1SDA071178R1 ABB E4.2V 3200 Ekip Hi-Touch LSI 3p F HR Air Circuit Breaker

1SDA071178R1 ABB E4.2V 3200 Ekip Hi-Touch LSI 3p F HR Air Circuit Breaker

ABB 1SDA071178R1 E4.2V 3200 Ekip Hi-Touch LSI is a fixed three-pole 3200 A SACE Emax 2 air circuit breaker with rear horizontal terminals, 150 kA breaking capacity at 400–440 V AC and advanced electronic long-time, short-time and instantaneous protection.

SKU: 1SDA071178R1MPN: 1SDA071178R1
Price
List Price £24,108.68 ex VAT
Your Price (ex VAT) Save 25%
£18,081.51 25% OFF
You save £6,027.17 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £18,081.51
Trade pricing is personalised to your account

Manufacturer Lead Time

£18,081.51

Why Choose the ABB E4.2V 3200 Ekip Hi-Touch LSI 3p F HR Air Circuit Breaker?

The ABB E4.2V 3200 Ekip Hi-Touch LSI 3p F HR, order code 1SDA071178R1, is a high-performance 3200 A three-pole air circuit breaker (ACB) designed for advanced protection, switching and isolation in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines the high-breaking-capacity E4.2V platform with fixed mounting, rear horizontal terminals and the advanced Ekip Hi-Touch LSI electronic trip unit.

The E4.2V 3200 provides an ultimate short-circuit breaking capacity of 150 kA at 440 V AC together with a rated short-time withstand current of 100 kA for 1 s. This exceptional fault-handling capability makes the breaker particularly suitable for main distribution systems where very high prospective short-circuit currents require robust and dependable interruption.

Protection is provided by the Ekip Hi-Touch LSI solid-state electronic release, delivering long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. The 1SDA071178R1 is supplied as a fixed three-pole breaker with rear horizontal terminals and includes four auxiliary change-over contacts plus open/closed breaker position indication.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding low-voltage distribution systems.
  • 3200 A rated uninterrupted current for high-current applications.
  • Ekip Hi-Touch LSI electronic trip unit for advanced protection, measurement and monitoring.
  • Long-time, short-time and instantaneous protection for effective circuit coordination.
  • Exceptional 150 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 100 kA rated short-time withstand current for 1 s.
  • Fixed three-pole construction with rear horizontal terminals for switchboard integration.

Key Features

  • ABB SACE Emax 2 E4.2V series.
  • 3200 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed mounting design.
  • Rear horizontal main terminals.
  • Ekip Hi-Touch LSI solid-state electronic release.
  • Long-time overload protection.
  • Short-time selective short-circuit protection.
  • Instantaneous short-circuit protection.
  • 150 kA Icu at 400–440 V AC.
  • 100 kA Icw for 1 s.
  • Rated operational voltage up to 690 V AC.
  • Four auxiliary change-over contacts.
  • Open/closed circuit-breaker position indication.
  • Optional motor operating mechanism.
  • IP30 degree of protection.

Advanced Selective Protection for High-Fault-Level Distribution

ABB SACE Emax 2 air circuit breakers provide switching, isolation and electronic circuit protection for high-current low-voltage networks. The E4.2V 3200 combines a 3200 A continuous-current rating, 150 kA breaking capacity at 400–440 V AC and 100 kA one-second short-time withstand capability, making it particularly well suited to distribution systems with very high prospective fault currents.

The Ekip Hi-Touch LSI release provides long-time overload, short-time selective and instantaneous short-circuit protection together with advanced measurement and monitoring capabilities. Short-time protection supports selective coordination with downstream protective devices, helping isolate faults while maintaining continuity of supply to unaffected parts of the electrical installation.

Typical Applications

  • Main low-voltage distribution switchboards.
  • High-current industrial power distribution systems.
  • Manufacturing and process plants.
  • Large commercial and infrastructure installations.
  • Transformer-fed distribution networks.
  • Critical power and utility installations.
  • High-fault-level switchgear and power distribution assemblies.

Technical Specifications

Series SACE Emax 2
Order code 1SDA071178R1
EAN 8015644750282
Product type Air circuit breaker (ACB)
Rated uninterrupted current (Iu) 3200 A
Rated operational voltage up to 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 150 kA
Rated short-time withstand current (Icw, 1 s) 100 kA
Number of poles 3
Current type AC
Mounting Fixed
Main terminal arrangement Rear horizontal
Main circuit connection Bolt connection
Trip unit Ekip Hi-Touch LSI
Release type Solid-state electronic
Protection functions Long-time, short-time and instantaneous
Integrated earth-fault protection No
Overload release setting from 1280 A
Short-time delayed short-circuit setting from 1920 A
Instantaneous short-circuit setting from 4800 A
Auxiliary contacts 4 change-over contacts
Breaker position indication Open / closed
Integrated motor operator No
Optional motor operator Yes
Degree of protection IP30
Power loss 425 W
Dimensions (W × H × D) 384 × 371 × 270 mm
Net weight 56 kg
Electrical durability 7000 cycles
Mechanical durability 20000 cycles

Frequently Asked Questions

What is the ABB 1SDA071178R1 used for?

The ABB 1SDA071178R1 is a 3200 A air circuit breaker designed for switching, isolation and advanced protection of high-current low-voltage distribution circuits, particularly where very high prospective short-circuit currents are present.

What protection unit is fitted to the ABB 1SDA071178R1?

The breaker is fitted with an ABB Ekip Hi-Touch LSI electronic trip unit, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection together with advanced measurement and monitoring functionality.

What is the rated current of the ABB E4.2V 1SDA071178R1?

The breaker has a rated uninterrupted current of 3200 A.

Is the ABB 1SDA071178R1 fixed or withdrawable?

The 1SDA071178R1 is a fixed three-pole air circuit breaker equipped with rear horizontal main terminals.

What is the breaking capacity of the ABB E4.2V 3200?

The E4.2V 3200 provides an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC together with a rated short-time withstand current of 100 kA for 1 s, making it suitable for demanding high-fault-level power distribution systems.

Trusted by Power Distribution Professionals Worldwide

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, sophisticated measurement and monitoring, selective fault coordination and exceptional short-circuit performance for dependable operation in demanding low-voltage power distribution systems.