ABB 1SDA071191R1 SACE Emax 2 E4.2N fixed three-pole air circuit breaker with Ekip Dip LI electronic protection, 4000 A rated current and 66 kA breaking capacity at 440 V AC.
£14,061.80
The ABB E4.2N 4000 Ekip Dip LI 3p FHR, order code 1SDA071191R1, is a high-current SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. This fixed three-pole E4.2 breaker combines a 4000 A rated uninterrupted current with ABB's Ekip Dip LI solid-state electronic trip unit.
The Ekip Dip LI release provides long-time overload and instantaneous short-circuit protection. Its electronic protection functions are configured using DIP switches, providing a straightforward and dependable solution for applications requiring adjustable overload protection and rapid interruption of high-level short-circuit faults.
The E4.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 440 V AC together with a rated short-time withstand current of 66 kA for 1 s. Supplied as a fixed three-pole breaker with rear horizontal terminals, four auxiliary contacts and open/closed circuit-breaker position indication, the 1SDA071191R1 is engineered for major industrial and infrastructure distribution switchboards.
The ABB SACE Emax 2 E4.2N is engineered for major low-voltage distribution points where very high continuous currents require robust switching and electronic protection. Its 4000 A current rating, 66 kA breaking capacity at 440 V AC and 66 kA short-time withstand capability make it suitable for protecting high-capacity switchboards, busbars, transformers and major outgoing circuits.
The Ekip Dip LI trip unit combines adjustable long-time overload protection with rapid instantaneous short-circuit protection. This focused LI configuration is suited to installations where straightforward electronic protection is required without short-time delayed or integrated earth-fault functions, while the Emax 2 platform provides a robust basis for high-current power distribution.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA071191R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Frame | E4.2 |
| Performance level | N |
| Rated uninterrupted current (Iu) | 4000 A |
| Current type | AC |
| Number of poles | 3 |
| Installation | Fixed |
| Trip unit | Ekip Dip LI |
| Release type | Solid-state electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Short-time delayed protection | No |
| Integrated earth-fault protection | No |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Main terminal position | Rear |
| Terminal orientation | Horizontal |
| Configuration | Fixed breaker, rear connection |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Product net width | 384 mm |
| Product net height | 371 mm |
| Product net depth | 270 mm |
| Product net weight | 56 kg |
| Minimum order quantity | 1 piece |
| Customs tariff number | 85362090 |
| EAN / GTIN | 8015644750411 |
| ABB EcoSolutions | Yes |
| Recyclability rate | 79.3% |
| RoHS status | Compliant with EU Directive 2011/65/EU and amendment 2015/863 |
The ABB 1SDA071191R1 is a SACE Emax 2 E4.2N fixed three-pole air circuit breaker rated at 4000 A and equipped with an Ekip Dip LI solid-state electronic trip unit.
The Ekip Dip LI release provides long-time overload and instantaneous short-circuit protection, with protection settings configured using DIP switches.
The E4.2N 4000 has an ultimate short-circuit breaking capacity of 66 kA at 440 V AC and a rated short-time withstand current of 66 kA for 1 s.
No. This model uses an LI protection configuration, providing long-time overload and instantaneous short-circuit protection without integrated earth-fault protection.
It is designed for high-current low-voltage distribution applications including industrial main switchboards, high-capacity incomers and feeders, transformer secondary systems, infrastructure installations, critical-power networks and OEM switchgear assemblies.
ABB SACE Emax 2 air circuit breakers combine high-current switching, dependable short-circuit performance and proven electronic protection for reliable low-voltage power distribution in demanding industrial, commercial and infrastructure installations.