dip LSI trip unit adds adjustable short-time protection between the long-time overload and instantaneous protection functions. This enables more effective selective coordination between upstream and downstream protective devices, helping a correctly engineered distribution system isolate the circuit closest to a fault while maintaining supply to unaffected sections.
| Series | SACE Emax 2 |
|---|---|
| Frame | E4.2N |
| ABB order code | 1SDA071192R1 |
| EAN / GTIN | 8015644750428 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated current (In) | 4000 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | L, S and I |
| Overload release setting range | 1600–4000 A |
| Short-time delayed short-circuit setting range | 2400–40000 A |
| Instantaneous short-circuit setting range | 6000–60000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw, 1 s) | 66 kA |
| Rated short-time withstand current (Icw, 3 s) | 50 kA |
| Current type | AC |
| Integrated earth-fault protection | No |
| Installation | Fixed |
| Terminal configuration | Rear flat horizontal (HR) |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker position indication | Open / closed |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Mechanical durability | 15000 cycles |
| Electrical durability at ≤440 V | 5000 cycles |
| Electrical durability at 500–690 V | 4000 cycles |
| Power loss | 465 W |
| Dimensions (W × H × D) | 384 × 371 × 270 mm |
| Product net weight | 56 kg |
| Standard | IEC |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071192R1 is a SACE Emax 2 E4.2N fixed three-pole air circuit breaker rated at 4000 A and equipped with an Ekip Dip LSI solid-state electronic trip unit.
The Ekip Dip LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
The circuit breaker has a rated uninterrupted current of 4000 A.
The E4.2N 1SDA071192R1 provides an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC and retains a 66 kA rating at 690 V AC.
The circuit breaker has a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.
No. The supplied Ekip Dip LSI configuration provides long-time, short-time and instantaneous overcurrent protection; integrated G earth-fault protection is not included in this LSI configuration.
The 1SDA071192R1 is a fixed-version circuit breaker designed for permanent installation within a low-voltage switchboard.
This configuration is a fixed circuit breaker with rear horizontal terminals, providing rear-facing main connections suitable for integration with switchboard busbars and conductors.
ABB SACE Emax 2 air circuit breakers combine high-current switching and protection with proven electronic trip technology and robust short-circuit performance for demanding industrial, commercial, infrastructure and critical power distribution installations worldwide.